•Do not install the Reader in an area where sources of broadband electromagnetic noise
may exist. Avoid mounting the reader facing a cellular phone tower or in close proximity
to the base station of a 900 MHz wireless telephone.
•Keep all the Reader wiring at least 12 inches (30 cm) away from all other wiring, which
includes but is not limited to, AC power, computer data wiring, telephone wiring and
wiring to electrical locking devices.
•Do not operate the reader in close proximity to any 900 MHz wireless equipments.
4.2 Preferred Reader Installation Practices
•Avoid mounting reader under direct sun light. Sun light in some locations may cause the
reader to be operating at temperatures well above the 55 degrees Celsius limit.
•Make sure that the supply voltage of the Reader is within specification.
•Use cables with over-all braid or shield.
•For best results, run the cable in an individual conduit, at least 12 inches from AC power,
computer data cables and cables for electrical locking devices.
•Use recommended cable. Do not use any un-shielded "Twisted Pair" type cable.
•Use the largest wire gauge possible (22AWG and thicker).
•Use a dedicated power supply, where necessary.
•Use Single Point Grounding (Earthing) for black wire of cable. No ground loops. Outer
shield of cable should not be grounded.
4.3 Mounting Preference
The LR-911 has a unidirectional antenna with an antenna beam width of about 60-70 degrees.
The radiation pattern is a cone shaped beam, which should be aimed to the location where the
transponders will pass. For best results, the antenna should be mounted on a post; about 6 to 7
feet from pavement with the antenna angled slightly downward.
With a vehicle passing through the drive lane, the center of the antenna radiation pattern should
project to the windshield directly in front of the passenger side.
Be sure to elevate the antenna slightly to accommodate sport utility vehicles and minivans. Fig.
4.3-1 is a typical mounting arrangement that should work in most single lane and multi-lane
cases.
4.4 General Wiring Requirements
All the Reader wiring must be continuously shielded. AWID recommends using #22 AWG up to
#18 AWG, six or seven-conductor shielded cables. Longer distances and higher current
consumption on the power supply line may require larger gauge wires. Due to system data
termination differences, contact your panel manufacturer for the proper wire sizes to meet their
specific requirements.