Automated Logic SE6166 Owner's manual

Verify that you have the most current version of this document. Go to http://accounts.automatedlogic.com, then select Support >
Download > Documents > Technical Instructions.
SE6166 Controller
Technical Instructions
Rev. 4/13/2011

© 2011 Automated Logic Corporation. All rights reserved throughout the world. Automated Logic Corporation, the Automated Logic logo,
WebCTRL, EIKON, BACview, SuperVision, and InterOp are registered trademarks, and Alert is a trademark of Automated Logic Corporation.
BACnet®is a registered trademark of ASHRAE. All other brand and product names are trademarked by their respective companies.
Contents
What is the SE6166 controller?..................................................................................................1
Driver and control program ........................................................................................... 1
Specifications .............................................................................................................. 1
Inputs .......................................................................................................................... 3
Digital outputs ............................................................................................................. 3
Analog outputs............................................................................................................. 4
Room sensors .............................................................................................................. 4
BACviews..................................................................................................................... 4
To mount the SE6166 ...............................................................................................................5
Wiring for power........................................................................................................................5
To wire for power .......................................................................................................... 5
To address the SE6166 .............................................................................................................5
Wiring for communications ........................................................................................................6
Wiring specifications .................................................................................................... 6
To wire the SE6166 for communications ....................................................................... 6
Wiring inputs and outputs..........................................................................................................7
Wiring specifications .................................................................................................... 7
To wire inputs and outputs............................................................................................ 8
Wiring a room sensor to the SE6166.........................................................................................10
Rnet wiring specifications........................................................................................... 10
To wire an RS sensor................................................................................................... 11
LogiStat wiring specifications ..................................................................................... 11
To wire a LogiStat sensor ............................................................................................ 11
Downloading the SE6166........................................................................................................12
To download in WebCTRL............................................................................................ 12
To assign inputs or outputs to points.........................................................................................13
Input values ............................................................................................................... 13
Output values............................................................................................................. 14
Resolution values....................................................................................................... 15
Offset/Polarity values................................................................................................. 15
To use the Auto-Off-On switches.................................................................................. 16
To set up the driver..................................................................................................................16
Driver......................................................................................................................... 16
Device........................................................................................................................ 17
Notification Classes ................................................................................................... 18
Calendars .................................................................................................................. 19
Common and Specific Alarms..................................................................................... 19
Custom Translation Tables.......................................................................................... 19
Switch and Jumper Positions ...................................................................................... 19
To communicate through the local access port...........................................................................20
To set up a Local Access connection in WebCTRL......................................................... 20
Troubleshooting......................................................................................................................21
Formatting the controller ............................................................................................ 21
LED's......................................................................................................................... 22
Serial number ............................................................................................................ 23
Replacing the SE6166's battery................................................................................. 23
To take the SE6166 out of service ............................................................................... 23
Compliance............................................................................................................................24
FCC Compliance......................................................................................................... 24
CE Compliance........................................................................................................... 24
BACnet Compliance ................................................................................................... 24
Appendix - SE6166 coverplate.................................................................................................25

SE6166 Controller • Rev. 4/13/2011 1 © 2011 Automated Logic Corporation
The SE6166 controller controls rooftop Air Handling Units (AHUs) or other large single
pieces of equipment. You can mount the SE6166 on or inside the rooftop equipment.
Driver DRV_SE
Maximum number of control programs 1
Maximum number of BACnet objects* 300**
*Depends on available memory.
** Any points that exceed this number will not be network visible.
Power 24 Vac ±10%, 50–60 Hz, 20 VA power consumption (38.4
VA with BACview6 attached) single Class 2 source only, 100
VA or less
BACnet port
(This port may be labeled
CMnet.)
For communication with the controller network using
ARC156 or MS/TP (9600 bps–76.8 kbps)
Local Access port For system start-up and troubleshooting
LogiStat port For LogiStat and LogiStat Plus room sensors. The LogiStat
port uses two universal inputs.
NOTE
The SE6166 does not support the LogiStat Pro. Use
an RS Pro on the Rnet port instead.
Rnet port Supports up to four RS Standard sensors and one RS Plus,
RS Pro, or RS Pro-F sensor for averaging or high/low select
control. The sensors can share the Rnet port with a BACview5
or BACview6.
NOTE
If you use the Rnet port, you cannot connect a
LogiStat sensor to the LogiStat port.
Inputs 16 inputs, configurable for 0–10 Vdc, 0–20 mA, RTD,
thermistor, or dry contact, and one LogiStat port. Inputs 1
and 2 are also configurable for pulse counter or timed local
override (TLO).
NOTE
If using a LogiStat or LogiStat Plus, temperature and
setpoint adjust inputs replace inputs 9 and 10, making 9
and 10 unavailable.
Input resolution 12 bit A/D
Input pulse frequency 40 pulses per second. Minimum pulse width (on or off time)
required for each pulse is 12.5 msec.
Digital outputs 6 digital outputs, relay contacts rated at 3 A max @ 24 Vac.
Configured normally open.
What is the SE6166 controller?
Driver and control
program
Specifications

