AutoGate GENESIS User manual

AUTOGATE INC.
RETROFIT INSTRUCTIONS TO INSTALL A GENESIS BOARD REPLACING A LIFTMASTER BOARD
Congratulations on your purchase of our new state of the art GENESIS control board
kit for replacing the LiftMaster control board which has been discontinued.
PLEASE READ THESE INSCTRUCTIONS THOURHLY BEFORE PROCEEDING.
Included in your kit are the following items:
•GENESIS Control Board (w/terminal blocks)
•RSP-320-27 Power Supply w/(2) mounting screws & (2) Mounting brackets
•6’ RED & BLACK wire (power from the power supply to the board-replaces YELLOW wires)
•6’ BLACK & WHITE AC Power wires 14 gauge (power from AC box to power supply if needed)
•6’ GREEN ground wire
•DC Troubleshooting light w/4’ of 24 gauge 2-conductor RED & BLACK wire
•10Amp Glass fuse (Replaces the AC 3Amp in the face of the Battery Tray)
•Miscellaneous wire connectors and cable ties
1. Turn off all power (AC at Outlet Box & DC Toggle switch under Control Box). For extra precaution, turn off
the main dedicated breaker feeding the operator outlet box.
2. CAUTION: Additional accessories may have been installed and powered off the AC transfomer by a 3rd
party! These will need to be handled by the onsite technichian doing the upgrade.
3. Remove transformer cover. Unplug the wires, unbolt, remove transformer, discard or recycle.
4. When removing the YELLOW transformer wires and discarding, also remove the small RED & BLACK wires
going to the AC POWER INDICATOR LIGHT (If used). These wires will be re-connected on the GENESIS
board “MAIN POWER LOSS/LOW BATTERY” & COM (See P3). The AC Indicator light will be replaced with a
DC LED FAULT light. It will FLASH where there are issues. Review the GENESIS Board menus for more
details on what causes the light to flash and the different types of flashing.
LIFMASTER BOARD GENESIS BOARD RSP-320-27 POWER SUPPLY
Optional location for
new power supply. Fan
facing out. Secure on top
tubing to back skin.
Remove Transformer
Cover & Transformer.
Transformer: Remove
wires, Unbolt, remove
transformer discard or
recycle.

5. Connect the original or supplied AC BLACK & WHITE wires that fed the transformer to the Power Supply
using spade connectors. BLACK to the L-Line, WHITE to the N-Neutral.
6. Connect the supplied 14-gauge GREEN Ground wire to the power supply ground. Run the GREEN Ground
wire along the BLACK & WHITE wires back to the AC Outlet box and connect to the AC Outlet box GREEN
Ground wire.
7. Using the supplied new RED & BLACK wires connect them to the Power Supply, RED to positive, BLACK to
negative.
8. The RSP-320-27 has a universal AC input switch. It can be set to 110 or 230 AC volts. Any voltage over 120
needs to be single phase. Make sure switch is set for your proper AC voltage.
9. We suggest Installing the new power supply by securing it to the frame on top of the back tubing above the
Battery Shelf in the same area the transformer was located but towards the corner (see above picture)
using one or two of the included mounting brackets. The brackets attach to the power supply with metric
M4 x 6 mm screws. Use the self-tapping screws provided to attach to the battery shelf/frame or skin.
Options: install on the back panel next to the AC outlet or installed UNDER the Battery Shelf. Make sure
the fan is not blocked. NOTE: Leave the ORIGINAL AC and DC switches in place!
10. On the old LiftMaster board, Remove the J2 terminal strip (4 terminals: Limit Switches wires) from the top
left side of the board.
11. Remove the J5 (12 terminals: Input, reversing devices & grounds) terminal strip at the top right side of the
board.
12. Remove the BROWN wire from the J1 terminal
13. Mark and unscrew the wires from the J4 terminal strip at the bottom of the board.
14. Remove and save screws from side of control box mounting the control board. Then, using a pair of needle
nose pliers, squeeze the tabs together on the stand-offs to release the control board.
J2: LIMIT SWITCH WIRES J5: ACCESSORY INPUT J4: MOTOR & POWER Bolts
15. Remove the LiftMaster board. Align the GENESIS board over the stand-offs and push down to lock in place.
A small screwdriver may be used to pry open the lock tabs on the stand-offs.
Mounting bracket & mounting holes
L-Line (BLACK)
N-Neutral (WHITE)
G-Ground (GREEN)
-V (BLACK)
+V (RED)
VOLTAGE ADJUSTMENT
POT

16. Using the original screws and nuts, attach the mounting bracket to the side of the control box.
17. Attach BATTERY RED & BLACK wires to the P11 terminal marked BATTERY +/-. Leave the 24 VDC MAIN
POWER toggle switch in the battery positive wire. This will allow turning the batteries on/off without
having to remove wires.
