Baccara G75-DFC Owner's manual

G75-DFC
AUTOMATION & CONTROL
Tackling climate
change together
Differential Filtration Controller
Installation - Operation - Maintenance
IOM

2
AUTOMATION & CONTROL
G75-DFC Differential Filtration Controller
Baccara’s G75-DFC is a 1-3 stations filtration backwash controller, with optional main valve output. It can backwash the
filters by a differential pressure gauge switch signal (Baccara’s G75-DP DP switch), and/or by time intervals.
This document is the installation, operation and maintenance manual of the G75-DFC controller
Disclaimer:
This document is a user manual for Baccara Automation & Control (Baccara) product.
The information enclosed in this user manual contains restricted, privileged, proprietary and confidential data, intended
for use by Baccara Customers and Authorized Technicians only. If you are not a customer or an authorized technician,
you must not take any action in reliance upon this document, unless otherwise permitted in writing by Baccara.
The contents of this document, including without limitation all information and materials, images, illustrations, data,
drawings, names and any other such materials that appear in this document are the sole property of Baccara, including
any intellectual property rights, whether registered or not, and all know-how contained or embodied therein. Baccara
may alter, remove or change the content without any further notice. You may not reproduce, copy, modify, create
derivative works from, sell or participate in any sale of, or exploit in any way, in whole or in part, any part of this document
or its content.
The confidential nature of and/or privilege in the file enclosed is not waived or lost as a result of a mistake or error in this
file. If you received this file in error, please notify Baccara immediately at info@baccara-geva.com
This document does not replace any certified drawing, procedure or information provided by Baccara in reference to a
specific customer, site or project.
Every Baccara project’s layout, design, and application are always based on the information provided by the customer.
Baccara cannot take any responsibility for incorrect data provided by the customer.
Baccara makes no commitment to update or keep current the information in this document, and reserves the right to
make improvements to this document and/or to the products described in this document, at any time without notice.
Baccara assumes that all users understand the risks involved within this file and/or its attached materials and accepts/
assumes no liability whatsoever, whether caused by: accessing and/or relying upon this IOM and/or in any document
enclosed hereto including without limitation any links, procedures or materials.
This document is given in good faith and is not intended to impose any obligation on Baccara. While every effort has
been made to ensure the information in this IOM is accurate and complete, we would appreciate it if you brought any
errors or omissions to the attention of Baccara or consult Baccara experts or its authorized representatives for any
Copyright © 2020 - Baccara Automation & Control Kvutzat Geva 1891500 Israel

3
G75-DFC - Differential Filtration Controller | IOM
IOMIOM
INDEX
INTRODUCTION 4
General..............................................................................................................................................4
Display: ..............................................................................................................................................4
Technical Data...............................................................................................................................4
SAFETY INSTRUCTIONS 5
General..............................................................................................................................................5
Preparation to Installation .....................................................................................................5
Installation.......................................................................................................................................5
First Startup ...................................................................................................................................5
Operation and Maintenance: ...............................................................................................5
The G-75-DFC Main Components......................................................................................6
INSTALLATION 7
G75-DFC - Wires assignment...............................................................................................7
DP Switch Installation ..............................................................................................................7
LV9000 - Wire Connectors 8
(Provided by Blazing Waterproof
Small Wire Connector | LV9000).......................................................................................8
DryConn #22 to #12 AWG - Wire Connectors 8
(Provided by DryConn) ............................................................................................................8
BATTERY INSTALLATION 9
Before installing the battery.................................................................................................9
Replacing the battery:..............................................................................................................9
The User Interface 10
Monitoring the controller’s operation............................................................................10
The Auto mode.............................................................................................................................10
The OFF mode...............................................................................................................................10
Switching operation modes .................................................................................................10
The backwash cycles counter.............................................................................................10
Starting a backwash cycle manually ..............................................................................10
Programing the controller.....................................................................................................11
Factory-Set Parameters:..........................................................................................................11
User Programable Parameters:...........................................................................................11
Setting the Interval Time between backwash cycles...........................................12
Setting the number of filters: ..............................................................................................12
TROUBLESHOOTING 13
WARRANTY 14

