3. Putting into operation / Settings
Self test cycle
After an initial 60-second self-test cycle, the LUXOMAT®PD4-DIM/-DUO-
DIM is ready for operation.
Follow-up time for light control
The time can be set infinitely variably at between
1 and 30 minutes. The time-setting is valid for both DIM-Out-
puts of the PD4-DUO-DIM.
Symbol TEST: Test mode (Every movement switches on the
light for a period of 1 second, switching it off for a period of
2 seconds after that regardless of the level of brightness)
Twilight-switch for light control (relay 1)
The switch-on value for the light can be set at between 40
and 2000 Lux. Using the rotary control, the luminance set
points can be set as desired.
Symbol : Night-time operation
Symbol : Daytime/Night-time operation
Orientation lighting (only PD4-M-DIM)
This rotary controller serves to determine the working time of
the orientation lighting (fixed to 20 %).
“ON” for permanent orientation lighting.
“OFF” for deactiviation of orientation lighting.
Installation and Operating Instruction for B.E.G. - Occupancy detectors PD4-M-DIM and PD4-M-DUO-DIM
A circular opening of diameter 68 – 70 mm
must be produced in the ceiling. Having
connecte
d up the cables in accordance
with regulations, the detector is inserted
into the opening as shown in the drawing
opposite and fixed into position with the
assistance of the spring clips.
2a.
Installation of the LUXOMAT
®
PD4-DIM-SM
2d. Installation of the
LUXOMAT
®
PD4-DI
M
and PD4-DUO-DIM-FM
The detector can be installed in
conventional inlet-sockets mounted on
the ceiling.
The assembly plate enclosed must be
stripped off prior to installation and
secured to the ceiling using 4 screws
and ensuring that it flat. Having con-
nected up the cables in accordance
with regulations, the detector can be
placed in position as shown in the
drawing opposite and, applying a
little pressure, can then be locked into
position with the assistance of the
spring clips.
(Please refer to the connection
diagrams)
2c. Installation of the LUXOMAT®
PD4-DIM and PD4-DUO-
DIM-FC
The detector must be installed on a solid and
level surface.
The circular cover ring must be
removed prior to assembly. To do this, twist the
lens (C) anticlockwise through approximately 5°
and lift off.
Having connected up the wires in accordance with
regulations, secure the detector with 2 screws.
After installation replace the lens and lock (turn
clockwise). Mains to be connected
.
Unlocking device
Lock device
4. Settings carried out using remote control (optional)
Remote control LUXOMAT®IR-PDim
1. Check Battery:
open battery compartment by pressing the
plastic springs together and removing the
battery-holder.
2. IMPORTANT
Please pay attention, that the setting is Potentio-
meter 1 at “TEST” and Potentiometer 2 not at
“SUN”. All values which have been program-
med using the remote control will be deleted
in the event of power failure in the position
“TEST/SUN”. Please switch Potentiometer 2 over
to “MOON” or any other value.
Caution:
Settings with remote control supersede the
settings by courtesy of potentiometers.
LUXOMAT®PD4-DIM/-DUO-DIM
1. Mounting preparations
Work on the 230V mains supply
may only be carried out by qualified
professionals or by instructed persons
under the direction and supervision
of qualified skilled electrical person-
nel in accordance with electrotechni-
cal regulations.
Disconnect supply before installing!
When in Master/Slave mode of
operation, the Master-appliance
must always be installed at the
location where there is least
daylight.
Luminance set point for constant light regulation
Dimming
The following approach will prove useful when setting a
command value (example workplace): Place a luxmeter flat
on the desk, then, using the remote control IR-PDim, adjust
the light up or down by pressing the keys max or min until
the desired command value which best suits your require-
ments has been reached.
Automatic reading in the current light value
as new luminance set point
Individual light value 2 - 2500 Lux
Follow-up time
1 upto 30 min.
Orientation lighting and its follow-up time
OFF button: No orientation light
Grey button: Programming the switch-off delay time
On button: Orientation light is permanently activated.
Note: During the orientation light phase, the constant light
regulation is also active: if there is sufficient brightness,
dimming occurs < 2V and, if applicable, the lighting is
switched off.
Preset/user mode => (see page 2, point 6)
Fully automatic/semi automatic mode => (see page 2, point 5)
Semi automatic: green LED,
Fully automatic: red LED on for ca. 3 sec.
Resetting when open
All values which have been programmed using the remote
control IR-PDim are deleted, and those values which have
been set by potentiometer are activated.
Lock device
Test mode
Reset to deactivate
Resetting when closed
The lighting relay is switched off, i.e.