18. Attach the DC RED & BLACK power supply wires from the power supply to the 24V DC terminals on the P11
terminal strip. Make sure to follow the correct polarity!
19. Attach the Motor wires to the MOTOR A/B terminals
20. Wires: RH OPERATOR MOTOR: A=BLUE, B=ORANGE.LH OPERATOR MOTOR: A=ORANGE, B=BLUE
21. Attach the RED & BLACK ACCESSORY POWER STRIP wires to the P9 terminal strip (24VDC). RED to
POSITIVE, BLACK to COMMON.
22. Transfer the limit switch wires from the LiftMaster terminal strip J2 to the GENESIS P1 terminals (see
above) LIMIT input terminals. These will be the in the same position. Left end wire is the WHITE OPEN
limit wire. The second terminal is the RED CLOSE limit wire. The third terminal is for the 2 Black wires
(commons) from the limit switches. WARNING! DO NOT TURN ON ANY POWER AT THIS TIME!
23. Remove wires from the J5 12 terminal strip taken from the LiftMaster board earlier. One by one insert
them in their proper location on the GENESIS P2 terminal strip (see below). Any wires that were in
terminals #1, #2, or #3 on the J5 LM board, put into Open 1 or Open 2. Any wire in terminal #4 on the J5
LM board, put into the OP/CL PGM. Wires located in terminal #5 on the J5 of the LM board will be put into
REV/INT. If there is a wire in the J5 #6, move it to the CLOSE input on GENESIS. Normally, the FE/BACK &
SHADOW are not used. If they are, use the same input as marked on GENESIS.
P11
P9
P2
P1

20. Now attach the BROWN wire into the 6th terminal down on the P3 terminal strip on the left side of the
GENESIS board. This is the UL alarm wire. The ground for the alarm is already wired to the ground on the
auxiliary power strip to the left of the board. If the there is an auxiliary limit switch kit, the power wires for
this will be removed from the LM BATTERY terminals and attached to the 24 VDC & COM terminals on the
P9 (see graphic above) terminal strip.
FAULT LIGHT CONNECTION
COMMON
MAIN POWER LOSS/LOW BATTERY
J2: LIFMASTER PRIMARY/SECONDARY (M/S) P8: GENESIS PRIMARY/SECONDARY
21. If you are replacing both boards in a PRIMARY/SECONDARY DUAL gate system, remove the cross-connected
wires between the gates, but do not reconnect yet. After connecting control wires to the GENEISIS board,
use 3 of the cross-connect wires for the DUAL GATE COMMUNICATION connection on P8. If you have a
shielded multi-conductor wire cable for the connection, connect the SHIELD to a COMMON on the
PRIMARY gate only! Then use any three remaining wires for the PRIMARY/SECONDARY connection. A to A,
B to B and C to C.
22. NOTE: DO NOT re-connect the CYCLE COUNTER, AMP METER (located in the electrical box door), both of
these items are built into the GENESIS board. (See screens below)
23. If you had a VOLTAGE CLAMP ACCESSORY board, do not re-connect it as well, just toss it.
24. POWERING UP YOUR SYSTEM: If main circuit breaker has been turned off, turn it back on. Turn on AC
power switch and turn on the DC battery toggle switch. Note: IF YOUR BOARD WAS FACTORY PRESET, the
board should power up and display the TITLE screen with the GENESIS Version number (Ver. #.#). After 6
to 8 seconds the screen will change to the MAIN screen showing the Line Voltage (DC) from the AC/DC
Power Supply, Battery Voltage (DC), Motor Amps, Cycles and Close Timer.If your board was not Factory
preset, you will get a FAULT warning screen with this message: LPS SENSOR NOT DETECTED BY THE
GENESIS BOARD! You will need to call AutoGate (800-944-4283) for assistance in programming your board
for LIMIT SWITCH use. WARNING! DO NOT OPERATE YOUR GATE AT THIS TIME!
25. Scroll down to TIMER SETTINGS to set the AUTO CLOSE if your system was set to close automatically.
P3
AutoGate Ver A#.#
GENESIS 01:22am
Line Voltage 25.39*
Batt Voltage 26.67
Motor 0.00 Amp
Cycles 0 T=00
Auto Close: Off<
Auto Delay: 03
Open Time: 10
Close Time: 10
Timer Settings
P8

26. Follow the enclosed GENESIS board instructions (included) to setup ALL options, accessories and reversing
equipment paramaters
27. Change the BATT: Bulk Charge >Power SUPPLY to “NORMAL”(may already be done by the factory)
28. The OUTPUT VOLTAGE is adjustable between 27-31 Vdc. We recommend setting it to 29.5 volts.
29. You are now ready to fully test your gate system.
a. Check your board programming for to make sure you are set for LIMIT SWITCHES and your
MONITORED INPUTS are all set to OFF. If not, you will need to contact AutoGate for the KEY
code to change those status’s.
