DETAIL OF GAS FEED REGULATOR THROTTLE
VALVE WITH DUNGS SERVOMOTOR
AGasthrottlevalvepositionreferenceindex
BGas modulation servomotor
STARTING UP AND REGULATION WITH METHANE
1) If not already done at the moment of connecting the bur-
nertothegaspipeline,itisindispensabletocarryouta
purge of the air contained in the pipeline. As a precau-
tion,specialcareshouldbetakenanddoorsandwindows
should be opened. Open the pipe union on the pipeline
situated near the burner and then open a little the gas
cut-off cock (or cocks). When the characteristic odour of
gascanbesmelled,closethecut-offcock.Waituntilthe
gaspresent inroomhasdispersed,andthenreconnect
theburnertothegaspipeline.Subsequently,re-openthe
gas cut-off cock.
2) Check that there is water in the boiler and that the sy-
stem’s gate valves are open.
3)Check,withabsolutecertaintythatthedischargeofcom-
bustion products can take place freely (boiler and chim-
ney lock-gates should be open).
4) Make sure that the voltage of the electric line to which the
burneristobeconnected,correspondstothatrequiredby
the burner and that the electrical connections (motor and
principle line) have been prepared to match the voltage
rating available. Also check that all the electrical connec-
tions carried out on the spot are in accordance with our
electric wiring diagram.
5) Make sure that the combustion head is long enough to
enterthefurnacetotheextentspeciedbytheboilerma-
nufacturer. Check that the device which regulates the air
on the combustion head is in the position considered ne-
cessary for the fuel delivery required (air passage betwe-
en the disk and the head should be considerably reduced
whenthefueldeliveryisreduced;ontheotherhand,when
thefueldeliveryisfairlyhigh,theairpassagebetweenthe
disk and the head should be relatively open). See Chapter
“AirRegulationontheCombustionHead”.
6)Apply a manometer with an adequate scale (if the entity of
pressure forecast allows it is preferable to use a column
ofwaterinstrument,donotuseapointerinstrumentfor
moderate pressure) to the pressure plug on the gas pres-
sure switch.
7) With the I/O (22) switch on the control panel switched to “O”
(0002935870n1) and the master switch turned on, manually
close the remote control switch and check that the motor revol-
ves in the correct direction. If necessary, exchange the position
of the two cables in the line that feeds the motor in order to
invert the rotation direction.
8) Now insert the switch on the command panel. The con-
trolboxreceivesvoltageinthiswayandtheprogrammer
turns on the burner as described in Chapter “Description
of Operations”. To adjust the burner see the “MPA 22”
electronic cam instructions in the attached manual code
0006080905.
9)After adjusting the “minimum”,(P1)bringtheburnerto-
wardsmaximumviathecontrolsontheMPA22keypad.
(see MPA 22 electronic cam instructions in the attached
manual code 0006080905).
10) We recommend that you carry the out combustion tests
with the appropriate instrument at all intermediate points
in the modulation range (from P1 to P9); also check the
gasowdeliveryrateviathemeter.Itisessentialtocheck,
withasuitableinstrument,thatthepercentageofcarbon
monoxide(CO)presentinthefumesdoesnotexceedthe
limitsetbyregulationsatthetimeofinstallation.”
11) Now check automatic mode working of the modulation
(see “MPA 22” electronic cam instructions in enclosed
manual code 0006080905). In this mode the equipment
receives the signal from the electronic modulation adju-
sterRWF40,iftheburnerismodulatingversion,orfrom
the thermostat or the pressure switch second stage if the
burner is progressive two stage.
12) The air pressure switch has the job of bringing the con-
trolboxtoasafetyshutdowniftheairpressureisnotat
thecorrectvalue.Therefore,theairpressureswitchmust
be regulated in such a way as to intervene by closing the
contact (foreseen to by closed while working) when the air
pressureintheburnerhasreachedasufcientlevel.The
pressure switch is self-controlled and therefore it must
close the contact (fan stops and consequently there is an
absenceofairpressureintheburner)ifitdoesnot,the
controlboxwillbeinserted(theburnerremainsatastad-
still).Itmustbespeciedthatifthecontactisnotclosed
duringworking(insufcientairpressure),thecontrolbox
willcarryoutitscycle,buttheignitiontransformerwillnot
be inserted and the gas pilot valves will not open. Con-
sequently,theburner will go to“shutdown”.Checkthat
the air pressure switch functions properly with burner at
minimumdelivery,increasetheregulatingvalueuntilitre-
aches intervention point and the burner should go to shut
down.Tounblocktheburner,pressthespecialpush-but-
tonandreturnthepressureswitchregulatortoasufcient
valueinordertomeasuretheairpressureexistingduring
the pre-ventilation phase.
13) The pressure switches which control the gas pressure
(minimum and maximum) have the job of stopping the
burner functioning when the gas pressure is not within
the values specied. From the specic functions of the
AB
0002934940