SE6166 Controller • Rev. 4/13/2011 2 © 2011 Automated Logic Corporation
Analog outputs 6 analog outputs, 0–10 Vdc or 0–20 mA selectable
Output resolution 8 bit D/A
Microprocessor High speed 16-bit microprocessor with ARCNET
communication co-processor
Memory 1 MB non-volatile battery-backed RAM, 1 MB Flash memory,
16-bit memory bus
Real-time clock Battery-backed real-time clock keeps track of time in event
of power failure
Battery 10-year Lithium CR2032 battery provides a minimum of
10,000 hours of data retention during power outages
Protection Incoming power and network connections are protected by
non-replaceable internal solid-state polyswitches that reset
themselves when the condition that causes a fault returns to
normal. The power, network, input, and output connections
are also protected against voltage transient and surge
events.
BT485 connector You attach a BT485 (not included) to a controller at the
beginning and end of a network segment to add bias and to
terminate a network segment.
Status indicators LED's indicate status of communications, running, errors,
power, and digital outputs
Environmental operating
range
-20 to 140°F (-29 to 60°C), 10–90% relative humidity, non-
condensing
NOTE
The controllers should be mounted in a protective
enclosure.
Physical Rugged aluminum cover, removable, screw-type terminal
blocks
Overall dimensions Width:
Height:
8 5/16 in. (21.1 cm)
7 in. (17.8 cm)
Mounting dimensions Width:
Height:
7 7/8 in. (19.9 cm)
5 in. (12.7 cm)
Recommended panel
depth
1 1/2 in. (3.8 cm)
Weight 1.2 lbs (0.5 kg)
BACnet support Conforms to the Advanced Application Controller (B-AAC)
Standard Device Profile as defined in ANSI/ASHRAE
Standard 135-2004 (BACnet) Annex L
Listed by UL-916 (PAZX), cUL-916 (PAZX7), FCC Part 15-Subpart B-
Class A, CE EN50082-1997

SE6166 Controller • Rev. 4/13/2011 3 © 2011 Automated Logic Corporation
The SE6166 has 16 inputs that accept the signal types described below.
These
inputs...
Support this
signal type...
Description
All Thermistor1Precon type 2 (10 kOhm at 77°F). Input voltages should
be from 0.489 Vdc to 3.825 Vdc for thermistors.
All Dry contact A 5 Vdc wetting voltage detects contact position, resulting
in a 1 mA maximum sense current when the contacts are
closed.
All 0–5 Vdc
0–10 Vdc
The output impedance of a 0–5 Vdc or a 0–10 Vdc source
must not exceed 200 Ohms. The input impedance of the
SE6166 is approximately 20 kOhm.
All 0–20 mA The input resistance on the positive (+) terminal is 250
Ohms. The
Aux Power Out
connector is capable of
supplying 24 Vdc to multiple 4–20 mA transducers, but
the total current demanded must not exceed 200 mA. If
the voltage measured from the
Aux Power Out
connector
to
Gnd
is less than 18 Vdc, you need to use an external
power supply.
All RTD1Platinum - 1 kOhm at 32°F (0°C)
Nickel/Iron - 1 kOhm at 70°F (21°C)
Balco TS8000 - 1 kOhm at 70°F (21°C)
Input voltages should be from 0.6–1.2 V.
NOTE
ALC recommends use of an external current
transducer between an RTD and the SE6166.
IN-1, IN-2 Pulse
counter2
Pulse counting up to 40 pulses per second.
Minimum pulse width (on or off time) required for each
pulse is 12.5 msec.
IN-1, IN-2 Timed local
override
A momentary contact switch that overrides a schedule and
turns equipment on for a defined period of time. The
override time added for each push of the button and the
maximum allowable On time are software adjustable.
IN-9, IN-10 LogiStat
LogiStat Plus3
IN-9–See Thermistor.
IN-10–Setpoint adjust. Input voltages should be from 1.4–
3.4 Vdc.
1To use a thermistor or RTD not listed above, you can set up a custom translation table (page 19)
for your sensor.
2The SE6166 can perform pulse counting for dry contact or voltage inputs if you assign the input to
a Pulse to Analog Input microblock. See To assign inputs or outputs to points (page 13).
3A LogiStat or LogiStat Plus connected to the SE6166 uses IN-9 and IN-10. A LogiStat Pro or an RS
room sensor does not use these inputs.
The SE6166 has 6 digital outputs. You can connect each output to a maximum of 24 Vac.
Each output is a dry contact rated at 3 A maximum and is normally open.
Inputs
Digital outputs