opened and the follow-up times reset.
Permanent protection against sabotage
This function blocks the unit permanently (green LED is illuminated).
Th
is operating mode can only be activated during the period of 5
seconds after pressing the “lock“ button. This status will only
permit actuating the function “Light on/Light off”.
The procedure for leaving this mode is as follows:
1. Switch off the current
2. Apply current for 31 - 59 seconds
3. Switch of the current again
4. Apply current
5. Open detector
Light on/off
The light will remain switched on/off for as long as movements
are detected in the areas of coverage. Once the last movement
has been detected, the light will remain on for the duration of the
follow-up time as per setting.
The appliance will then return independently to the mode selected
(Fully or Semi-automatic).
2b.
Installation of the LUXOMAT
®
PD4-DUO-
DIM-FM with socket for Surface Mounting
Before mounting the base, the
enclosed mounting plate must
be mounted true to side, i.e.
the writing must be legible.
Now fix the base on ceiling
or wall, but first put the cable
through one of the cable
openings provided.
The detector must be mounted
on a flat, solid surface.
Next prepare the sensor part by screwing in
both fixing screws according, then connect the
cable. Now insert the sensor part. Press beyond
the spring housing pressure so that the sensor
part firmly locks in place.
Option:
Wall bracket for remote
control IR-PDim
B.E.G. (UK) Ltd.
Q West
Great West Road
Brentford, Middlesex
TW8 0GP
Tel: 0870.850 5412
Fax: 0870.850 5413
E-Mail: inf[email protected].uk
Internet: www.beg-luxomat.com
B.E.G. Brück Electronic GmbH
Schlosserstr. 30
51789 Lindlar
Tel: 02266.90 12 10
Fax: 02266.45 092
E-Mail: inf[email protected]
Internet: www.beg-luxomat.com
close
open
C
25 22
18
1
6
10
3
1
TEST 6
30
R1
120 6050
40
30
15
10
A
16 10 5
2
1
30
15
TEST
2000
1200
600
200
40
5
60
5
10
30
50
ON
OFF
1
1 2
2
25 22
18
1
6
10
3
1
TEST 6
30
R1
120 6050
40
30
15
10
A
16 10 5
2
1
30
15
TEST
2000
1200
600
200
40
5
25 22
18
1
6
10
3
1
TEST 6
30
R1
2000
1200
600
200
40
max
50
Lux
1500
Lux
ON
OFF
max
50
Lux
1500
Lux
ON
OFF
max
50
Lux
1500
Lux
ON
OFF
max
50
Lux
1500
Lux
ON
OFF
max
50
Lux
1500
Lux
ON
OFF
max
50
Lux
1500
Lux
ON
OFF
max
50
Lux
1500
Lux
ON
OFF
max
50
Lux
1500
Lux
ON
OFF
max
50
Lux
1500
Lux
ON
OFF
max
50
Lux
1500
Lux
ON
OFF
20 %
max
50
Lux
1500
Lux
ON
OFF
Sensor and power supply in one case for onwall-, ceiling-
and flushmounting
Power supply: 230 V~ +6 %/-10 %
Power consumption: < 1 W
Ambient temperature: -25°C – +40°C
Degree of protection/class:
SM IP54, FC and FM IP20 / II
Settings:
locally and by remote control
Light values:
10 - 2000 Lux
Parallel operation:
Master/Slave
Area of coverage:
circular 360°
Range of coverage Ø H 2.5m / T=18°C:
seated 6.4m / tangential 24 m / radial 8 m
Recommended height for mounting:
2 - 3 m
Light measurement: Mixed light, daylight + artificial light
Lux values:
5 - 2000 Lux
• Relay/Channel 1 for light-connection
Type of contact
: NOC/with pretravel tungsten contact
Contact load:
2300 W, 230 V~, 10 A cos (ϕ) =1 /
1150 VA cos (ϕ) = 0.5
Max. no. of series-connected electronic ballasts:
depending on type and make, total connectable 140 µF.
DIM-Outputs:
PD4-DIM 1 x (1-10 V)
PD4-DUO-DIM 2 x (1-10 V)
Max. no. of series-connected electronic ballasts:
max. 50 electronic ballasts by one single supply with
max. 100m cable run and a conductur cross-section of
0.75 mm²
Time-settings:
1 - 30 min. / test
Dimensions HxØ [mm]
SM FC FM
PD4-M-DIM 76 x 101 103 x 97 74 x 97
PD4-M-DUO-DIM 95 x 106 103 x 106 74 x 106
Visible portion when built into ceiling: 30 x 97 mm
Technical data PD4-Slave
Electrical data same as above, but just one channel for
signaling motion detection.
Declaration of Conformity:
The product complies with
the low voltage recommendation 2006/95/EC and the
EMV recommendation 2004/108/EC.
13. Technical data PD4-M-DIM/-DUO-DIM
10. Wiring diagrams
11. PD4-DIM/-DUO-DIM - Connections
Type SM FC FM
PD4-DIM (Master) 92147 92247 92248
PD4-DUO-DIM (Master)
92271 92272 92273
PD4-S (Slave) 92142 92254 92163
LUXOMAT®Remote control:
IR-PDim (incl. wall bracket) 92200
Accessory:
BSK Ball basket guard 92199
Wall bracket for remote control as replacement
92100
Occupancy detectors - Covering IP23 92206
12. Article / Part-Nr. / Accessory
MAN 5554 – 02_12/2008
In case the sensing area of the LUXOMAT®PD4-DIM/
DUO-DIM is too large or areas are being covered that
should not be monitored, the range can be reduced or
limited through use of the enclosed masking clips (e).
9. Exclude sources of interference
8. Range of Coverage
6. Manual Dimming - Preset / User
(for IR-PDim functions see page 1)
You can dim manually by pressing the pushbutton
for a long time (> 2 sec). When the button is released,
the current dimming value is retained. Upon renewed
dimming, the dimming direction is reversed.