4
AUTOMATION & CONTROL
G75-DFC Differential Filtration Controller
INTRODUCTION
General
The Baccara Differential Filtration Controller combines a Controller and a Differential Pressure Sensor (DP).
The Controller has seven wires; four wires for valves, and a molded 3 wire cable with connector for the DP switch.
The G75-DFC operates up to three G75 4Ωlatch two-wires solenoids, and has a display screen that shows the actual
differential pressure (DIF) and the pressure SET point.
The Flushing Cycle (FC) begins when the DIF reading is greater than or equal to the SET value.
Display:
The LCD display shows:
• The actual differential pressure - DIF
• The pressure set point - SET
• The flushing cycles counter - FC
• While in flushing, a Faucet icon appeases on screen
• When the battery needs replacing, a Low Battery icon appears on screen
Technical Data
Controller Set | Supplied with DFC controller, suitable for DC only, and one analog sensor
Mechanical
• Operating temperature: -10ºC to 60ºC
• Outdoor UV protection
• Front panel cover protection
• “H” proof pressure: 14 bar (203 PSI)
• “H” pressure must be ≥ “L” pressure
Electrical
DC units are powered by single 9V alkaline battery.
• Back-up memory
• Low battery warning
• Power saving LCD
Mounting
• Pressure ports 1/8” BSP/NPT (male)
• High pressure port is marked by the letter “H” on the housing
• Connect high pressure before low pressure
• Disconnect low pressure before high pressure
Controller:
• Directly on a 28mm diameter solenoid in horizontal or vertical position with adaptor
• Wall mounting with four screws
• Accessories provided | Sensor: 2” (52 mm diameter)
Software See the “Programming” chapter of this document
Options Option to change default factory settings
Standard protection class IP66 | Dust and watertight
Solenoid G75-A, GALIT Latch 4Ω, G75-A3P 1Ω

5
G75-DFC - Differential Filtration Controller | IOM
IOM
General
• Prior to installation, operation, maintenance or any other type of action carried out on the G75-DFC Filtration
Controller, read the safety, installation and operation instructions carefully.
• The G75-DFC Filtration Controller operates as part of larger irrigation systems; therefore, it is essential to comply with
all the safety instructions and standards relevant to the whole irrigation system.
• During installation, operation, or maintenance of the controller all conventional, general and local safety instructions
should be observed in order to avoid danger to the workers, the public or to property in the vicinity.
• Always use personal safety gear such as gloves, full coverage clothes, helmet, and safety goggles.
• When installing or servicing the G75-DFC Filtration Controller, use only standard and adequate tools.
• The G75-DFC Filtration Controller must be used with non-hazardous liquids.
• The filtration battery controlled by the G75-DFC Filtration Controller enters to backwashing mode automatically
without warning.
• No change or modification to the equipment is permitted without a written notification given by Baccara Automation
& Control.
• Always observe standard safety instructions and good engineering practices whilst working in the filtration system
vicinity.
• Use the G75-DFC Filtration Controller only for its intended use, as designed by the manufacturer, any misuse of the
controller may lead to undesired damage and may affect your warranty coverage.
Preparation to Installation
• Shipping and transporting the G75-DFC Filtration Controller must be done in a safe manner and in accordance with
the relevant standards and regulations.
• Electrical wiring should be performed by an authorized electrician only, using standardized and approved
components and tools. Locate the G75-DFC Filtration Controller where direct water splashing on the electrical
components of the controller is avoided. Prevent electrification; when using an external power, appropriate external
fuse and wires gauge are required.
• Install the G75-DFC Filtration Controller where the filtration battery can be clearly seen from its installation point.
Installation
• Install the G75-DFC Filtration Controller according to the detailed Installation Instructions provided with it and
according to the description given in this manual.
• Leave enough clearance around the G75-DFC Filtration Controller for easy access for safe maintenance.
• Ensure easy and safe access to the G75-DFC Filtration Controller without climbing on pipes or equipment. Make
sure that any access equipment is built, installed and used in accordance with the relevant local regulations and
standards.
First Startup
• Carefully observe the First Start-up operation instructions prior to the first operation of the G75-DFC Filtration
Controller.
• For smooth operation and performance of the G75-DFC Filtration Controller, make sure to perform the startup and first
operation procedures exactly as described in this manual.
Operation and Maintenance:
• Do not operate the G75-DFC Filtration Controller before reading carefully and being familiar with its operation
instructions.
• Never operate or use the G75-DFC Filtration Controller for purposes other than its original design and operational
envelope.
• When servicing the G75-DFC Filtration Controller, disconnect it and the filters from the power supply.
• Before returning to regular operation follow the First-time Start-up Operation instructions as detailed in this user
manual.
SAFETY INSTRUCTIONS