SE6166 Controller • Rev. 4/13/2011 4 © 2011 Automated Logic Corporation
The SE6166 has 6 analog outputs that support voltage or current devices. The controlled
device must share the same ground as the controller and have the following resistance to
ground:
0–10 Vdc
0–20 mA
min 500 Ohms
max 800 Ohms
NOTE The SE6166 supervises all outputs.
RS sensors
You can wire RS sensors to the SE6166's Rnet port. An Rnet can consist of any of the
following combinations of devices wired in a daisy-chain or star configuration:
•1 RS Plus, RS Pro, or RS Pro-F
•1–4 RS Standards
•1–4 RS Standards, and 1 RS Plus, RS Pro, or RS Pro-F
•Any of the above combinations, plus up to 2 BACviews, but no more than 6 devices
total. See BACviews below.
LogiStats
You can wire a LogiStat or LogiStat Plus to the SE6166's LogiStat port.
NOTES
•The SE6166 does not support the LogiStat Pro.
•A LogiStat or LogiStat Plus wired to the SE6166 cannot be used for local access.
•If you use the Rnet port, you cannot connect a LogiStat sensor to the LogiStat port.
You can wire a BACview5or BACview6keypad/display unit to the Rnet port of the SE6166
to view or edit some of its property values or its real time clock. See Room sensors above
for Rnet configurations. See the BACview5Hardware Setup Guide
(http://accounts.automatedlogic.com) or BACview6Hardware Setup Guide
(http://accounts.automatedlogic.com) for installation instructions.
To start up and troubleshoot the SE6166, you can temporarily connect the following items
to its Local Access port:
•The BACview6Handheld. See its Technical Instructions
(http://accounts.automatedlogic.com).
•A laptop running the Virtual BACview software. Virtual BACview software simulates the
BACview6and is included with WebCTRL v4 or later.
NOTE Before you can use the BACview5, BACview6, BACview6Handheld, or Virtual
BACview with the SE6166, you must create a BACview screen file in ViewBuilder, enter
the screen file name in the controller's Properties box in SiteBuilder, and then download
the control program to the SE6166.
Analog outputs
Room sensors
BACviews

SE6166 Controller • Rev. 4/13/2011 5 © 2011 Automated Logic Corporation
Screw the SE6166 into an enclosed panel using the mounting holes provided on the
cover plate. Leave about 2 in. (5 cm) on each side of the controller for wiring.
CAUTIONS
•The SE6166 is powered by a Class 2 power source. Take appropriate isolation
measures when mounting it in a control panel where non-Class 2 circuits are present.
•ALC controllers can share a power supply as long as you:
○Maintain the same polarity.
○Use the power supply only for ALC controllers.
1 Turn off the SE6166’s power to prevent it from powering up before you can verify the
correct voltage.
2 Remove power from the 24 Vac transformer.
3 Pull the screw terminal connector from the controller's power terminals labeled Gnd
and 24 Vac.
4 Connect the transformer wires to the screw terminal connector.
5 Apply power to the transformer.
6 Measure the voltage at the SE6166’s power input terminals to verify that the voltage
is within the operating range of 21.6–26.4 Vac.
7 Insert the screw terminal connector into the SE6166's power terminals.
8 Turn on the SE6166's power.
9 Verify that the Power LED is on and the Run LED is blinking.
You must give the SE6166 an address that is unique on the network. You can address the
SE6166 before or after you wire it for power.
1 If wired for power, turn off the controller's power. The controller reads the address
each time you turn it on.
2 Using the rotary switches, set the controller's address to match the Address in the
controller's Device Properties dialog box in SiteBuilder. Set the Tens (10's) switch to
the tens digit of the address, and set the Ones (1's) switch to the ones digit.
To mount the SE6166
Wiring for power
To wire for power
To address the SE6166