PRESET –the luminance set point is set during start-up
operation by the installer and remains unchanged.
The luminance set- point congured through manual
dimming is only applied for the time being.
Caution:
The constant light regulation is now deactivated!
The currently set articial light is retained independent
of the ambient/daylight brightness!
After switching off and then back on, the originally set
luminance set-point is reset = constant light regulation
is activated.
USER - can only be activated via the remote control!
The luminance set-point is changed upon each manual
dimming and re-adjusted by the user (Conformation
through relay clicking!)
The constant light regulation remains activated!
5. Fully / Semi automatic mode
(for IR-PDim functions see page 1)
Fully automatic operation
In this operating mode, the lighting switches automati-
cally on and off for increased comfort, depending on
presence and brightness.
Semiautomatic operation
(Semiautomatic can only be activated via the remote
control!)
In this operating condition, in order to gain increased
savings, the lighting is energized only after being manu-
ally switched on. Switch-off takes place automatically.
The semiautomatic mode basically behaves like the fully
automatic one. However, the difference is that switching-
on must always be carried out manually!
As many (closer-contact) buttons as desired can be wired
in parallel on the “S” button input (ON/OFF Dimm).
7. Manual Switching
You can switch the lighting on and off manually
by pressing the pushbutton for a short time. It will
stay on or off as long as people are detected plus the
congured follow up time.
14. LED-functional indicators, fault-finding
The functional indicators in the case of the LUXOMAT®
PD4-DIM/DUO-DIM-MASTER (red and green LED‘s)
Red LED indicating self-checking mode (over a period
of 60 seconds following mains‘-supply lock-on)
Flashing at intervals of 1 second
EEPROM/memory empty
Flashing rapidly
EEPROM/memory contains information
Red LED as an indicator of status
Flashing irregularly
Movements are detected within the area of coverage
Flashing regularly
Detector identifies bright, light off
(dependent upon operating mode)
Not illuminated
Detector identifies dark, light on
(dependent upon operating mode)
Flashing extremely rapidly
Too bright / Too dark / Undefined
Red LED as an acknowledgement of receipt for
commands from the remote control
Illuminated for 2 seconds
Signal validly received
Illuminated for 0.5 seconds
Not-accepted command, detector blocked
Flashing extremely rapidly
Not-accepted command, occurs, for example, when
an attempt is made to input twilight-value are too
bright or too dark
Green LED as an acknowledgement of receipt for
commands from the remote control
Lights up for 3 seconds
Semi automatic or user signal correctly received
Green LED as an indicator of status (only for status
“Permanent protection against sabotage”)
Flashing irregularly
Movement are detected within the area of coverage
Flashing regularly
Detector identifies bright, light off
(dependent upon operating mode)
Not illuminated
Detector identifies dark, light on
(dependent upon operating mode)
lluminated for 2 seconds
Signal validly received
(dependent upon operating mode)
PD4-DIM
PD4-DUO-DIM
Push button operation For manual switching push
the button only a short time (0.2 - 0.5 sec.)! To dim
push the button until the wished light level is arrived.
Separate reading of the lux levels for both
channels, but only one switching channel!
For manual switching push the button only a short
time (0.2 - 0.5 sec.)! To dim push the button until the
desired light level is arrived.
1-10 VDC
Terminal connection for master-/ slave-operation
MASTER SLAVE
R R N N L L
R L' N L S + -
Terminal connection PD4-M-DUO-DIM
Channel 1
1-10 VDC
Channel 2
1-10 VDC
SLAVE
R S L L' N ++
Master-/ slave-operation. The master is the only one
to read the light level and to switch the connected
loads. Independant of the light level the slave units
react to movements only by sending impulsions via
the dry contact.
No load can be connected to the dry
contact. The master-dim-occupancy detec-
tors can not be switched into parallel. For
that application please prefer the master- /
slave-installation. It is recommended to put
the master the furthest possible postion
away from the natural light source.
1-10
VDC
Terminal connection for push button operation
MASTER
+
R L' N L S
24 m
8 m
6.4 m
24 m
360°
Mounting height
2.5 m
1
2
walking across
walking towards
seated
e
Connection PD4-DUO-DIM-FM/-FC/-SM
Connection example PD4-DIM-FM
max
50
Lux
1500
Lux
ON
OFF
max
50
Lux
1500
Lux
ON
OFF
++
–NL' LSR
+2
+1
– 1-10 V
SLAVE 1-10 V
+
–NL' LSR
+
–
SLAVE
1-10 V
max
50
Lux
1500
Lux
ON
OFF
21
12 m 12 m
8 m
6.4 m
24 m
360°
Mounting height
2.5 m
2
1
quer zum Melder gehen
frontal zum Melder gehen
sitzende Tätigkeit