b. If your GENESIS board was FACTORY PRESET your operating speed should be set for
OPENING and CLOSING speed of 110%, if not change the speed to 110%.
c. Now cycle the gate and record your OPENING & CLOSING cycle times.
d. Set the OPEN RUN and CLOSE RUN times for 2 seconds LESS than the cycle times you just
recorded. For example, if the cycle time was 12 seconds, set the run times to 10.
a. Press the GREEN OPEN button, if you set the CLOSE TIME the gate should time out and close. If you
have not set the CLOSE TIME, it is found under TIMER SETTINGS.
b. Press the YELLOW CLOSE button to close the gate.
c. Test ALL Accessory & Reversing (Photo Beams, Loops, Keypad, Card Readers, etc.) devices to make
sure they are operational.
Note: There should not be any accessory indicator or warning lights on.
27. For the balance of the GENESIS board instructions and set up, please review the GENESIS CONTROL
BOARD document attached.
28. Refer to TROUBLESHOOTING guide or for more information, go to GENESIS Board Instructions or 2490
Installation manual which is located online at https://www.autogate.com/vertical-pivot-gates/ under the
INFORMATION tab.
For further assistance, call AutoGate 800-944-4283 and ask for Tech help.
Maintenance
Batt: Float Charge
>PWR SUPPLY: “Normal”
Batt V Check Freq:
50 Cycles
GENESIS BOARD OPERATION BUTTONS
GREEN: OPEN (Will also act as a constant pressure and override defaults to OPEN the gate)
YELLOW: CLOSE (Will also act as a constant pressure and override defaults to OPEN the gate)
RED: STOP (Stops the gate in either direction)
WHITE: RESET (Resets the board in the event of a program change or fault)
>Limit Switches:
Yes
Open Obstruction:
>Edge: Off
Beam: Off
Close Obstruction:
>Edge: Off
Beam: Off

OVERVIEW: The GENESIS board has a 4 line 20 characters per line LCD backlit screen. At power up, the display will show
the AutoGate and GENESIS branding, along with the program version number and the current time. After 5 or 6 seconds,
this will then shift to the HOME screen, or base operational data shown below under MAIN Screen.
TITLE Screen MAIN Screen Example 1 Example 2
JOG/SELECT Knob
SCROLLING: Rotating the Jog/Select knob clockwise will scroll through the adjustments on that screen. If there is
another screen in that sub-section, continue to scroll after the last character, the screen will automatically change to the
next screen. When at the last screen of a sub-section, a long push, (approx. 1 second), of the Jog/Select knob will return
to the sub-section main screen. Sub-sections can be scrolled in either direction by turning the Jog/Select knob clockwise
or counter-clockwise.
JOG/SELECT ACTIONS: Two different actions can occur on the screens:
1) If the cursor is pointed to a descriptive phrase (Example #1), then a momentary push of the Jog/Select knob will move
the cursor to the adjustable parameter. Then turning the Jog/Select knob will change the value.
2) When the cursor is pointed to left side of a value or parameter to be changed, (example #2), use quick momentary push
of the Jog/Select knob to move the cursor. The cursor will move to the right side of the value (<). Turning the Jog/Select
knob will change the value. When done, again, a quick momentary push of the Jog/Select knob moves the cursor back to
the left.
SCREEN MENUS
MAIN SCREEN
CALENDAR/TIME
AutoGate Ver. A#.#
GENESIS 01:22am
Line Voltage 25.39*
Batt Voltage 26.67
Motor 0.00 Amp
Cycles 0 T=00
Open Time: 10
Close Time: 10
>Auto Close: Off
Auto Delay: 03
Open Time: 10
Close Time: 10
Auto Close: Off<
Auto Delay: 03
JOG/SELECT Control Knob: The screens are accessed and modified by a JOG/SELECT control
knob. Turning the Jog/Select dial will scroll through the sub-menu selections. When a sub-
menu is showing, a quick momentary press of the Jog/Select knob will display the first
screen in that sub-menu. Turning the Jog/Select knob will move the cursor (>) through the
adjustable parameters.
Note: Gate will not be operational while in programming mode. When in programming
mode there will be a series of flashing lights at all times above the LCD screen.