SE6166 Controller • Rev. 4/13/2011 6 © 2011 Automated Logic Corporation
EXAMPLE If the controller’s address is 25, point the arrow on the Tens (10's) switch
to 2 and the arrow on the Ones (1's) switch to 5.
10's 1's
1
3
4
5
2
7
8
9
6
0
1
3
4
5
2
7
8
9
6
0
The SE6166 communicates using BACnet on the following types of network segments:
•ARC156 communicating at 156 kbps
•MS/TP communicating at 9600 bps, 19.2 kbps, 38.4 kbps, or 76.8 kbps
NOTE ARC156 is a unique implementation of the industry standard ARCNET. For a
summary of differences between ARCNET and ARC156, see the ARC156 Wiring Technical
Instructions (http://accounts.automatedlogic.com/download).
For...
Use...
Maximum Length
ARC156 1
and
MS/TP 2
22 AWG, low-capacitance, twisted,
stranded, shielded copper wire
2000 feet (610 meters)
1See the ARC156 Wiring Technical Instructions (http://accounts.automatedlogic.com/download).
2See the MS/TP Networking and Wiring Technical Instructions
(http://accounts.automatedlogic.com/download).
1 Turn off the SE6166's power.
2 Check the communications wiring for shorts and grounds.
3 Connect the communications wiring to the controller’s screw terminals labeled Net +,
Net -, and Shield.
NOTE Use the same polarity throughout the network segment.
4 Set the communication type and baud rate.
For...
Set DIP switch 4 to...
Set DIP switches 1 and 2 to...
ARC156
ARC156
N/A. Baud rate will be 156 kbps regardless
of the DIP switch settings.
MS/TP
MSTP
The appropriate baud rate. See the
MSTP
Baud
diagram on the controller.
NOTE Use the same baud rate for all controllers on the network segment.
Wiring for communications
Wiring
specifications
To wire the
SE6166 for
communications

SE6166 Controller • Rev. 4/13/2011 7 © 2011 Automated Logic Corporation
5 If the SE6166 is at either end of a network segment, connect a BT485 to the
SE6166.
6 Turn on the SE6166's power.
7 Verify communication with the network by viewing a Module Status report in
WebCTRL.
Input wiring
Input
Maximum length
Minimum gauge
Shielding
0–5 Vdc
0–10 Vdc
1000 feet
(305 meters)
26 AWG Shielded
0–20 mA 3000 feet
(914 meters)
26 AWG Shielded or
unshielded
Thermistor
Dry contact
Pulse counter
TLO
1000 feet
(305 meters)
22 AWG Shielded
RTD 100 feet
(30 meters)
22 AWG Shielded
RS sensor
LogiStat sensor
See Wiring a room sensor to the SE6166 (page 10).
NOTE ALC recommends use of an external current transducer between an RTD and the
SE6166.
Output wiring
To size output wiring, consider the following:
•Total loop distance from the power supply to the controller, and then to the controlled
device
NOTE Include the total distance of actual wire. For 2-conductor wires, this is twice the
cable length.
•Acceptable voltage drop in the wire from the controller to the controlled device
•Resistance (Ohms) of the chosen wire gauge
•Maximum current (Amps) the controlled device requires to operate
Wiring inputs and outputs
Wiring
specifications

SE6166 Controller • Rev. 4/13/2011 8 © 2011 Automated Logic Corporation
1 Verify that the SE6166's power and communications connections work properly.
2 Turn off the SE6166's power.
3 Connect the input wiring to the screw terminals on the SE6166.
Dry
contact
Any input
Gnd
Gnd
External
24 Vdc
half-wave
power
supply
2 wire
3 wire
Aux Power Out
+24 Vdc
200 mA max
Out
Gnd
V+
Gnd
+
Any input
Gnd
+
Any input
Gnd
+
Any input
+
Gnd
Any input
+
Gnd
Any input
+
Any input
+
Set Universal
Input Mode
Select jumper to...
Thermistor
Dry-contact
RTD
Out
Gnd
V+
Any input
+
Volts
Volts
Volts
Volts
Volts
Volts
mA
mA
mA
mA
mA
mA
10 kOhm
thermistor
1 kOhm
RTD
n/c
4 wire
2 wire
3 wire
4 wire
Out +
Out - Gnd
V+
Gnd Any input
+
Out
V+
Gnd
Out
V+
n/c
Out +
Out -
V+
Gnd
0-5 Vdc,
0-10 Vdc,
or
4-20 mA
0-5 Vdc,
0-10 Vdc,
or
4-20 mA
0-5 Vdc,
0-10 Vdc,
or
4-20 mA
0-5 Vdc,
0-10 Vdc,
or
4-20 mA
0-5 Vdc,
0-10 Vdc,
or
4-20 mA
0-5 Vdc,
0-10 Vdc,
or
4-20 mA
or
or
or
or
or
or
NOTES
○Connect the shield wire to the GND terminal with the ground wire.
○Use only IN-1 or IN-2 for pulse counter or timed local override.
○For a loop-powered 4-20 mA sensor, wire the sensor's positive terminal to the +
terminal on the SE6166's Aux Power Out connector. Wire the sensor's negative
terminal to an input's +terminal.
To wire inputs
and outputs