This manual suits for next models

3

Other B.E.G. Security Sensor manuals

B.E.G. LUXOMAT PD9-DIGI-FC User guide

B.E.G.

B.E.G. LUXOMAT PD9-DIGI-FC User guide

B.E.G. Luxomat BL4 User manual

B.E.G.

B.E.G. Luxomat BL4 User manual

B.E.G. LUXOMAT PD11-BMS-FLAT User manual

B.E.G.

B.E.G. LUXOMAT PD11-BMS-FLAT User manual

B.E.G. LUXOMAT PICO-N-M-1C-FC User guide

B.E.G.

B.E.G. LUXOMAT PICO-N-M-1C-FC User guide

B.E.G. Luxomat PD11-M-1C-FLAT User guide

B.E.G.

B.E.G. Luxomat PD11-M-1C-FLAT User guide

B.E.G. LUXOMAT 180-SC Service manual

B.E.G.

B.E.G. LUXOMAT 180-SC Service manual

B.E.G. LUXOMAT PD4-M-DALI/DSI-1C/PD4-S User guide

B.E.G.

B.E.G. LUXOMAT PD4-M-DALI/DSI-1C/PD4-S User guide

B.E.G. LUXOMAT PD4-M-DIM-Corridor User guide

B.E.G.

B.E.G. LUXOMAT PD4-M-DIM-Corridor User guide

B.E.G. Luxomat PD2-S User manual

B.E.G.