6
AUTOMATION & CONTROL
G75-DFC Differential Filtration Controller
The G-75-DFC Main Components
Electric cable Pipe fitting
Mounting
screws x 2
Pipe fitting
Controller (DFC display)
Upper digits
UD
Lower digits
LD
DP
Electric cable Pipe fitting
Mounting
screws x 2
Pipe fitting
Controller (DFC display)
Upper digits
UD
Lower digits
LD
DP
DP Switch
Controller (DFC display)

7
G75-DFC - Differential Filtration Controller | IOM
IOM
G75-DFC - Wires assignment
The colors and tasks of the four controller’s solenoids wires:
• Green - used as the Common Connection for the three DC solenoids (connects to the Green solenoids’ wires)
• White - Connects to the black wire of solenoid number 1 (filter valve 1)
• Yellow - Connects to the black wire of solenoid number 2 (filter valve 2)
• Blue - Connects to the black wire of solenoid number 3 (filter valve 3)
• Black wire of the Differential Pressure switch.
DP Switch Installation
Connect the controller’s molded cable with the 3-wire connector to the DP switch.
Important: Connect the High-Pressure control tube to the red connector of the DP switch first, then connect the Low-
Pressure control tube to the black connector of the DP switch. When needed disconnect the Low-pressure tube before
the High-pressure control tube.
INSTALLATION
White Black
Yellow
Blue
Green
G75
DFC
Black
Black
Red
Orange
Black
Red
Orange
Black
Di.
Sensor

8
AUTOMATION & CONTROL
G75-DFC Differential Filtration Controller
G75-DFC 22/04/21 Page 8 of 15
LV9000 - Wire Connectors
(Provided by Blazing Waterproof Small Wire Connector | LV9000)
LV9000 - Wire Connectors DryConn #22 to #12 AWG -
Wire Connectors
(Provided by Blazing Waterproof
Small Wire Connector | LV9000)
IMPORTANT: Turn off power before installing or removing
connector. Product to be used in accordance with local
and national codes.
1. Strip wires ¾” and group bare wires ends together. Do
not pre-twist solid wire.
You must pre-twist stranded wire. If using both wire
types, you must wrap stranded wire around untwisted
solid wires (1a).
2. Insert wires through flexible sealing fingers and bend
bare wire ends together into either “V-Channel.” With
proper 3/4” strip length, wire tips just reach to edge of
round hole below “V” (2a).
3. Separate connector, removing plastic “link” or “leg” from
inner sleeve. Push inner sleeve into Pre-filled outer
sleeve until double-locked. Pre-filled connection. Do not
reuse.
DryConn #22 to #12 AWG- Wire Connectors (Provide by
DryConn).
1. Strip #22 - #18 wires 1/2” (12.7mm)
And #16 - 12 wires 3/8” (9.5mm).
2. Align any frayed strands or conductors.
3. Pre-twisting unnecessary. Place stripped wires together
with ends of insulation even.
4. Twist connector onto wires pushing firmly until hand-
tight. Do not over torque.
5. Wipe sealant in and around conductors and connector
opening while tightening. Do not reuse.
(Provided by DryConn)
1. Strip wires 13 mm.
2. Align frayed strands or conductors.
3. Do not pre-twist. Place stripped wires with ends even,
lead stranded wires slightly.
4. Twist connector onto wires pushing firmly until hand-
tight. DO NOT over torque.
5. Swipe excess sealant in and around conductors.
6. DO NOT REUSE.
Operating Modes
• Auto
• Off
• FC counter rest
• Manual FC
G75-DFC 22/04/21 Page 8 of 15
LV9000 - Wire Connectors
(Provided by Blazing Waterproof Small Wire Connector | LV9000)
G75-DFC 22/04/21 Page 9 of 15
DryConn #22 to #12 AWG - Wire Connectors
(Provided by DryConn)
G75-DFC 22/04/21 Page 8 of 15
LV9000 - Wire Connectors
(Provided by Blazing Waterproof Small Wire Connector | LV9000)
G75-DFC 22/04/21 Page 8 of 15
LV9000 - Wire Connectors
(Provided by Blazing Waterproof Small Wire Connector | LV9000)
UD = Upper Digits
LD = Lower Digits