Line Voltage 25.39*
Chrg Voltage 26.67
Motor 0.00 Amps
Cycles 0 T-00
Line voltage: From the Power supply. (Normal voltage should be 29 to 30, Recommended to 29.5Vdc)
Charge/Battery voltage: When AC present: Charging Voltage to batteries, When on DC only: Actual
battery voltage. (Normal Battery voltage is 26.4 to 26.8) (Normal Charging Voltage is 26.0 to 28.5 volts)
Note: * Indicates CURRRENT POWER source
Motor: Displays actual motor amperage during cycling
Cycles/Position: A cycle count is considered a complete OPEN & CLOSE. Hold the Jog/Select button down
and the Cycles will change and show the gate position “0” being CLOSED and “90” being full OPEN.
T=00: Operation count in seconds for both open and close cycles and also counts down the “Timer to
Close” (CLOSE TIME) time. NOTE: 0-90 Display is not available with LIMIT SWITCHES.
Calendar/Time
Set the time, date and day of the week. This is an important feature.
It will affect the data in all FAULT and OPERATION logs as well as any
TIME functions to hold the gate open on any given day(s).
Note: Screens in ORANGE are WARNING screens that will appear when there is an issue.
GENESIS CONTROL BOARD

CALENDAR/TIME (cont.)
TIMER SETTINGS
>01:14:58 am
03/21/19 Th
Timer Settings
Set the time, date and day of the week.
>Auto Close: Off<
Auto Delay: 03
Open Time: 10
Close Time: 10
>Motion Alarm: On
Pre-Op Alarm: 0
Pre-Cl Alarm: 0
Monday
>On
Open: 08:00 am
Close: 06:00 pm
Thursday 2
OFF<
Open: 06:00 am
Close: 05:00 pm
(Same as above) Each day has the ability to set a second HOLD OPEN and CLOSE time.
Set the time, date and day of the week individually. Two complete options for each day: SUNDAY to
SATURDAY and SUNDAY 2 to SATURDAY 2.
MOTION ALARM: Turns ON and OFF an alarm or Strobe Light.
PRE-OPEN ALARM: Turns on the alarm from 1 to 5 seconds before the gate opens.
PRE-CLOSE ALARM: Turns on the alarm from 1 to 5 seconds before the gate closes.
*Note: This time value must be equal to or shorter than the AUTO CLOSE TIME value.
AUTO CLOSE TIME: Default is ON from 1 to 120 seconds, OFF requires a CLOSE command.
CLOSE TIME DELAY: Timer to close after all inputs are clear. Settable from 1 to 120 seconds.
(Note: If using the “Auto Close” in a PRIMARY/SECONARY gate system, only set the PRIMARY “Auto
Close” to on, leave the Secondary off).
OPEN/CLOSE TIME: Full Speed Run Time, Set this when the slow down is to start. Slows down after time
value expires. This option is only active when LIMIT SWITCHES are used. Set this time for TWO SECONDS
less than recorded cycle time in your initial test of your gate!
TIMER SETTINGS: 4 Sub Menus to set OPEN & CLOSE times, MOTION ALARM times and 7-DAY TIMERS
>Automatic Schedule:
Off
Automatic Schedule:
>7 days a week
Automatic Schedule:
>Mon-Fri only
Automatic Schedule:
>Sat & Sun only
Automatic Schedule:
>Custom-Daily
AUTOMATIC SCHEDULE: Sets the gate to lock OPEN and CLOSE daily, 7 Days a week, Monday thru Friday
or Saturday & Sunday only
Each day has the ability to set a HOLD OPEN and CLOSE time.
GENESIS CONTROL BOARD

OPERATOR CONTROL
OPTIONS: GATE SPEED, LIMIT SWITCHES, HALL (A & B), OPEN/CLOSE, POSITION SETTINGS
Operator Control
>Gate Opening Speed:
110%
Gate Closing Speed:
110%
DECEL SPEED: Sets the time value on setting the gate speed from full speed to slow speed. The scale is
7 to 20, with 7 being the fastest and 20 being the slowest.
>Open Decel: 10
Close Decel: 10
LIMIT SWITCHES: Default is “NOT USED”. You will need to contact AutoGate if your board was not set
at the factory to LIMIT SWITCHES before you go received it. Choices are: NORMALLY OPEN,
NORMALLY CLOSED, HALL A & HALL B. Normally open & close will choose the type of wired Limit
Switch to be used.
>Limit Switches:
Not Used
WARNING! No Limit
Position Sensor
detected! Gate will
not operate!
GATE SPEED: Default 100%, any percentage less than 100% down to 75% will slow the gate opening
and closing down accordingly. Downward speed to fast will cause a FAULT: SPEED OVER-RUN (see
below). When retro fitting, set speed to 110% for both OPEN and CLOSE.
GENESIS CONTROL BOARD
>Gate Orientation:
Right
GATE ORIENTATION: Set for LEFT or RIGHT hand gate. The hand is always determined from the INSIDE
or PRIVATE side of the gate system. If the operator is located on the right-RIGHTHAND, left-LEFTHAND.
