Avocent Cyclades PM10-15A User manual

Admin
Branch Office
DSView 3
Management Software
Data Center
Branch Office
1
1
2
2
2
2
2
2
1
Cyclades OnSite
Branch Office Appliance IPDU Advanced Console Server Switch
Cyclades PM Cyclades ACS DSR
3
3
4
4
2
2
Cyclades PM
Intelligent Power Distribution Unit
NEMA Models
Integrated Remote Power Management and Distribution for Use in
Branch and Remote Offices
Cyclades®PM intelligent power distribution units (IPDUs) enable remote power control and
system management of IT assets in branch and remote offices. When used in conjunction with
Cyclades ACS advanced console servers and DSR®switch appliances, Cyclades PM IPDUs offer
quick problem resolution through an integrated management interface. With one or more
outlets positively associated with a particular device, users may control power “in line”
through a user-defined “hot key” or by using an intuitive Web browser-based GUI. In addition,
a special command set facilitates scripting.
Cyclades PM IPDUs — NEMA Models
Cyclades PM NEMA models are equipped with 5-15R power outlets and fixed power cables.
These units are available in 15A, 20A and 30A capacities with optional twist-lock input plugs.
Each model includes two RS-232 ports: one for management and the second for daisy-chain
expansion. Daisy chaining allows an operator to control up to 128 power outlets as a single
device. Cyclades NEMA IPDUs are designed to operate in 100-125 VAC environments.
An LED display shows the real time, true RMS current draw. Each PM unit may be configured
to sound an alarm during an overcurrent condition, and if it is connected to a Cyclades ACS
console server, the IPDU may also send notifications via e-mail messages, Short Message
Service (SMS) pager messages and SNMP traps.
Applications
•Power control over remote IT assets from
anywhere on earth
•Seamless integration with Cyclades ACS
console servers, DSR switches and
DSView®3 management software
•Proactive fault management and isolation
•Fault notifications via e-mail, SMS page
and SNMP traps
Benefits
•Restore practically any IT asset without
dispatching service personnel
•Virtually eliminate power control errors
during crisis situations
•Improve administrative efficiency with
integrated control functions
•Proactively identify and manage
problems to improve mean time between
failure (MTBF)
•Reduce risk, reduce mean time to repair
(MTTR)
•Conserve valuable IP addresses and
switch ports
Corporate Headquarters
4991 Corporate Drive, Huntsville, AL 35805
TEL 866.277.1924 FAX 256.430.4030
www.avocent.com
Avocent, the Avocent logo, The Power of Being There, Cyclades, DSR
and DSView are registered trademarks of Avocent Corporation or its
affiliates. All other marks are the property of their respective owners.
Copyright © 2006. Avocent Corporation. All rights reserved.
1206-PMNEMA-DS
Hardware Specifications – NEMA
Interfaces: 2 RJ-45 RS-232 serial ports (9,600 8-N-1)
10 or 20 NEMA 5-15R outlets
Power*:PM10-15A
100–125 VAC, 15 A, NEMA 5-15P plug
15 A max. branch circuit rating
15 A max. per NEMA 5-15R outlet
PM10-20A, PM20-20A
100–125 VAC, 20 A, NEMA 5-20P plug
20 A max. branch circuit rating
15 A max. per NEMA 5-15R outlet
PM10-L20A, PM20-L20A
100–125 VAC, 20 A, NEMA L5-20P twist-lock plug
20 A max. branch circuit rating
15 A max. per NEMA 5-15R outlet
PM10-L30A, PM20-L30A
100–125 VAC, 30 A, NEMA L5-30P twist-lock plug
30 A max. branch circuit rating
15 A max. per NEMA 5-15R outlet
Operating
Temperature: 50ºF to 122ºF (10ºC to 50ºC)
Storage
Temperature: –40ºF to 185ºF (–40ºC to 85ºC)
Humidity: 5% to 95% noncondensing
Dimensions:
(W x D x H) PM10-15A, -20A, -L20A
17 x 8.25 x 1.75 in. (43.18 x 20.96 x 4.45 cm)
PM10-L30A
17 x 8.5 x 1.75 in. (43.18 x 21.59 x 4.45 cm)
PM20-20A, -L20A, -L30A
1.8 x 2.2 x 66 in. (4.57 x 5.56 x 167.64 cm)
Weight: PM10 8.8 lb 4.0 kg
PM20 12.4 lb 5.6 kg
Certifications: FCC Part 15, A
CSA (fully compliant to UL standard)
*Units are certified to 80% of max. current rating.
Part Number Model Description
ATP3015-001 PM10-15A 10 outlets, 15 A max. branch, NEMA 5-15P
ATP3020-001 PM10-20A 10 outlets, 20 A max. branch, NEMA 5-20P
ATP3025-001 PM10-L20A 10 outlets, 20 A max. branch, NEMA L5-20P
ATP3036-001 PM10-L30A 10 outlets, 30 A max. branch, NEMA L5-30P
ATP2020-001 PM20-20A 20 outlets, 20 A max. branch, NEMA 5-20P
ATP2025-001 PM20-L20A 20 outlets, 20 A max. branch, NEMA L5-20P
ATP2035-001 PM20-L30A 20 outlets, 30 A max. branch, NEMA L5-30P
Features
Connectivity
•RS-232 serial port for configuration and management
•Second RS-232 serial port for control-level daisy chaining
(up to 128 outlets)
•Full RS-232 signal support allows dial-in access via modem
Administration
•Name assignment per IPDU (up to 8 characters)
•Name assignment per outlet (up to 16 characters)
•Local authentication support (up to 8 users)
•Per-outlet access control lists
Management
•Independent control of power outlets (power on/off, cycle)
•Virtual lock per outlet (on or off states)
•Sequential power up with user-defined inter-outlet delays
•Global, true RMS current monitoring per IPDU
•Two-digit 7-segment LED current display
•On/off status LED per outlet
•User-defined overcurrent threshold with alarm
•Built-in visual and audible alarms
•Built-in ambient temperature sensor
Form Factors
•Industry’s highest outlet density (up to 10 outlets per 1U)
•Horizontal (1U) and vertical (0U) models address a wide variety
of applications
Integration Features*
•Integrated power management through console and KVM sessions
•CLI, menu and GUI interfaces
•Multioutlet grouping for devices with redundant power supplies
•RADIUS, TACACS+, Kerberos, LDAP, and Active Directory
server-based authentication with local fallback
•Token-based strong authentication (RSA SecurID)
•Event logging via syslog
•Fault notification via e-mail, SMS page, SNMP trap
•SNMP integration with enterprise systems
*Features available when product is used in conjunction with Cyclades ACS console servers, DSR
switches, Cyclades OnSite branch office appliance or DSView 3 management software (not included).
NEMA
NEMA 5-15P
on fixed 12 ft power cord on fixed 12 ft power cord on fixed 8 ft power cord
NEMA 5-20P NEMA L5-30P
on fixed 12 ft power cord
NEMA L5-20P
NEMA 5-15R
Inputs
Outlets