SE6166 Controller • Rev. 4/13/2011 9 © 2011 Automated Logic Corporation
4 Set the appropriate jumpers on the SE6166.
To use...
For...
Any input Thermistor
Dry contract
0–5 Vdc
0-10 Vdc
0–20 mA
RTD
Set each input's
Universal Input Mode
Select
jumper to the type
of signal the input will
receive.
Jumpers for
inputs...
1
3
5
7
9
11
13
15
2
4
6
8
10
12
14
16
Aux Power Out
connector
Loop-powered
4-20 mA
Set the
Select
jumper to
+5V
or
+24V
as
required by the sensor.
5 Connect the digital output wiring to the screw terminals on the SE6166 and to the
controlled device.
24 Vac/dc
Motor
Valve
Any DO
Any DO
Any DO

SE6166 Controller • Rev. 4/13/2011 10 © 2011 Automated Logic Corporation
6 Connect the analog output wiring to the screw terminals on the SE6166 and to the
controlled device.
Any AO
Gnd
Gnd
24 Vac/dc
+
+
–
–
Gnd
0-10 V
0-10 V
Hot
Hot
Gnd
4-wire
3-wire
+
Any AO +
Set AO
Mode Select
jumper to...
0-10 Vdc
0-20 mA Gnd
+
–
0-20 mA
0-20 mA
Hot
3-wire
Any AO +
Gnd
+
–Hot
Gnd
4-wire
Any AO +
0-10 Vdc
0-20 mA
7 Set the AO Mode Select jumper to the type of device you are wiring the output to.
8 Turn on the SE6166's power.
You can wire:
•An RS Standard, RS Plus, RS Pro, or RS Pro-F to the SE6166's Rnet port
•A LogiStat or LogiStat Plus to the SE6166's Lstat port
See the following sections for wiring instructions. For other details, see the RS Room
Sensors Technical Instructions or the LogiStat Sensors Technical Instructions.
NOTE Use the specified type of wire and cable for maximum signal integrity.
Description 4 conductor, shielded or unshielded, CMP, plenum rated cable
Conductor 22 AWG (7x0096) bare copper if Rnet has only RS sensors.
18 AWG (7x0152) bare copper if Rnet has a BACview.
Maximum length 500 feet (152 meters)
Insulation Low-smoke PVC (or equivalent)
Wiring a room sensor to the SE6166
Rnet wiring
specifications

SE6166 Controller • Rev. 4/13/2011 11 © 2011 Automated Logic Corporation
Color Code Black, white, green, red
Shielding If shielded, Aluminum/Mylar shield (100% coverage) with TC
drain wire
UL temperature rating 32–167°F (0–75°C)
Voltage 300 Vac, power limited
Listing UL: NEC CL2P, or better
1 Turn off the SE6166's power.
2 Partially cut, then bend and pull off the outer jacket of the Rnet cable(s). Do not nick
the inner insulation.
3
Inner insulation
Outer jacket
Foil shield
.25 in.
(.6 cm)
4 Strip about .25 inch (.6 cm) of the inner insulation from each wire.
5 Wire each terminal on the SE6166's Rnet port to the terminal of the same name on
the RS room sensor.
NOTE If using shielded wire, connect the shield wire and the ground wire to the Gnd
terminal.
6 Set the Stat Select jumper to Rnet.
7 Turn on the SE6166's power.
Use 22 AWG, unshielded wire, maximum length 100 feet (30 meters).
1 Turn off the SE6166's power.
2 Wire each terminal on the SE6166's LStat port to the terminal of the same name on
the LogiStat.
3 Set the Stat Select jumper to LogiStat.
4 Turn on the SE6166's power.
To wire an RS
sensor
LogiStat wiring
specifications
To wire a LogiStat
sensor