B.E.G. Luxomat PD2-S User manual

B.E.G. LUXOMAT PD2-M-DALI/DSI User guide

B.E.G.

B.E.G. LUXOMAT PD2-M-DALI/DSI User guide

B.E.G. 93385 User manual

B.E.G.

B.E.G. 93385 User manual

B.E.G. LUXOMAT PD2-M-2C-24V User guide

B.E.G.

B.E.G. LUXOMAT PD2-M-2C-24V User guide

B.E.G. PD4-M-1C-GH-SM User guide

B.E.G.

B.E.G. PD4-M-1C-GH-SM User guide

B.E.G. LUXOMAT Indoor 180-M-2C User guide

B.E.G.

B.E.G. LUXOMAT Indoor 180-M-2C User guide

B.E.G. LUXOMAT PD4-M-2C-DS User guide

B.E.G.

B.E.G. LUXOMAT PD4-M-2C-DS User guide

B.E.G. LUXOMAT PD3-1C User guide

B.E.G.

B.E.G. LUXOMAT PD3-1C User guide

B.E.G. LUXOMAT PD9-M-1C+HVAC User guide

B.E.G.

B.E.G. LUXOMAT PD9-M-1C+HVAC User guide

B.E.G. LUXOMAT PD4-S-GH User guide

B.E.G.

B.E.G. LUXOMAT PD4-S-GH User guide

B.E.G. LUXOMAT BL2 User manual

B.E.G.

B.E.G. LUXOMAT BL2 User manual

B.E.G. LUXOMAT PD4-S-DAA4G User guide

B.E.G.

B.E.G. LUXOMAT PD4-S-DAA4G User guide

B.E.G. LUXOMAT PD4-M-1C-GH-AP User manual

B.E.G.

B.E.G. LUXOMAT PD4-M-1C-GH-AP User manual

B.E.G. LUXOMAT LC-Click 140 Owner's manual

B.E.G.

B.E.G. LUXOMAT LC-Click 140 Owner's manual

B.E.G. LUXOMAT PD4-M-DIM-Corridor Series User guide

B.E.G.

B.E.G. LUXOMAT PD4-M-DIM-Corridor Series User guide

B.E.G. LUXOMAT PD9-M-2C User guide

B.E.G.

B.E.G. LUXOMAT PD9-M-2C User guide

Popular Security Sensor manuals by other brands

Aritech RF4112I4 Installation sheet

Aritech

Aritech RF4112I4 Installation sheet

Dors 1000 user manual

Dors

Dors 1000 user manual

Sperian PHD6 Reference manual

Sperian

Sperian PHD6 Reference manual

Vive LVA1074BED user manual

Vive

Vive LVA1074BED user manual

Extronic PD-22LF installation instructions

Extronic

Extronic PD-22LF installation instructions

TS-market LORNET-24 user manual

TS-market

TS-market LORNET-24 user manual

BW Technologies MicroClip XT Operator's manual

BW Technologies

BW Technologies MicroClip XT Operator's manual

Danieli Automation ID6100 instruction manual

Danieli Automation

Danieli Automation ID6100 instruction manual

schmersal CSS 34F0 operating instructions

schmersal

schmersal CSS 34F0 operating instructions

Detection Systems Security Escort SE88 Series user guide

Detection Systems

Detection Systems Security Escort SE88 Series user guide

Ecolink Firefighter CS-600 Installation manual & users guide

Ecolink

Ecolink Firefighter CS-600 Installation manual & users guide

Smoke Guard 200 Operation & maintenance manual

Smoke Guard

Smoke Guard 200 Operation & maintenance manual

Winland WaterBug WB-200 Installation & owner's manual

Winland

Winland WaterBug WB-200 Installation & owner's manual

Bosch WEU PDO 6 Original instructions

Bosch

Bosch WEU PDO 6 Original instructions

EOT ET-3500AF user guide

EOT

EOT ET-3500AF user guide

Saxby Lighting 90977 instruction manual

Saxby Lighting

Saxby Lighting 90977 instruction manual

GJD D-TECT Pet Immune GJD370 installation manual

GJD

GJD D-TECT Pet Immune GJD370 installation manual

iRay Technology NDT1013LA user manual

iRay Technology

iRay Technology NDT1013LA user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.