manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. AutomationDirect
  6. •
  7. Power Supply
  8. •
  9. AutomationDirect RHINO PSS0524-100 User manual

AutomationDirect RHINO PSS0524-100 User manual

RHINO Installation Instructions for PSS0524-100 Power Supply
READ INSTRUCTIONS BEFORE INSTALLING OR OPERATING THIS DEVICE. KEEP FOR FUTURE REFERENCE.
1. Safety instructions
• To ensure sufficient convection cooling, always maintain a safety distance of M 20 mm (0.79 in) from all
ventilated surfaces while the device is in operation.
• The device is not recommended to be placed on low thermal conductive surface, for example, plastics.
• Note that the enclosure of the device can become very hot depending on the ambient temperature and load
of the power supply. Do not touch the device while it is in operation or immediately after power is turned OFF.
Risk of burning.
• Do not touch the terminals while power is being supplied. Risk of electric shock.
• Prevent any foreign metal, particles or conductors from entering the device through the openings during in-
stallation. It can cause electric shock, safety hazard, fire, and/or product failure.
• Warning: When connecting the device, secure GND connection before connecting L and N. When
disconnecting the device, remove the L and N connections before removing the GND connection.
2. Device description (Fig. 1)
(1) Input & Output terminal block connector (V1: 24VDC, V2: 5VDC)
(2) DC voltage adjustment potentiometer for V1: 24VDC
(3) DC OK indicatorLED (green)
3. Connection (Fig. 1)
The terminal block connector allows easy and fast wiring.
4. Mounting (Fig. 2)
A. Mounting holes for power supply assembly onto the mounting surface. Power supply shall be mounted on
minimum 2 mounting holes using M3 x 0.5 screw minimum 5 mm (0.19 in) length.
B. This surface belongs to customer’s system or panel where the power supply is mounted.
C. Connector:
Use flexible (stranded wire) or solid wire 22–12 AWG. The torque at the connector shall not
exceed 1.3 Nm (11.3 in-lb). The insulation stripping length should not exceed 0.28 in or 7 mm.
Fork terminal recommended for stranded wire. Refer to figure 3.
5. Installation of Mounting Accessories (Fig. 4)
• Only use M3 screw m 6 mm through the base mounting holes. This is to keep a safety distance between the
screw and internal compontents.
• Refer to Figure 4: Recommended mounting tightening torque: 0.4 to 0.8 Nm (3.5 to 7 in-lb).
FOR TECHNICAL ASSISTANCE CALL 770-844-4200
1
2
3
Top surface
Side surface
Ventilated surface
Base surface
Figure 1 - Device Descriptions
Figure 2 - Mounting
Lug Stripped wire
7mm
[0.28in]
Figure 3 - Wire Type
AutomationDirect
P/N V70GK004003 (22-18AWG)
V70GK004008 (16-14AWG)
V70GK004003 (12AWG)
or equivalent
Mounting
accessories
Chassis of
the device
Mounting
screw
6mm max.
Figure 4 - Mounting Screw
Side Mounting (Vertical) Base Mounting (Vertical) Side Mounting (Horizontal)
Technical Data For PSS0524-100
All parameters are specified at 25°C (77°F)
* Operating to 70 °C (158°F) possible with a linear derating to half power from 50°C to 70°C (122°F to 158°F)
Input (AC)
Nominal input voltage 100-240 VAC / 125-250 VDC
Voltage range 85-264 VAC (DC input range 125-375 VDC)
Frequency 47-63 Hz (0 Hz @ DC input)
Nominal current 2.0A max. @ 115 VAC, 1.1A max. @ 230 VAC
Inrush current limitation. I2t (+25 °C) typ. < 50A @ 115 VAC, < 100A @ 230 VAC
Leakage current < 1 mA @ 240 VAC
Output (DC)
Nominal output voltage / adjustment range V1: 24 VDC / 22.8-26.4 VDC; V2: 5 VDC / fixed
Output Voltage Tolerance V1: +/- 2% (initial setpoint tolerance from factory); V2: fixed
Output power* 100W
Output current V1: 0.3-4.0 Amp; V2: 0.8-7.0 Amp (each output can work within the current range, but ensure that the total output power does not exceed 100W)
PARD (ripple and noise) (20MHz) V1: <200mVpp; V2: <80mVpp (each measured with AC coupling mode, and in parallel with 0.1uF ceramic capacitor and 47uF electrolytic capacitor.)
Start-up time <1000ms@100% load and typical line input
Hold-up time > 15ms @ 115VAC, >80ms @ 230VAC with 100% load
Rise time V1: <30ms; V2: <20ms @100% load
Dynamic response (overshoot and undershoot O/P voltage) +/-5%@V1: 0-100% rated load and V2: 60%rated load and vice versa (Slew rate: 0.1A/uS)
Start-up with capacitive loads V1: 4000uF max
Efficiency > 84% @ 115 VAC & > 86% @ 230 VAC
Line regulation < 0.5% typical (@ 85-264VAC input)
Load regulation <1% typical (@85 to 264 VAC input, V1: 20-100% rated load and V2: 60% rated load and vice versa)
General Data
Type of housing Aluminum
Dimensions (L x W x H) 178 mm x 97 mm x 38 mm (7.0 in x 3.82 in x 1.50 in)
Weight 0.52 kg (1.15 lb)
MTBF > 700,000 hrs.
Connection method Screw connection
Noise Sound pressure level (SPL) < 40 dBA
Cooling Convection
Terminal input/output M3.5 x 7 Pins (Rated 300V/15A)
Wire size / torque 0.82-2.08 mm² (AWG 18-14) / 1.3 Nm (11.3 in-lb)
Shock test (non-operating) IEC60068-2-27, 30G (300m/S²) for a duration of 18ms 3 times per direction, 18 times in total
Vibration (non-operating) IEC60068-2-6, 10Hz to 150Hz @ 50m/S² (5G peak); 20 min per axis for all X, Y, Z direction
Safety / Environmental
EMC / Emissions FCC Title 47, Class B/EN55032;CISPR32, Class B
Immunity IEC61000-4-2; IEC61000-4-3; IEC61000-4-4; IEC61000-4-5; IEC61006-4-6; IEC61006-4-8; IEC61006-4-11; IEC61006-4-12
Voltage dips IEC61000-4-11 100% dip; 1 cycle (20ms); self recoverable
Galvanic isolation Input to Output : 3KVAC, Input to Ground : 1.5KVAC, Output to Ground : 0.5KVAC
Approvals UR/cUR recognized to UL60950-1 and CSA C22.2 No. 60950-1 (file no. E198298); CB test certificate and report to IEC60950-1, CE (EMC and Low Voltage directive)
E198298
RoHS Compliant Yes
Operating temperature -10 °C to +70 °C* (14°F to 158°F)
Storage temperature -25 °C to +85 °C (-13°F to 185°F)
Humidity < 95 % RH non-condensing