SE6166 Controller • Rev. 4/13/2011 12 © 2011 Automated Logic Corporation
Download the following items to the SE6166's battery-backed memory:
Item
Notes
Control program Must be in
WebCTRLx.x\webroot\
<system_name>
\programs
.
DRV_SE driver Must be in
WebCTRLx.x\webroot\
<system_name>
\drivers
.
NOTE
To verify that you have the driver's latest version, go to
http://accounts.automatedlogic.com/download, then select
Drivers
>
ExecB
. Compare the latest version to the SE6166's
driver in SiteBuilder.
Editable properties
Schedules
If you change any of these items or the SE6166's address after the initial download, you
must download again. The first download takes longer than subsequent downloads.
CAUTIONS
•The SE6166 will lose stored data when you download.
•Equipment controlled by the SE6166 will shut down and restart when you download.
You download the controller from WebCTRL. If your network is complete, you can
download from any network browser. If not complete, connect a laptop with a local copy of
the system database to the SE6166's local access port. See To communicate through the
local access port (page 20).
1 On WebCTRL's NET tree, select the controller.
2 Click Downloads.
3 Do one of the following:
○If the controller is in the Downloads list, go to step 4.
○If the controller is not in the list:
a. Click Add.
b. In the pop-up, select the controller.
c. Select All Content.
d. Click Add.
e. Click Close.
4 Select the controller in the Downloads list.
5 Click Start.
NOTES
•If the download fails, locate and resolve the problem, then retry the download.
•You can also download a controller from the Devices page.
Downloading the SE6166
To download in
WebCTRL

SE6166 Controller • Rev. 4/13/2011 13 © 2011 Automated Logic Corporation
To use an input or output, you must assign it to its corresponding point in the control
program.
1 In WebCTRL's GEO tree, select the equipment controlled by the SE6166.
2 On the Properties page, select the I/O Points tab.
3 In each point's Num field, type the number of the controller's corresponding input or
output. For example, if you use DO1 on the SE6166 for the point Fan S/S, type 1in
the Num field for Fan S/S.
NOTES
○Exp (expander number) is 00 for the SE6166.
○Do not assign the same output number to more than one point.
4 Enter the appropriate values for each input and output in the remaining columns. See
Input values, Output values, Resolution values and Offset/Polarity values below.
NOTE You can also enter these values in EIKON LogicBuilder.
5 If you have not performed the initial download to the SE6166, you must download
now so you can verify inputs and outputs.
6 To verify each input's operation, force each sensor to a known value, then compare it
to the Value shown on the Properties page on the I/O Points tab.
7 To verify each output's operation, lock each output to a known condition on the I/O
Points tab, then verify that the equipment operates correctly.
Input
I/O Type
Sensor/Actuator Type
Min/Max
Analog (BAI)
0-5 Vdc
0–5 Volt
Linear Full Range
Engineering values
associated with 0 Vdc
(Min) and 5 Vdc (Max)1
0-10 Vdc
0–10 Volt
Linear Full Range
Engineering values
associated with 0 Vdc
(Min) and 10 Vdc (Max)1
2-10 Vdc
0–10 Volt
Linear w/Offset,
2–10 Volts
Engineering values
associated with 2 Vdc
(Min) and 10 Vdc (Max)1
0-20 mA
0–20 mA
Linear Full Range
Engineering values
associated with 0 mA
(Min) and 20 mA (Max)1
4-20 mA
0–20 mA
Linear w/Offset,
4–20 mA
Engineering values
associated with 4 mA
(Min) and 20 mA (Max)1
RTD
RTD Input
Select your RTD type or set
up and select a
Non-Linear,
Custom Table
2
N/A
To assign inputs or outputs to points
Input values

SE6166 Controller • Rev. 4/13/2011 14 © 2011 Automated Logic Corporation
Input
I/O Type
Sensor/Actuator Type
Min/Max
Thermistor
Thermistor
Select your Thermistor type
or set up and select a
Non-
Linear, Custom Table
2
N/A
Pulse to Analog (BPTA)
3
Pulse Counter
Counter Input
N/A N/A
Digital (Binary) (BBI)
Dry Contact
Dry Contact
N/A N/A
1The sensor reads a value and sends a corresponding signal (Volt, mA, or psi) to the SE6166's
physical input. The Analog Input microblock uses the Min and Max values to linearly translate the
signal into the engineering value used in subsequent control logic. For example, set Min to 0 and
Max to 10 for a 4–20 mA sensor that measures velocity from 0.0 to 10.0 inches/second so that
when the input reads 4 mA, the microblock outputs a value of 0. Similarly, when the input reads 8
mA, the microblock outputs a value of 2.5.
2You can set up a custom translation table (page 19) on the driver's Custom Translation Tables
pages in WebCTRL.
3 The control program must have one Pulse to Analog Input microblock for each pulse counting
input.
Output
I/O Type
Sensor/Actuator Type
Min/Max
Analog (BAO)
0-10 Vdc
Electrical
0–10 Volt
Linear Full Range
Engineering values
associated with 0 Vdc
(Min) and 10 Vdc (Max)1
2-10 Vdc
Electrical
0–10 Volt
Linear w/Offset,
2–10 Volts
Engineering values
associated with 2 Vdc
(Min) and 10 Vdc (Max)1
0-20 mA
Electrical
0–20 mA
Linear Full Range
Engineering values
associated with 0 mA
(Min) and 20 mA (Max)1
4-20 mA
Electrical
0–20 mA
Linear w/Offset,
4–20 mA
Engineering values
associated with 4 mA
(Min) and 20 mA (Max)1
Digital (Binary) (BBO)
Relay
Relay/Triac
Output
N/A N/A
1The Analog Output microblock uses the Min and Max values to linearly translate its EIKON
LogicBuilder wire value into a physical output signal (Volt, mA, or psi) sent from the SE6166 to an
actuator. For example, set Min to 0 and Max to 100 for an Analog Output microblock that
receives a 0 to 100% open signal from a PID microblock and that controls a 0–10 Vdc actuator
so that when the PID signal is 100%, the SE6166 output is 10 Vdc. Similarly, when the PID signal
is 50%, the SE6166 output is 5 Vdc.
Output values

