SR-2400 Reader Installation Sheet
Installation Sheet
SR-2400 Low-
These instructions are for AWID’s SR-
2400 Reader, using co patible proxi ity credentials
Parts List
(a) 1 Installation Sheet for SR-2400
(b) 1 Model SR-2400 Reader
(c) 2 #6-32 × 1” thread-
(d) 3 Screw-hole plug (1 spare)
Preparation
Reader Location
: Select the reader’s ounting location. The SR
1-
3/4 inch door fra e, or to a wall or other surface. On a etal surface, read range is reduced about 20%.
The SR-
2400 ay be installed indoors or outdoors. The diagra for screw and cable holes is on page 2.
DC Power Supply: DC po
wer for this reader is usually supplied fro the +DC and Ground ter inals of the
Wiegand reader port on the syste ’s panel. If this is not possible, use a separate power supply. Power ay be
shared with other readers if the supply has sufficient current
volts DC (as low as +5 volts is OK), 750 illia peres capacity, linear
Cable
to Controller and Power Supply: 4 to 6 conductors fro the reader to the syste (2 wires for DC po
2 wires for Wiegand data, and 1 or 2 wires for external LED and Beeper/Alar , if used). 22
wires. Overall 100%
shield for both power and data
If the DC power supply is separated fro the panel’s reader port, the reader’s
connected to both
the DC power supply’s Negative ter inal and the panel reader port’s Ground ter inal.
If the separate DC power supply is close to the reader, run two 22
and 3 to 5 wires for Wiegand data (including Ground) and for the external control lines, if used.
Both cables ust be overall-
Conduit: If cables are pulled through etal conduit, the conduit should be earth
Installation
1. Connector – Cut off the 10-pin in-
line connector fro the end of the reader’s cable. D
2. ire Connections –
Connect the reader’s wires to the cable(s) for power and data.
a. First, connect black
to the panel port’s Ground ter inal, and, if separate, to the power supply Negative.
b. Connect green to the Data-
c. Connect the gray
drain wire to the shield of the connecting cable.
If power and data are in separate cables, connect all three drains/shields together near the reader.
d. If the LED and/or Beeper/Alar
e.
At the end of the cable(s) near the panel (and near the power supply, if separate), connect the
verified earth-ground.
f. Last, connect red
to the DC Positive ter inal.
Version 2.1 / Doc# 041405
2400 Reader, using co patible proxi ity credentials
: Select the reader’s ounting location. The SR
-2400 Reader
3/4 inch door fra e, or to a wall or other surface. On a etal surface, read range is reduced about 20%.
2400 ay be installed indoors or outdoors. The diagra for screw and cable holes is on page 2.
wer for this reader is usually supplied fro the +DC and Ground ter inals of the
Wiegand reader port on the syste ’s panel. If this is not possible, use a separate power supply. Power ay be
shared with other readers if the supply has sufficient current
capacity. The power supply should be close to +12
volts DC (as low as +5 volts is OK), 750 illia peres capacity, linear
-
rated, regulated DC output.
to Controller and Power Supply: 4 to 6 conductors fro the reader to the syste (2 wires for DC po
2 wires for Wiegand data, and 1 or 2 wires for external LED and Beeper/Alar , if used). 22
shield for both power and data
. 500 feet axi u length.
If the DC power supply is separated fro the panel’s reader port, the reader’s
black
the DC power supply’s Negative ter inal and the panel reader port’s Ground ter inal.
If the separate DC power supply is close to the reader, run two 22
-gauge cables –
and 3 to 5 wires for Wiegand data (including Ground) and for the external control lines, if used.
-gr
ounded (at the end far fro the reader).
Conduit: If cables are pulled through etal conduit, the conduit should be earth
-
grounded (like the cables).
line connector fro the end of the reader’s cable. D
Connect the reader’s wires to the cable(s) for power and data.
to the panel port’s Ground ter inal, and, if separate, to the power supply Negative.
. Connect white to the Data-1 ter inal.
drain wire to the shield of the connecting cable.
If power and data are in separate cables, connect all three drains/shields together near the reader.
s are used, connect the brown and/or
At the end of the cable(s) near the panel (and near the power supply, if separate), connect the
to the DC Positive ter inal.
Page 1 of 2
2400 Reader, using co patible proxi ity credentials
fro AWID.
3/4 inch door fra e, or to a wall or other surface. On a etal surface, read range is reduced about 20%.
2400 ay be installed indoors or outdoors. The diagra for screw and cable holes is on page 2.
wer for this reader is usually supplied fro the +DC and Ground ter inals of the
Wiegand reader port on the syste ’s panel. If this is not possible, use a separate power supply. Power ay be
capacity. The power supply should be close to +12
rated, regulated DC output.
to Controller and Power Supply: 4 to 6 conductors fro the reader to the syste (2 wires for DC po
wer,
2 wires for Wiegand data, and 1 or 2 wires for external LED and Beeper/Alar , if used). 22
-gauge stranded
must be
the DC power supply’s Negative ter inal and the panel reader port’s Ground ter inal.
and 3 to 5 wires for Wiegand data (including Ground) and for the external control lines, if used.
ounded (at the end far fro the reader).
grounded (like the cables).
line connector fro the end of the reader’s cable. D
iscard the connector.
to the panel port’s Ground ter inal, and, if separate, to the power supply Negative.
If power and data are in separate cables, connect all three drains/shields together near the reader.
wires.
At the end of the cable(s) near the panel (and near the power supply, if separate), connect the
shield to a