DUAL GATE MODE: Turn “ON” when you have (2) gates opening at the same time.
Options: OFF, PRIMARY or SECONDARY. If “ON”, then each gate needs to be set accordingly
STATUS: Disconnected or Connected
•If using the “Auto Close”, only set the PRIMARY “Auto Close” to on, leave the Secondary off
•Make sure both gates are powered up, otherwise you receive a “communication” error
message (see yellow message below)
>Dual Gate Mode:
>Off
Status
Disconnected
Gate set in DUAL
Mode: Primary or
Secondary not
detected
In a PRIMARY/SECONDARY or DUAL gate mode system, if you lose communication between the two
operators you will get this message.
Note: Gates will not operate in DUAL gate mode unless BOTH are powered up and connected.
>Const Press Mode:
Off
Stop Input Mode:
Normally Open
CONSTANT PRESSURE (CP) MODE (CLASS IV): In the CP mode, the OPEN 1, OPEN 2 & CLOSE inputs can
be wired to a push button station for gate control. In a CP mode, these inputs will override the
Entrapment STOP/ALARM condition. Status is ON or OFF only. Default is OFF.
STOP INPUT MODE: Either Normally OPEN or Normally CLOSED
WARNING! Use caution when using these inputs. Always have direct line of site to
the gate at all times to avoid pedestrian injuries or equipment/vehicle damage.
WARNING! Downward
Speed too fast.

MONITORED INPUT SETTINGS (NOT USED WHEN REPLACING A LIFTMASTER CONTROL BOARD-SKIP THIS SECTION!)
Monitored Input
Options
OPTIONS: OPEN OBSTRUCTION, CLOSE OBSTRUCTION, PROGRAMMED MONITORED INPUTS:
Choices are: 10K (10,000 Ohms Resistance) or 2-Wire.
(The GENESIS board supports a maximum number of (2) OPEN, (2) CLOSED & (2) programmable inputs.
Contact AutoGate if additional inputs are required).
If your gate has a monitored UL Event and either “locks” open or goes “closed”, this warning screen will
appear as well as the FAULT light will flash. Any intended INPUT will reset the gate to normal operation.
Providing the obstruction is no longer present. You can also “manually” reset the board.
OPEN OBSTRUCTION: You have (3) choices: OFF, 10K or 2-WIRE. You must have a minimum of (1)
programmed at all times for UL325 Rev. 6 and up.
If your gate had an OPEN OBSTRUCTION event, the gate will stop and reverse to full close until the
obstruction is cleared and an INTENTED INPUT (Access Control Input, Loop Reset, etc., but NOT the
CLOSE TIMER) or a MANUAL INPUT on the control board resets your gate back to normal operation.
CLOSE OBSTRUCTION: You have (3) choices: OFF, 10K or 2-WIRE. You must have a minimum of (1)
installed and programmed at all times per UL325 latest edition. CLOSE OBSTRUTION DEVICES are
approved Beams and Edges only!
WARNING Monitored
Input missing
See LED indicators
For Monitored
Inputs
Open Obstruction:
>Edge: Off
Beam: Off
WARNING! Obstruction
An intended Input or
manual reset req’d.
to restore use.
Close Obstruction:
>Edge: Off
Beam: Off
If your gate had a DOUBLE CLOSED EDGE OBSTRUCTION event, the gate will shut down in the OPEN
position until the obstruction is cleared and an INTENTED INPUT (Access Control Input, Loop Reset,
etc., but NOT the CLOSE TIMER) or a MANUAL INPUT on the control board resets your gate back to
normal operation.
PROGRAM MONITORED INPUTS: Additional INPUTS for additional monitored devices. Choices are: OFF,
10K: OPEN EDGE, OPEN BEAM, CLOSE EDGE & CLOSE BEAM
2-WIRE: OPEN EDGE, OPEN BEAM, CLOSE EDGE & CLOSE BEAM.
Prog Mon Input 1:
>Open Edge 10K
Prog Mon Input 2:
Close Beam 2-Wire
WARNING! DOUBLE
DEFAULT! Push RED
STOP or RESET button
to restore use.
If your gate had an OBSTRUCTION event, depending on the monitored device, the gate will shut down
either in the OPEN or CLOSED position until the obstruction is cleared and an INTENTED INPUT (Access
Control Input, Loop Reset, other) or a MANUAL INPUT on the control board will reset your gate back to
normal operation.
WARNING! Obstruction
An intended Input or
manual reset req’d.
to restore use.
tore normal use.
GENESIS CONTROL BOARD
WARNING! Obstruction
An intended Input or
manual reset req’d.
to restore use.
Board is programmed for a Monitored Input. If it is missing, gate will not operate until the monitored
input is installed or restored.