9
IOM
Baccara landscape | solenoids
BATTERY INSTALLATION
Before installing the battery
1. Read the safety instructions chapter of this document
2. Make sure that the solenoids and the DP wires are isolated from each other - prevent short circuits.
3. Using a Phillips screwdriver, remove the four battery cover screws (see the following drawing).
4. Remove the cover and the seal.
5. Install the 9V alkaline battery.
6. Reinstall the seal into its designated slot, put back the cover, and secure the four screws.
The LCD display shows:
• The actual differential pressure - DIF
• The pressure set point - SET
• The flushing cycles counter - FC
• While in flushing, a Faucet icon appeases on screen
• When the battery needs replacing, a Low Battery icon appears on screen
Replacing the battery:
1. Replace the battery at the beginning of each irrigation season and whenever the Low Battery Symbol appears on the
controller’s screen.
2. Always use the best quality battery to ensure at least one year’s autonomous operation.
3. When replacing the seal, push its tabs into the slots.
screws
Battery cover seal
When replacing the seal, push seal tabs
into slots.

10
AUTOMATION & CONTROL
G75-DFC Differential Filtration Controller
Monitoring the controller’s operation
The G75-DFC has two operation modes: Auto and Off.
The Auto mode
The Auto mode is the running mode of the controller, while in this mode the upper digits (UD) of the screen display the
current accumulation of the Flush Cycles Counter, and the lower digits (LD) display the Differential Pressure (DIF) and its
Settings Value.
When the controller backwashes the filters the Faucet Icon appears on the display’s upper line and the number of the
currently backwashed filter blinks.
When low battery state is detected the Battery Icon on the upper line of the screen starts blinking.
The controller starts a backwash cycle (FC), when the current DIF reading is greater than the SET value for (n) number of
consecutive DIF readings. The backwash cycle ends one minute after the last filter cleaning ends.
The display turns OFF (blank) if no button is pressed for one minute. Pressing any button turns the display ON.
The OFF mode
This mode is used when the operation of the controller is paused, such as off season or when controlling the filters is not
required. In the OFF mode the lower line of the controller (LD) displays OFF. In this mode the controller stops reading the
DIF switch, and the display turns OFF (blank) if no button is pressed for one minute.
Switching operation modes
When the display is turned ON pressing the MODE button shortly (about 0.5 of a second) switches the controller from
Auto to OFF mode and vice versa.
The backwash cycles counter
When the controller is in Auto mode, pressing the MODE button together with the (Plus) key displays the current
value of the counter on the display’s upper line (UD).
Resetting the counter to zero is done by pressing together the (Minus) key. The upper line displays c000 and the
controller returns to Auto mode.
Starting a backwash cycle manually
When the controller is in Auto mode, pressing the SET button together with the (Plus) key starts a backwash cycle,
the screen displays the Hand and the Faucet icons and the currently backwashing filter number blinks. The controller
returns to Auto mode once the backwash cycle ends.
To manually stop a backwash cycle press the SET button together with the (Minus) key. The cycle stops and the
controller returns to Auto mode.
The User Interface

