Corporate Headquarters
4991 Corporate Drive, Huntsville, AL 35805
TEL 866.277.1924 FAX 256.430.4030
www.avocent.com
Avocent, the Avocent logo, The Power of Being There, Cyclades, DSR
and DSView are registered trademarks of Avocent Corporation or its
affiliates. All other marks are the property of their respective owners.
Copyright © 2006. Avocent Corporation. All rights reserved.
1206-PMIEC-DS
Hardware Specifications – IEC
Interfaces: 2 RJ-45 RS-232 serial ports (9,600 8-N-1)
10 or 20 IEC 320-C13 outlets
Power:
PM10i-10A
100–240 VAC, 10 A, IEC 320-C14 inlet
10 A max. branch circuit rating
10 A max. per IEC 320-C13 outlet
PM10i-15A*
100–240 VAC, 15 A, IEC 320-C14 inlet
15 A max. branch circuit rating
10 A max. per IEC 320-C13 outlet
PM10i-16A
100–240 VAC, 16 A, IEC 320-C20 inlet
16 A max. branch circuit rating
10 A max. per IEC 320-C13 outlet
PM10i-20A,* PM20i-20A*
100–240 VAC, 20 A, IEC 320-C20 inlet
20 A max. branch circuit rating
10 A max. per IEC 320-C13 outlet
PM10i-L30A,* PM20i-L30A*
100–240 VAC, 30 A, NEMA L6-30P twist-lock plug
30 A max. branch circuit rating
10 A max. per IEC 320-C13 outlet
Operating
Temperature: 50ºF to 122ºF (10ºC to 50ºC)
Storage
Temperature: –40ºF to 185ºF (–40ºC to 85ºC)
Humidity: 5% to 95% noncondensing
Dimensions:
(W x D x H) PM10i-10A, -15A, -16A, -20A
17 x 8 x 1.75 in. (43.18 x 20.32 x 4.45 cm)
PM10i-L30A, -32A, -32Au
17 x 12 x 1.75 in. (43.18 x 30.48 x 4.45 cm)
PM20i-16A, -20A, -L30A, -32A, -32Au
2 x 2.8 x 66 in. (5.08 x 7.11 x 167.64 cm)
Weight: PM10i 11.1 lb 5.0 kg
PM20i 14.1 lb 6.4 kg
Certifications: FCC Part 15, A CSA (fully compliant to UL standard)
EN55022, A (CE)†EN55024†
EN60950†C-Tick†
*Units are certified to 80% of max. current rating.
†International models.
Part Number Model Description
ATP3110 PM10i-10A 10 outlets, 10 A max. branch, IEC 320-C14
ATP3115-001 PM10i-15A 10 outlets, 15 A max. branch, IEC 320-C14
ATP3116 PM10i-16A 10 outlets, 16 A max. branch, IEC 320-C20
ATP3120-001 PM10i-20A 10 outlets, 20 A max. branch, IEC 320-C20
ATP3231-001 PM10i-L30A 10 outlets, 30 A max. branch, NEMA L6-30P
ATP3230 PM10i-32A 10 outlets, 32 A max. branch, IEC 309
ATP3232 PM10i-32Au 10 outlets, 32 A max. branch, unterminated
ATP2116 PM20i-16A 20 outlets, 16 A max. branch, IEC 320-C20
ATP2120-001 PM20i-20A 20 outlets, 20 A max. branch, IEC 320-C20
ATP3130-001 PM20i-L30A 20 outlets, 30 A max. branch, NEMA L6-30P
ATP2132 PM20i-32A 20 outlets, 32 A max. branch, IEC 309
ATP2131 PM20i-32Au 20 outlets, 32 A max. branch, unterminated
CAB0055 PM10i, 10 A Power Cable 8 ft, IEC320-C13 to AS3112, AUS & NZ
CAB0087 PM10i, 10 A Power Cable 8 ft, IEC320-C13 to CEE 7/7 Schuko,
Continental EU
CAB0088 PM10i, 10 A Power Cable 8 ft, IEC320-C13 to BS1363, UK &
Ireland
CAB0089 PM10i, 10 A Power Cable 8 ft, IEC320-C13 to NEMA 5-15P, USA
CAB0191 PM10i, 15 A Power Cable 8 ft, IEC320-C13 to NEMA 6-15P, USA
CAB0192 PM10i, PM20i, 16 A Power Cable 8 ft, IEC320-C19 to AS3112,
AUS & NZ
CAB0193 PM10i, PM20i, 16 A Power Cable 8 ft, IEC320-C19 to CEE 7/7
Schuko, Continental EU
CAB0194 PM10i, PM20i, 16 A Power Cable 8 ft, IEC320-C19 to BS1363,
UK & Ireland
CAB0195 PM10i, PM20i, 20 A US Power Cable 8 ft, IEC320-C19 to NEMA
5-20P, USA
CAB0197 PM10i, PM20i, 20 A US Power Cable 8 ft, IEC320-C19 to NEMA
L6-20P, USA
CAB0198 PM10i, PM20i, 20 A US Power Cable 8 ft, IEC320-C19 to NEMA
L5-20P, USA
Features
Connectivity
•RS-232 serial port for configuration and management
•Second RS-232 serial port for control-level daisy chaining
(up to 128 outlets)
•Full RS-232 signal support allows dial-in access via modem
Administration
•Name assignment per IPDU (up to 8 characters)
•Name assignment per outlet (up to 16 characters)
•Local authentication support (up to 8 users)
•Per-outlet access control lists
Management
•Independent control of power outlets (power on/off, cycle)
•Virtual lock per outlet (on or off states)
•Sequential power up with user-defined inter-outlet delays
•Global, true RMS current monitoring per IPDU
•Two-digit 7-segment LED current display
•On/off status LED per outlet
•User-defined overcurrent threshold with alarm
•Built-in visual and audible alarms
•Built-in ambient temperature sensor
Form Factors
•Industry’s highest outlet density (up to 10 outlets per 1U)
•Horizontal (1U) and vertical (0U) models address a wide variety
of applications
Integration Features*
•Integrated power management through console and KVM sessions
•CLI, menu and GUI interfaces
•Multioutlet grouping for devices with redundant power supplies
•RADIUS, TACACS+, Kerberos, LDAP, and Active Directory
server-based authentication with local fallback
•Token-based strong authentication (RSA SecurID)
•Event logging via syslog
•Fault notification via e-mail, SMS page, SNMP trap
•SNMP integration with enterprise systems
*Features available when product is used in conjunction with Cyclades ACS console servers, DSR
switches, Cyclades OnSite branch office appliance or DSView 3 management software (not included).
IEC
IEC 320-C14
IEC 320-C13 IEC 320-C20
Unterminated IEC-309
PM10i-32A, PM20i-32A
100–240 VAC, 32 A, IEC 309 plug
32 A max. branch circuit rating
10 A max. per IEC 320-C13 outlet
PM10i-32Au, PM20i-32Au
100–240 VAC, 32 A, unterminated cable
32 A max. branch circuit rating
10 A max. per IEC 320-C13 outlet
PM20i-16A
100–240 VAC, 16 A, IEC 320-C20 inlet
16 A max. branch circuit rating
10 A max. per IEC 320-C13 outlet
NEMA L6-30P
Inputs
Outlets
on fixed 8 ft power cord on fixed 8 ft power cord
modular inlet modular inlet
on fixed 8 ft power cord