Accepting the meter data (OBIS-Registers)
The Interface Module XC reads the service data list / table (TS) from the meter periodically
(interval between two readings: ca. 1 second) and creates an internal table. The OBIS coded values
from the meter will be convert to the M-Bus data.
This version of the implementation supports following OBIS-Registers:
Energy: Counter values for active, reactive and apparent energy (OBIS-Registers 1.8.x, 2.8.x,
3.8.x, 4.8.x, 5.8.x, 6.8.x, 7.8.x, 8.8.x, 9.8.x and 10.8.x).
Power: Instantaneous values (average) for active and reactive power, voltage, current and line
frequency (OBIS-Registers 1.25 at seq., 3.25 at seq., 11.25 at seq., 12.25 at seq. and 14.25);
Last average value for active and reactive power (OBIS-Registers 1.5.t, 2.5.t, 3.5.t and 4.5.t).
Possible OBIS-Registers in the service data list / table TS:
Identification 0 (device address / meter number): secondary address
Identification 1: primary address; possible range: 0 to 250
Last average 1 value active power, import*
t = tariff (0..8),
s = stored values (0..99)
Last average 1 phase 1/2/3*
Last average 1 value active power, export*
Last average 1 phase 1/2/3*
Last average 1 value reactive power, import*
Last average 1 phase 1/2/3*
Last average 1 value reactive power, export*
Last average 1 phase 1/2/3*
Counter value active energy, import
Counter value active energy, export
Counter value reactive energy, import
Counter value reactive energy, export
Counter value reactive energy, Q1
Counter value reactive energy, Q2
Counter value reactive energy, Q3
Counter value reactive energy, Q4
Counter value apparent energy, import
Counter value apparent energy, export
Instantaneous value 3 active power, cumulative
Instantaneous value 3 reactive power, cumulative
Instantaneous value 3 current, cumulative
Instantaneous value 3 voltage, cumulative
Instantaneous value 3 line frequency
Instantaneous value 3 active power, phase 1/2/3
Instantaneous value 3 reactive power, phase 1/2/3
Instantaneous value 3 current, phase 1/2/3
Instantaneous value 3 voltage, phase 1/2/3