11
IOM
Baccara landscape | solenoids
Programing the controller
The G75-DFC controller has two types of operation parameters: factory-set parameters and user programable parameters.
Factory-Set Parameters:
The factory-set parameters cannot be changed by the user and they include the following:
• Pressure units: bar
• Flush Cycle (FC) delay: 2 consecutive readings of DIF≥SET before the FC starts.
• Sample Interval time: In Auto operation mode, as the Differential Pressure (DIF) readings get closer to the SET point,
the interval time between samples shortens. The maximal interval time between readings is 60 seconds while the
minimal interval time between readings is 5 seconds.
• The delay between filters during flushing (Off time between valves) is 20 seconds.
• Number of consecutive flush cycles (FC) for alarm is 5 cycles.
• Sensor calibration - cannot be changed by the user.
User Programable Parameters:
Setting the backwash time (Valve ON Time):
The default value of this parameter is 40 seconds per filter, while the programable range is up to 5 minutes and 59
seconds.
1. Press the MODE button until the following screen appears:
2. Using the and the keys, adjust the seconds.
3. Press SET to continue.
4. Using the and the keys, adjust the minutes.
5. Press SET to complete the setting.

12
AUTOMATION & CONTROL
G75-DFC Differential Filtration Controller
Setting the Interval Time between backwash cycles
This parameter is the maximal time between two consecutive backwash cycles if no backwash cycle is triggered by the
differential pressure switch (DIF).
The programable range is up to 23 hours and 59 minutes, identified by “A”. if “A” is selected, the Interval Time parameter
is ignored.
The factory-set parameters cannot be changed by the user and they include the following:
1. Long press the MODE button followed by a short press on the MODE button: the following screen appears:
G75-DFC 22/04/21 Page 13 of 15
Setting the Interval Time between backwash cycles:
This parameter is the maximal time between two consecutive backwash cycles if no backwash cycle is triggered by the
differential pressure switch (DIF).
The programable range is up to 23 hours and 59 minutes, identified by “A”. if “A” is selected, the Interval Time
parameter is ignored.
1. Long press the MODE button followed by a short press on the MODE button: the following screen appears:
2. Using the and the keys, adjust the minutes. If “A” is selected, press SET to complete the setting.
3. Press SET to continue.
4. Using the and the keys, adjust the hours.
5. Press SET to complete the setting.
Setting the number of filters:
The parameter designates the operating filters in the system (up to three filters); the default value is #1.
Note: if needed (for technical reasons) the user may set the designated number not in a consecutive order.
1. Long press the MODE button followed by two short presses on the MODE button: the following screen
appears:
2. Using the key to select valve #1, valve #1 remans ON and valve #2 starts blinking. Use the key to
deselect a valve.
3. Repeat the above process for filters number 2 and 3.
2. Using the and the keys, adjust the minutes. If “A” is selected, press SET to complete the setting.
3. Press SET to continue.
4. Using the and the keys, adjust the hours.
5. Press SET to complete the setting.
Setting the number of filters:
The parameter designates the operating filters in the system (up to three filters); the default value is #1.
Note: if needed (for technical reasons) the user may set the designated number not in a consecutive order.
1. Long press the MODE button followed by two short presses on the MODE button: the following screen appears:
G75-DFC 22/04/21 Page 13 of 15
Setting the Interval Time between backwash cycles:
This parameter is the maximal time between two consecutive backwash cycles if no backwash cycle is triggered by the
differential pressure switch (DIF).
The programable range is up to 23 hours and 59 minutes, identified by “A”. if “A” is selected, the Interval Time
parameter is ignored.
1. Long press the MODE button followed by a short press on the MODE button: the following screen appears:
2. Using the and the keys, adjust the minutes. If “A” is selected, press SET to complete the setting.
3. Press SET to continue.
4. Using the and the keys, adjust the hours.
5. Press SET to complete the setting.
Setting the number of filters:
The parameter designates the operating filters in the system (up to three filters); the default value is #1.
Note: if needed (for technical reasons) the user may set the designated number not in a consecutive order.
1. Long press the MODE button followed by two short presses on the MODE button: the following screen
appears:
2. Using the key to select valve #1, valve #1 remans ON and valve #2 starts blinking. Use the key to
deselect a valve.
3. Repeat the above process for filters number 2 and 3.
2. Using the key to select valve #1, valve #1 remans ON and valve #2 starts blinking. Use the key to deselect a
valve.
3. Repeat the above process for filters number 2 and 3.