SE6166 Controller • Rev. 4/13/2011 15 © 2011 Automated Logic Corporation
Resolution is not particular to a type of input or output, but the driver handles analog and
digital (binary) inputs and outputs differently. To set these values appropriately, you
should understand how the driver uses them.
Resolution
Notes
Analog Input
(BAI)
The driver truncates the microblock's present value according to the
resolution.
EXAMPLE
If the calculated present value is 13.789 and you set the
Resolution
to 0.1, the control program uses 13.7 for any calculations
downstream from the microblock.
Analog Output
(BAO)
The driver truncates the wire input value to the microblock before
performing any scaling calculations.
EXAMPLE
If the wire input value is 13.789 and you set the
Resolution
to 0.1, the microblock uses 13.7 for any scaling
calculations.
Digital Inputs
and Outputs
N/A
Offset/Polarity is not particular to a type of input or output, but the driver handles analog
and digital (binary) inputs and outputs differently. To set these values appropriately, you
should understand how the driver uses them.
Offset/Polarity
Notes
Analog Input
(BAI)
Offset
value (positive or negative) adds a fine adjustment to a sensor
reading after all scaling for calibration.
EXAMPLE
If a sensor reads 74.9°F when the actual measured value
is 73.6°F, enter an
Offset
of –1.3 to calibrate the sensor to the
measured value.
Analog Output
(BAO)
You can use the
Offset
value (positive or negative) to calibrate an
output, but you generally do not need to. If used, the driver adds the
offset value to the wire input value before performing any scaling
calculations to determine the SE6166's output.
Digital (Binary)
Input (BBI)
Polarity
determines the microblock's present value when no signal is
received from the equipment.
When no signal is received from the equipment, if
Polarity
is set to:
normal
—present value is
off
reversed
—present value is
on
Digital (Binary)
Output (BBO)
Polarity
determines the SE6166's output based on the control
program's signal to the microblock.
When the control program's signal to the microblock is
on
, if
Polarity
is set to:
normal
—output is
on
reversed
—output is
off
NOTE
Regardless of
Polarity
, the output will be off if the SE6166
loses power.
Resolution values
Offset/Polarity
values

SE6166 Controller • Rev. 4/13/2011 16 © 2011 Automated Logic Corporation
You can control a digital output using the Auto-Off-On switch.
If switch position is...
Normally open output contacts are...
Auto
Determined by control program
Off
Locked open
On
Locked closed
The control program can monitor the status of an Auto-Off-On switch and display the
status on the control program's Point Checkout page in WebCTRL. The Value of the point
monitoring the Auto-Off-On switch shows Off if the switch is set to Auto, and On if the
switch is set to Off or On.
To monitor an Auto-Off-On switch
1 Insert a BACnet Binary Input microblock in the control program.
2 On the microblock's Properties page in WebCTRL, set the I/O Type field to H-O-A
Status Feedback.
3 In the Input Number field, type the number of the output you want to monitor.
After you download the driver and control program(s) to the SE6166, you may want to
change the driver's properties to suit your application.
1 On WebCTRL's NET tree, click to the left of your SE6166.
2 Click to the left of Driver to see its children.
3 Make changes as needed on the Properties page for Driver and any of its children.
On the Driver page, you can change the following properties:
•BACview inactivity timeout and user password. See table below.
•Module clock synchronization and failure. See table below.
•Network Input microblock communication properties.
BACview Control
Overwrite Daylight Saving
parameters set in
BACview?
Yes
—Every download includes Daylight Saving Time
properties from System Settings page and overwrites
changes to these properties made from BACview.
No
—Download System Settings page Daylight Saving Time
properties during first download. You must make
subsequent changes from BACview. (Primarily for OEM use.)
To use the Auto-
Off-On switches
To set up the driver
Driver