“Monitored” device
is enabled and the
reqd feedback (10K-
Pulse) is missing
Board is programmed for a Monitored Input. If it is enabled and the required feedback is missing you
will get these FAULTS: CLOSE BEAM MISSING, OPEN BEAM MISSING, CLOSE EDGE MISSING, OPEN EDGE
MISSING. PGM INPUT 1 MISSING, PGM. INPUT 2 MISSING.You will need to re-establish the monitored
device.

INPUT OPTIONS
AUXILARY OUTPUT OPTIONS
Input Options
OPTIONS: INPUT 1 & 2
All of the INPUTS will require a momentary pulse from a remote source such as a Pushbutton, Toggle
Switch, etc.
>Input 1 Mode:
Off
Input 2 Mode:
Off
WARNING! HOLD OPEN
IS ENABLED, gate
will not close
until released
WARNING! FIRE
SWITCH IS ENABLED.
Hold Stop and press
Jog/select to clear
INPUT (1 & 2) MODES:
OFF
OPEN-Open command
CLOSE-Close command
Single Button-Open-Stop-Close-Stop
Reverse-Reverse command
Fire-Holds the gate Open (will cause a FLASHING ALERT warning screen)
Shadow-Shadow Loop input
Auto Open: Default is OFF-Skips the next days 7-Day Timer cycle commands
Hold Open-Opens gate: Holds open until Input removed (will cause a FLASHING ALERT warning screen)
Emergency Secure-Gate will NOT open (will cause a FLASHING ALERT warning screen)
Emergency Close-(Custom programmed, contact AutoGate for this option)
Aux 1 Pulse-Pulses Auxiliary 1 contacts
Aux 1 Hold-Holds Auxiliary 1 contacts until triggered
Aux 2 Pulse-Same as Pulse 1
Aux 2 Hold-Same as Hold 1
WARNING! EMERGENCY
SECURE is enabled.
Gate will not OPEN
until released
OPTIONS: AUXILIARY RELAYS (A & B), OUPUT (1 & 2), PROGRAMMABLE LOCK
AUX RELAYS will switch contact between NORMALLY OPEN and NORMAMLLY CLOSED from a common
input.
AUX OUTPUTS physically switch 24VDC ON or OFF
Aux Output Options
GENESIS CONTROL BOARD
Open/Close Program: Programs the OP/CL PRM Input under P2 on the board to either: OFF, OPEN only
or OPEN and CLOSE.
>Open/Close Pgm In:
Off
>Aux Input 1 Delay
5 Seconds
Aux Input 2 Delay
0 Seconds
AUXILLARY INPUT 1 & 2 DELAY: Option to delay the INPUT from firing and opening the gate. Settable
from 1 to 20 seconds
WARNING Double Fault
Red Stop input or
manual reset req’d
to restore use.
If your gate had a DOUBLE FAULT, it will be shut down. To restore normal activity, check for
obstructions and if clear, hit the RED STOP button, do a manual reset or power the system down and
back on again.

AUXILARY OUTPUT OPTIONS (cont.)
>Relay A Mode:
Off
Relay B Mode:
AUXILIARY RELAYS (A & B): Either relay can be set for a variety of functions:
OFF
Pulse on Open Limit
Pulse on Close Limit
Hold on Open Limit
Hold on Close Limit
Pulse on Motor Open
Pulse on Motor Close
Hold on Motor Open
Hold on Motor Close
>Output 1 Mode:
Hold on Aux 2
Output 2 Mode:
Off
>Programmable lock:
Magnetic
Aux Output states:
Out1 N-O, Out2 N-O
PROGRAMMABLE LOCK: Output to control Maglocks or Solenoid Locks. The Maglock will be powered
all the time and turn off prior to gate motion. The Solenoid mode will power a 24VDC output prior to
gate motion.
AUX OUTPUT STATES:
Out 1 N-O, Out 2 N-O: Normally OPEN, Normally OPEN
Out 1 N-C, Out 2 N-C : Normally CLOSED, Normally CLOSED
Out 1 N-C, Out 2 N-O: Normally CLOSED, Normally OPEN
Out 1 N-O, Out 2 N-C: Normally OPEN, Normally CLOSED
GENESIS CONTROL BOARD
>Output 1 Quick Set:
Always Flashing
Output 2 Quick Set:
Flashing Closed
Quick Set:
OUTPUT QUICK SET OUTPUT 1 & 2: 4 Quick Set options for flashing lights:
Choices are:
No Preset: Off
Always Flashing: Light Flash 24/7
Closed & Motion 1: Always flashes except on solid on full open
Closed and Motion 2: Always flashes except off on full open
Flashing Closed: Lights flash when the gate is closed only
OUTPUT (1 & 2): Either relay can be set for a variety of functions and provides 24vdc power
OFF
Pulse on Open Limit
Pulse on Close Limit
Hold on Open Limit
Hold on Close Limit
Pulse on Motor Open
Pulse on Motor Close
Hold on Motor Open
Hold on Motor Close
Hold on UL Alarm
Hold on Motor Run
Hold Always
Pulse Always
Hold Not Open Limit
Pulse Not Open Limit
Hold Not Close Limit
Pulse Not Close Limit
Hold Not Opening
Pulse Not Opening
Hold Not Closing
Pulse Not Closing
Pulse On Motor Run
Note: For all accessories (lights, alarms, etc.),
check on www.autogate.com for technical
data or refer to the manufacturer’s technical
data and installation sheets.