13
IOM
Baccara landscape | solenoids
Problem Cause Check Solution
The controller does
not perform flushing
(Automatic or Manual)
1. No water 1. Check the inlet pressure
and the system flowrate
1. Make sure that the water
supply (or the pump) is on.
2. Empty Battery 2. Check the battery 2. Replace the battery
3. Incorrect DP settings -
High
3. Check the DP across the
filtration system.
If it is lower than the
setting, make sure it is
increasing over time.
If not check the filters
integrity.
3. Lower the DP setting to
appropriate valve for the
specific water quality and
dirt load.
4. No control pressure 4. Check the control tubes
filter for clogging
4. Clean the control tubes
filter
The controller backwashes
constantly
1. Incorrect DP settings - Low 1. Check if the DP is set too
low
1. Set the DP to 0.5 bar
2. Sensor not zeroed 2. Disconnect the upstream
and downstream tubes
and check that the
pressure indicated in the
octopus app is 0
2. Disconnect the upstream
and downstream tubes
and perform ‘Zero offset’
from the advanced
settings screen
Valve does not
open / close
1. The valve number selected
is incorrect
1. Check the valve number 1. Select the correct valve
number
2. Faulty solenoid 2. Check the solenoid 2. Replace the solenoid
3. No control pressure 3. Check the control tubes’
filter for clogging
3. Clean the control tubs’
filter
4. Faulty flushing valve 4. Check the valve 4. Service or replace the
valve
Valves open instead of
closing and close instead
of opening
1. Solenoid valves in reverse
polarity
2. check if the solenoids
are connected in reverse
polarity
3. Reverse the solenoids
connections polarity
TROUBLESHOOTING

