Banner R95C User manual

BANNER ENGINEERING CORP. March 13, 2023
R95C 8-Port 2-Channel Discrete IO-Link Hub Instruction Manual
Features
Models
Overview
The R95C-8B22-KQ hub connects two discrete Input/Output channels to each of the eight unique ports, providing access to monitoring and configuring those ports
with an IO-Link master. Host mirroring is available where a selected port input/output discrete signal can be routed to Pin 2 (male) on the PLC/Host connection.
Configuration
Figure 1 details the logic flow for each of the eight ports, while the tables define the configuration for each pin.
For more information, see P/N 233583 R95C-8B22-KQ IO-Link Data Reference Guide and P/N 233584 R95C-8B22-KQ IODD Files.
Figure 1: Logic Flow
• Compact bimodal to IO-Link device converter that connects discrete inputs and sends the
value to the IO-Link Master
• Outputs a discrete value as received from IO-Link Master Process Data Out
• Enabled Delay Modes: ON/OFF Delay, ON/OFF One-shot, ON/OFF/Retriggerable One-shot,
ON/OFF Pulse-stretcher and Totalizer
• Measurement Metrics: Count, Events Per Minute (EPM), and Duration
• Discrete Mirroring: Discrete signals (In/Out) from all eight ports can be mirrored to any of the
eight ports, Discrete Out, or the host white wire output
• Discrete input/output can be independently configured as NPN or PNP
• Rugged overmolded design meets IP65, IP67, and IP68
• Connects directly to a sensor or anywhere in-line for ease of use
• R95C IO-Link hubs are a quick, easy, and economical way to integrate non-IO-Link devices
into an IO-Link system
C = Converter 8B22 = 8-port,
bimodal, 2
inputs, 2 outputs
K = IO-Link Q = M12 integral
quick disconnect
Function Converter Control
C
Housing
R95 K
Connector
Q
8B22
Input State
Delay Mode
• Disabled
• On/Off Delay
• On/Off/Retriggerable One-shot
• On/Off Pulse Stretcher
• Totalizer
Host
Mirroring
Enable
Host Mirroring
Process Data
Input
Measurement
Statistics
Mirroring
Enabled
Enabled
Input
Disabled
Ouput
Process Data In
Measurement Statistics
Mirroring - Discrete 1 and 2 Output
• Discrete 1 and 2 Input State (active/inactive)
Process Data
Input
Process Data Out
• Discrete 1 and 2 Output State (active/inactive)
• Count
• RPM
• Duration
• Port/Channel selected state driven to Pin 2 (F) and Pin 4 (F)
Process Data
Output Process Data Out - Discrete 1 and 2 Output
• Process Data Out selected state driven to Pin 2 (F) and Pin 4 (F)
Host Mirroring - Discrete Host Out
• Port/Channel selected state driven to Pin 2 (M)
Discrete 1 & 2
Selection
Mirroring
Enable

2 © Banner Engineering Corp. www.bannerengineering.com
R95C 8-PORT 2-CHANNEL DISCRETE IO-LINK HUB INSTRUCTION MANUAL BANNER ENGINEERING CORP.
Table 1: Measurements – Female Pins
Port 1-Port 8 Pin Number: Description IO Metric Description
Pin 4 – Discrete 1
Pin 2 – Discrete 2
Count Value Running count of the received input pulses
Duration Value Duration of the last input pulse in µs with 500 µs granularity
Events per Minute Value
Running count of the number of pulses received averaged
over one minute
Range: 1 to 37,500
Reset Metrics • Do Not Reset
• Reset
Table 2: Pin Configuration – Female Input
Port 1-Port 8 Pin Number: Description Name Values
Pin 4 – Discrete 1
Pin 2 – Discrete 2
Discrete I/O Selection
• NPN Input
• PNP Input
• NPN Output with Pull Up
• PNP Output with Pull Down
• NPN Output with Push/Pull
• PNP Output with Push/Pull
Discrete Delay Mode
• Disabled
• On/Off Delay
• On One-shot
• Off One-shot
• On Pulse-stretcher
• Off Pulse-stretcher
• Totalizer
• Retriggerable On One-shot
• Retriggerable Off One-shot
Discrete Delay Timer 1 Discrete On Delay, One-shot, Pulse-Stretcher
Time, or Totalizer Count
Discrete Delay Timer 2 Discrete Off Delay or Totalizer Time
Mirroring Enable • Disabled
• Enabled
Mirroring Port Selection
• Port 1
• Port 2
• Port 3
• Port 4
• Port 5
• Port 6
• Port 7
• Port 8
Mirroring Channel Selection • Pin 4 – Discrete 1
• Pin 2 – Discrete 2
Mirroring Inversion • Not Inverted
• Inverted
Table 3: Pin Configuration – Male Output
Pin Number: Description Name Values
Pin 2 – Discrete Host Out
Host Mirroring Enable • Disabled
• Enabled
Host Mirroring Port Selection
• Port 1
• Port 2
• Port 3
• Port 4
• Port 5
• Port 6
• Port 7
• Port 8
Host Mirroring Channel Selection • Pin 4 – Discrete 1
• Pin 2 – Discrete 2
Host Mirroring Inversion • Not Inverted
• Inverted
Host Mirroring Polarity • PNP
• NPN
Host Mirroring Output Type • Open Collector
• Push/Pull

