Basic Installation 3-3MN1919
3.2 Mechanical installation and cooling requirements
It is essential that you read and understand this section before beginning the
installation.
CAUTION: To prevent equipment damage, be certain that the input power has
correctly rated protective devices installed.
CAUTION: To prevent equipment damage, be certain that input and output signals
are powered and referenced correctly.
CAUTION: To ensure reliable performance of this equipment be certain that all
signals to/from the MicroFlex are shielded correctly.
CAUTION: Avoid locating the MicroFlex immediately above or beside heat generating
equipment, or directly below water steam pipes.
CAUTION: Avoid locating the MicroFlex in the vicinity of corrosive substances or
vapors, metal particles and dust.
CAUTION: Failure to meet cooling air flow requirements will result in reduced product
lifetime and/or drive overtemperature trips.
The safe operation of this equipment depends upon its use in the appropriate environment.
The following points must be considered:
HThe MicroFlex must be installed indoors, permanently fixed and located so that it can only
be accessed by service personnel using tools.
HThe maximum suggested operating altitude is 1000m (3300ft).
HThe MicroFlex must be installed where the pollution degree according to IEC664 shall not
exceed 2.
HThe 24VDC control circuit supply must be installed so that the 24VDC supplied to the unit
is isolated from the AC supply using double or reinforced insulation.
HThe input of the control circuit must be limited to Safety Extra Low Voltage circuits.
HBoth the AC supply and the 24VDC supply must be fused.
HThe atmosphere must not contain flammable gases or vapors.
HThere must not be abnormal levels of nuclear radiation or X-rays.
HThe MicroFlex must be secured by the slots in the flange. The protective earth/ground (the
threaded hole on the top of the MicroFlex) must be bonded to a safety earth/ground using
either a 25A conductor or a conductor of three times the peak current rating - whichever is
the greater.
HTo comply with CE directive 89/336/EEC an appropriate AC filter must be installed.
HThe threaded holes in the top and bottom of the enclosure are for cable clamps. The holes
are threaded for M4 bolts no longer than 11mm (0.43 in) in length.
HEach D-type connector on the front panel of the MicroFlex is secured using two hexagonal
jack screws (sometimes known as “screwlocks”). If a jack screw is removed accidentally
or lost it must be replaced with a jack screw with an external male threaded section no
longer than 10mm (0.4 in).