Other manuals for Cyclades PM10-15A

3

This manual suits for next models

20

Other Avocent Power Distribution Unit manuals

Avocent Cyclades PM3000 User manual

Avocent

Avocent Cyclades PM3000 User manual

Avocent CYCLADES PM IPDU Installation and maintenance instructions

Avocent

Avocent CYCLADES PM IPDU Installation and maintenance instructions

Avocent Cyclades PM User manual

Avocent

Avocent Cyclades PM User manual

Avocent Cyclades PM10-15A User manual

Avocent

Avocent Cyclades PM10-15A User manual

Avocent Cyclades PM2000 User manual

Avocent

Avocent Cyclades PM2000 User manual

Avocent Cyclades PM10-15A User manual

Avocent

Avocent Cyclades PM10-15A User manual

Avocent Cyclades PM10-15A User manual

Avocent

Avocent Cyclades PM10-15A User manual

Popular Power Distribution Unit manuals by other brands

IBM DPI C13 PDU+ Installation and maintenance guide

IBM

IBM DPI C13 PDU+ Installation and maintenance guide

Woodward HighPROTEC MRU4 manual

Woodward

Woodward HighPROTEC MRU4 manual

Eaton Bussmann Series instruction sheet

Eaton

Eaton Bussmann Series instruction sheet

Panduit smartzone G5 user manual

Panduit

Panduit smartzone G5 user manual

Middle Atlantic Products HDR Series instruction sheet

Middle Atlantic Products

Middle Atlantic Products HDR Series instruction sheet

GE ALPS instruction manual

GE

GE ALPS instruction manual

PS Audio Juice Bar II Owner's reference

PS Audio

PS Audio Juice Bar II Owner's reference

Vertiv VP7557 instruction manual

Vertiv

Vertiv VP7557 instruction manual

Wöhner CrossBoard 11 225 quick start guide

Wöhner

Wöhner CrossBoard 11 225 quick start guide

Anritsu MU181800A Operation manual

Anritsu

Anritsu MU181800A Operation manual

Belkin PUREIAV PF31 user manual

Belkin

Belkin PUREIAV PF31 user manual

Eaton Mini PDU Installation and operation manual

Eaton

Eaton Mini PDU Installation and operation manual

BS 20 A Series instruction manual

BS

BS 20 A Series instruction manual

Lucent Technologies J85568C-1 product manual

Lucent Technologies

Lucent Technologies J85568C-1 product manual

Renkforce 1296315 operating instructions

Renkforce

Renkforce 1296315 operating instructions

BEGA 10 569 Instructions for use

BEGA

BEGA 10 569 Instructions for use

brennenstuhl Professional Series operating instructions

brennenstuhl

brennenstuhl Professional Series operating instructions

DAS DASnet Rack 99 230V ETH user manual

DAS

DAS DASnet Rack 99 230V ETH user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.