14
AUTOMATION & CONTROL
G75-DFC Differential Filtration Controller
WARRANTY
Baccara Geva ACS Ltd. (“Baccara”) products are made to exacting standards of design, material, workmanship, and quality
control and are warranted to be free of defects in material and workmanship and reasonably fit for the uses set forth in
Baccara’s catalog or the purchase order specifications for twelve (12) months from delivery or eighteen (18) months from
shipment of the product to buyer, whichever occurs first, if properly installed and maintained and under the normal use
and service for which the product is intended.
This warranty does not apply in cases of damage resulting from breakage, negligence, neglect (such as neglect in the
maintenance of the product, including the use of unfiltered water, if applicable), abuse, mishandling, normal depreciation
or wear and tear, short circuit, breakdown resulting from an irregular power supply (voltage drop), fall or any accident
including natural disaster and force major damage. For clarity, any repair of such damage, if possible, shall involve a fee.
This warranty will not apply in the event of a breakdown due to operation not in accordance with the instructions for use
mentioned in our catalog and the customer information leaflets.
Buyer shall inspect the product within ten days of delivery and must immediately notify Baccara of any defects. Failure to
so notify Baccara within such ten-day period shall constitute a waiver of all claims by Buyer against Baccara arising out
of such defects.
This warranty is in lieu of all other warranties whether they are statutory, express or implied, including, among other
things, any implied warranty of merchantability fitness for a particular purpose not set forth in Baccara’s catalog.
The warranty will expire in the event of any modification and / or repair made to the product not by a person authorized
by Baccara and / or the use of chemicals not in accordance with our instructions.
Baccara shall not be liable for any consequential, incidental, or special damages resulting directly or indirectly from the
design, material, workmanship, operation or installation of any of its products and neither assumes nor authorizes any
other person to assume on its behalf any other liability in connection therewith. Buyer’s exclusive remedy shall be the
repair or replacement, according to Baccara’s exclusive discretion, of any such defective product, after inspection and
verification by Baccara, provided that such defective product was purchased from Baccara or from any of its authorized
distributors. Service and repair pursuant to this warranty shall be provided in Baccara’s facilities and is subject to
presenting the warranty certificate, invoice and delivery of the product for inspection. Buyer shall deliver the product to
one of Baccara’s facilities and collect it from the same facility once repair is completed.
G75-DFC 22/04/21 Page 15 of 15
Warranty:
Baccara Geva ACS Ltd. ("Baccara") products are made to exacting standards of design, material, workmanship, and
quality control and are warranted to be free of defects in material and workmanship and reasonably fit for the uses set
forth in Baccara’s catalog or the purchase order specifications for twelve (12) months from delivery or eighteen (18)
months from shipment of the product to buyer, whichever occurs first, if properly installed and maintained and under
the normal use and service for which the product is intended.
This warranty does not apply in cases of damage resulting from breakage, negligence, neglect (such as neglect in the
maintenance of the product, including the use of unfiltered water, if applicable), abuse, mishandling, normal
depreciation or wear and tear, short circuit, breakdown resulting from an irregular power supply (voltage drop), fall or
any accident including natural disaster and force majeure damage. For clarity, any repair of such damage, if possible,
shall involve a fee.
This warranty will not apply in the event of a breakdown due to operation not in accordance with the instructions for
use mentioned in our catalog and the customer information leaflets.
Buyer shall inspect the product within ten days of delivery and must immediately notify Baccara of any defects. Failure
to so notify Baccara within such ten-day period shall constitute a waiver of all claims by Buyer against Baccara arising
out of such defects.
This warranty is in lieu of all other warranties whether they are statutory, express or implied, including, among other
things, any implied warranty of merchantability fitness for a particular purpose not set forth in Baccara’s catalog.
The warranty will expire in the event of any modification and / or repair made to the product not by a person
authorized by Baccara and / or the use of chemicals not in accordance with our instructions.
Baccara shall not be liable for any consequential, incidental, or special damages resulting directly or indirectly from the
design, material, workmanship, operation or installation of any of its products and neither assumes nor authorizes any
other person to assume on its behalf any other liability in connection therewith. Buyer’s exclusive remedy shall be the
repair or replacement, according to Baccara's exclusive discretion, of any such defective product, after inspection and
verification by Baccara, provided that such defective product was purchased from Baccara or from any of its authorized
distributors. Service and repair pursuant to this warranty shall be provided in Baccara's facilities and is subject to
presenting the warranty certificate, invoice and delivery of the product for inspection. Buyer shall deliver the product
to one of Baccara's facilities and collect it from the same facility once repair is completed.

AUTOMATION & CONTROL
Tackling climate
change together
08/2021
BACCARA WORLD WIDE
Baccara India
Empirical Business Center,
Oce no. 405, Navale Icon, Near
Navale Bridge, O NH4, Narhe,
Pune. PIN- 411041. [Maharashtra]
T. +91 90 499 94197
vishal@baccara-geva.com
Baccara Australia Pty Ltd.
15/347 Bay Rd. Cheltenham | VIC,
Australia 3192
T. +61 (0) 3 9553 4963
F. +61 (0) 3 9553 4965
Cheltenham, Victoria 3192 Australia
australia@baccara-geva.com
www.baccarageva.com.au
Store: www.baccarastore.com.au
BACCARA España
C/ Marqués de Monteagudo N° 24, Madrid
T. (+34) 913446310
spain@baccara-geva.com
https://www.linkedin.com/company/baccara-espana/
Baccara USA
1312 W Stanford Ave
Englewood, CO 80110
T. 719-304-4224
F. 520 746 9390
info.us@baccara-geva.com
www.baccarausa.com
BACCARA Corporate Headquarters
Kvutzat Geva, 1891500, Israel
T. +972 4 6535960
F. +972 4 6531445
info@baccara-geva.com
www.baccara-geva.com
Other manuals for G75-DFC
1
Table of contents
Other Baccara Controllers manuals
Popular Controllers manuals by other brands

Penn
Penn TC3B21 installation guide

fimotec-fischer
fimotec-fischer FS-26 operating instructions

Intiel
Intiel INT092F user manual

Black Stone
Black Stone BL 981411-0 instruction manual

Conrad
Conrad 64 05 52 operating instructions

Mitsubishi Electric
Mitsubishi Electric MELSEC iQ-R Series Safety function block reference