SE6166 Controller • Rev. 4/13/2011 17 © 2011 Automated Logic Corporation
Keypad inactivity timeout
(minutes)
End the user session, turn off the backlight, and display the
standby screen after this period of inactivity.
Keypad user-level
password
Numeric password user must enter to access system
through BACview.
Module Clock
Clock Fail Date and Time
Date and time control program uses when controller's real-
time clock is invalid.
TIP
Use an occupied date and time (such as a Tuesday at
10 a.m.) so the equipment does not operate in unoccupied
mode if the controller loses power during occupancy.
Time Synch Sensitivity
(seconds)
When the controller receives a time synch, if the difference
between the controller's time and the time synch's time is
greater than this field's value, the controller's time is
immediately changed. If the difference is less than this
field's value, the controller's time is slowly adjusted until the
time is correct.
BACnet COV Throttling
Enable COV Throttling
Under normal circumstances, COV Throttling should be
enabled to prevent excessive network traffic if an object's
COV Increment is set too low. See EXCEPTION below.
When enabled, if an object generates excessive COV
broadcasts (5 updates in 3 seconds), the driver
automatically throttles the broadcasts to 1 per second.
Also, if the object's value updates excessively for 30
seconds, an alarm is sent to WebCTRL listing all objects
that are updating excessively. A Return-to-normal alarm is
sent only after all objects have stopped updating
excessively.
EXCEPTION: In rare circumstances, such as process
control, a subscribing object may require COV updates more
frequently than once per second. For these situations, clear
this checkbox, but make sure that your network can support
the increased traffic. You will also need to disable the
Excessive COV
alarms under the driver's
Common Alarms
.
On the Device page, you can change the following properties:
•BACnet device object properties for the SE6166
•SE6166 network communication
Configuration
NOTE
The three APDU fields refer to all networks over
which the SE6166 communicates.
Max Masters and Max Info
Frames
Apply only if the SE6166 is on an MS/TP network.
Device

SE6166 Controller • Rev. 4/13/2011 18 © 2011 Automated Logic Corporation
WebCTRL alarms use Notification Class #1. A BACnet alarm's Notification Class defines:
•Alarm priority for Alarm, Fault, and Return to Normal states
•Options for BACnet alarm acknowledgement
•Where alarms should be sent (recipients)
NOTE You may need to set up additional Notification Classes if your system will handle
Life Safety alarms or if you need to send certain types of alarms only to an alarm manager
other than WebCTRL.
Priorities
NOTE
BACnet defines the following Network message
priorities for Alarms and Events.
Priority range
Network message priority
00–63
Life Safety
64–127
Critical Equipment
128–191
Urgent
192–255
Normal
Priority of Off-Normal
BACnet priority for Alarms.
Priority of Fault
BACnet priority for Fault messages.
Priority of Normal
BACnet priority for Return-to-normal messages.
Ack Required for Off-
Normal, Fault, and
Normal
Requires a controller acknowledgement for each message
type. Normally not required.
TIP
To require operator acknowledgement for an Alarm or
Return-to-normal message (stored in the WebCTRL
database) change the acknowledgement settings on
WebCTRL's
Alarm > Enable/Disable
tab for an alarm
source or an alarm category.
Recipient List
Recipients
The first row in this list is the WebCTRL Server. Do not
delete this row. Click
Add
if you want other BACnet devices
to receive alarms.
Recipient Description
Name that appears in the
Recipients
table.
Recipient Type
Use
Address
(static binding) only for third-party BACnet
device recipients that do not support dynamic binding.
Recipient Device Object
Identifier
Type the
Device Instance
from SiteBuilder (or from the
network administrator for third-party devices) in the
#
field.
Process Identifier
Change for third-party devices that use a BACnet Process
Identifier other than 1. WebCTRL processes alarms for any
32-bit Process Identifier.
Issue Confirmed
Notifications
Select to have a device continue sending an alarm
message until it receives delivery confirmation from the
recipient.
Notification
Classes
Table of contents
Other Automated Logic Controllers manuals
Popular Controllers manuals by other brands

Raypak
Raypak TempTracker B-21 Specifications

Mitsubishi
Mitsubishi MELSEC Q Series Programming manual

Orion
Orion 41710 HP-RB1 owner's manual

Sauter Components
Sauter Components AVM 234S Series instructions

X-keys
X-keys XK-16 Stick product manual

SunMaxx Solar
SunMaxx Solar SmartMaxx-Pro-XL6D installation guide