Note: When installing an accessory item (traffic
light, siren, etc), you need to run the COMMON
down to our POWER TERMINAL (common) and
then take a wire from the 24vdc up to the RELAY A
or B COMMON. This will provide power to your unit.

AUXILARY OUTPUT OPTIONS (cont.)
MAINTENANCE
Maintenance
GATE ORIENTATION, BATTERY STATUS, SOLAR, BATTERY CHECK, BATTERY LEVEL, OVER CURRENT
LEVEL, CONSTANT PRESSURE MODE, DUAL GATE MODE & CUSTOM SETTINGS
LOW BATTERY ACTION: Default is No Action
Options are:
FAIL SAFE: Gate will fail OPEN (will cause a FLASHING ALERT warning screen)
FAIL SECURE: Gate will fail CLOSED. (will cause a FLASHING ALERT warning screen)
NO MAIN AC POWER ACTION:
Options are:
RUN ON BATTERIES: If you lose AC power, your gate will continue to run on battery power
HOLD OPEN: If you lose AC power, your gate will lock up in the OPEN mode
>Low Battery Action
No Action
No Main Power Act.:
Run on Batteries
>Low Battery Level
Note: this screen
not viewable.
Requires passcode
BATTERY LEVEL: During battery test, if the battery level falls below the level set, it will turn on the
FAULT LIGHT and issue a FAULT CODE. (Passcode required to change). (will cause a FLASHING ALERT
warning screen)
GENESIS CONTROL BOARD
WARNING! FAIL SECURE
Gate held CLOSED due
to critical low
battery voltage
WARNING! FAIL SAFE!
Gate held OPEN due
to critical low
battery voltage
>Output 1 Pulse Rate
2 Seconds
Output 2 Pulse Rate
¼ Seconds
OUTPUT PULSE RATE: Controls the time sequence of the pulse
Options: ¼ Second, ½ Second, 1 Second, 2 Seconds
Options: 1 Second Single
Batt: Float Charge
>PWR SUPPLY: Normal
Batt V Check Freq:
50 Cycles
BATTERY STATUS: Indicates the charging status:
FLOAT: When battery is FULL voltage and not being charged
BULK: Battery is in charging mode
ABSORBTION: Batteries are low, switches to charging
POWER SUPPLY VOLTAGE:
NORMAL (Default): Standard power supply
CHARGE: For retrofitting older systems only and replaces the original factory transformer
SOLAR: Used when you have Solar Panels
WARNING! If Solar is set to ON, and AC voltage is present, the AC voltage will not be connected and
you will still be operating off batteries only!
Loss of SOLAR or Power Supply connection for 24 hours (will cause a FLASHING ALERT warning screen)
BATTERY V CHECK: How often the board will test the batteries under load. The factory pre-set is every
50 cycles. (Pass code required to change cycle frequency)
Additional VOLTAGE WARNINGS FAULTS & Screens: AC is missing: There is no AC voltage detected on
the GENESIS board at the AC INPUT. OVER VOLTAGE: The voltage at the AC INPUT measured over the
30V in normal mode. MOTOR OVER-CURRENT: The motor current exceeded the high set point.
WARNING! Charging
source NOT detected
in the last 24
hours!
Voltage not
detected at the AC
Input
Voltage at the AC
Input measured over
30V in normal mode
Motor current went
above set point

MAINTENANCE (cont.)
FAULT/LOGS/ALERTS
>Over-Current level:
20 Amps
OVER-CURRENT LEVEL: Adjusts the Internal Inherent Amp current level for the motor. On model
2490 systems with the GENESIS board and the LPS SENSOR, this will not be in effect. When using
LIMIT SWITCHES, the OVER-CURRENT LEVEL must be set for obstruction/entrapment sensing. If the
board senses an OVER-CURRENT it will reverse the gate on the first activation. On a sequential
activation, this will stop the gate and turn on the UL Alarm. To reset…. Check for any obstructions, if
none, Press the STOP button on the board or if you have an accessory STOP button wired to the STOP
input. Other options are hit the RESET button or cycle all power off and on.