Other AutomationDirect Power Supply manuals

AutomationDirect PS Series User manual

AutomationDirect

AutomationDirect PS Series User manual

AutomationDirect Rhino PSB12-015-P User manual

AutomationDirect

AutomationDirect Rhino PSB12-015-P User manual

AutomationDirect P3-01AC User manual

AutomationDirect

AutomationDirect P3-01AC User manual

Popular Power Supply manuals by other brands

KEPCO JQE Series Operator's manual

KEPCO

KEPCO JQE Series Operator's manual

InWin Premium Basic Series user manual

InWin

InWin Premium Basic Series user manual

DekoLight Ultra105 Product notes

DekoLight

DekoLight Ultra105 Product notes

Smart power DSS1500RT-TBF BATTERY REPLACEMENT INSTRUCTIONS

Smart power

Smart power DSS1500RT-TBF BATTERY REPLACEMENT INSTRUCTIONS

AimTTi QL Series II instruction manual

AimTTi

AimTTi QL Series II instruction manual

Delta PM 24V200W1AI Series instruction manual

Delta

Delta PM 24V200W1AI Series instruction manual

B+K precision 1610 instruction manual

B+K precision

B+K precision 1610 instruction manual

TracoPower TEX 120-112 installation instructions

TracoPower

TracoPower TEX 120-112 installation instructions

B+K precision 1602 instruction manual

B+K precision

B+K precision 1602 instruction manual

KEPCO HSP Series quick start guide

KEPCO

KEPCO HSP Series quick start guide

KEPCO BOP 500M Operator's manual

KEPCO

KEPCO BOP 500M Operator's manual

Vox Power VCCS300 Series user manual

Vox Power

Vox Power VCCS300 Series user manual

Unit UDP3305S Series user manual

Unit

Unit UDP3305S Series user manual

Meanwell RHP-1U Series user manual

Meanwell

Meanwell RHP-1U Series user manual

B+K precision 1620A instruction manual

B+K precision

B+K precision 1620A instruction manual

Vanair AIR N ARC RELIANT 250 Series Operations manual & parts list

Vanair

Vanair AIR N ARC RELIANT 250 Series Operations manual & parts list

Delta PMC-12V035W1AA instruction manual

Delta

Delta PMC-12V035W1AA instruction manual

EcoPower APC013.350 quick start guide

EcoPower

EcoPower APC013.350 quick start guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.