LOCKED
Key: EB60F3CA
_ _ _ _ _
CUSTOM SETTINGS: For advanced features. Requires a “PASSCODE” available from AutoGate only.
Code is active for 24 hours only. After 24 hours a new code is required.
OTHER FAULT CODES:
Battery issue: Check the charge voltage, check the Batteries or replaced if necessary.
FORCED OPEN DETECT: The gate was attempted to be opened and moved off the CLOSED limit without
a command from the GENESIS board.
INTERNAL EEPROM & MISSING EEPROM: Internal EEPROM missing of defective
WARNING! LOW BATTERY
Check charge
circuit, charge or
replace Batteries
OPTIONS: Fault log, Operation Log, Maintenance Alerts
Fault/Logs/Alerts
Fault Log
>25 10:34p 04/20/18
Gate Angle Sensor
FAULT LOG: Running list of faults, stored for reference for diagnostic troubleshooting. The last 99
Faults are stored. The newest Fault will always be the first one shown. Any fault in the system will also
turn on the FAULT LIGHT on the outside of the cabinet.
Operation Log
#06< 02:55p
06/29/18
Local Open
OPERATION LOG: All normal “operations” are recorded up to 99 events. (i.e. Close Limit, Open Limit,
Green Open button, Red Stop button, entry Inputs, loop detections, & photoelectric sensors/beam
detections, traffic lights, etc. are examples of normal “operation” events logged.)
>Maintenance Alerts
50K Cycles
Next due at 80,000
MAINTENANCE ALERT: Alerts the owner that maintenance is due after a selected number of cycles.
This can be set by the installer for 10K, 20K or 50,000 cycles. The screen will show how long until the
next alert will show.
>Maintenance
Required, Hold Stop
button & Press Jog
to clear.
MAINTENANCE ALERT: You have reached your predetermined number of cycles to perform general
maintenance. Hold the STOP button and press the JOG/Select button to clear.
GENESIS CONTROL BOARD
Gate has been moved
off the CLOSE limit
w/o a command from
the GENESIS board
Internal EEPROM
fault detected
EEPROM chip not
detected

FAULT LOG ENTRY
FAULT MENU DISPLAY
AC MISSING
Voltage not detected at the AC input
BATTERY LOW CHARGE
WARNING! Battery low, check battery charge
voltage
CLOSE BEAM MISSING
If your “monitored” device is enabled and the
required feedback (10K or Pulse) is missing
CLOSE EDGE MISSING
If your “monitored” device is enabled and the
required feedback (10K or Pulse) is missing
DUAL GATE COMM. LOST
Gate set in DUAL mode: Primary or Secondary
not detected
EMERGENCY SECURE
WARNING! EMERGENCY SECURE is enabled, gate
will not OPEN until released
FAIL SAFE OPEN
WARNING! Fail Safe gate held open due to critical
battery voltage
FAIL SECURE CLOSE
WARNING! Fail Secure gate held close due to
critical battery voltage
FIRE HOLD ENABLED
WARNING! FIRE SWITCH IS ENABLED. Hold Stop
and press Jog/select to clear
FORCED OPEN DETECT
Gate has been moved off the CLOSE limit position
without a command from the GENESIS board
HOLD OPEN
WARNING! HOLD OPEN is enabled, gate will not
close until released
INTERNAL EEPROM
Internal EEPROM fault detected
LPS SENSOR NOT DETECTED
LPS Sensor is not detected by the GENESIS board
(not applicable in LIMIT SWITCH more)
MAITNENANCE REQ’D.
Maintenance required, hold stop button and
press Jog/Select to clear
MISSING EEPROM CHIP
EEPROM chip not detected
MONIT. INPUT MISSING
WARNING! Monitored input missing, see LED
indicators for monitored inputs
MOTOR OVER-CURRENT
Motor current went above set point
NO CHARGE IN 24 HRS
WARNING! Charging source not detected in the
last 24 hours
OPEN BEAM MISSING
If your “monitored” device is enabled and the
required feedback (10K or Pulse) is missing
OPEN EDGE MISSING
If your “monitored” device is enabled and the
required feedback (10K or Pulse) is missing
OVER VOLTAGE
Voltage at AC input measured over 30V in normal
power mode
PGM. INPUT 1 MISSING
If your “monitored” device is enabled and the
required feedback (10K or Pulse) is missing
PGM. INPUT 2 MISSING
If your “monitored” device is enabled and the
required feedback (10K or Pulse) is missing
SPEED OVER-RUN
Downward speed was too fast
UL FAULT CONDITION
WARNING! DOUBLE DEFAULT. Push RED stop
button or RESET button to restore to use
UL FAULT CONDITION
WARNING! OBSTRUCTION DETECTED! An
intended input or RESET required to restore use
GENESIS CONTROL BOARD
Table of contents