© Banner Engineering Corp. www.bannerengineering.com 3
BANNER ENGINEERING CORP R95C 8-PORT 2-CHANNEL DISCRETE IO-LINK HUB INSTRUCTION MANUAL
IO-Link®
IO-Link® is a point-to-point communication link between a master device and a sensor and/or light. It can be used to automatically parameterize sensors or lights and
to transmit process data. For the latest IO-Link protocol and specifications, please visit www.io-link.com.
For the latest IODD files, please refer to the Banner Engineering Corp website at: www.bannerengineering.com.
Mechanical Installation
Install the R95C to allow access for functional checks, maintenance, and service or replacement. Do not install the R95C in such a way to allow for intentional defeat.
Fasteners must be of sufficient strength to guard against breakage. The use of permanent fasteners or locking hardware is recommended to prevent the loosening
or displacement of the device. The mounting hole (4.5 mm) in the R95C accepts M4 (#8) hardware. See the figure below to help in determining the minimum screw
length.
CAUTION: Do not overtighten the R95C's mounting screw during installation. Overtightening can affect the performance of the R95C.
Wiring
Status Indicators
The R95C 8-Port 2-Channel Discrete Bimodal IO-Link Hub has two matching amber LED indicators, one for each channel, on both sides for each discrete device port
to allow for installation needs and still provide adequate indication visibility. There is also an additional amber LED indicator on both sides of the converter, which is
specific to the IO-Link communication.
Port 1-Port 8 — Female Pin Signal Description
1 18 V DC to 30 V DC
2 Discrete 2 (IN/OUT)
3 Ground
4 Discrete 1 (IN/OUT)
Male Pin Signal Description
1 18 V DC to 30 V DC
2 Banner-specific
3 Ground
4 IO-Link
17.0 mm
MOUNTING SCREW
2
3
4
1
1
4
3
2

4 © Banner Engineering Corp. www.bannerengineering.com
R95C 8-PORT 2-CHANNEL DISCRETE IO-LINK HUB INSTRUCTION MANUAL BANNER ENGINEERING CORP.
Specifications
Required Overcurrent Protection
WARNING: Electrical connections must be made by qualified personnel in accordance with local and national electrical codes and regulations.
Overcurrent protection is required to be provided by end product application per the supplied table.
Overcurrent protection may be provided with external fusing or via Current Limiting, Class 2 Power Supply.
Supply wiring leads < 24 AWG shall not be spliced.
For additional product support, go to www.bannerengineering.com.
LED Indication Status
Discrete Device Amber LEDs Off Discrete In and Out are inactive
Solid Amber Discrete In or Out is active
IO-Link Communication Amber LED Off IO-Link communications are not present
Flashing Amber (900 ms On, 100 ms Off) IO-Link communications are active
Power Indicator Green LED Off Power off
Solid Green Power on
Supply Voltage
18 V DC to 30 V DC at 400 mA maximum (exclusive of load)
Power Pass-Through Current
500 mA per port maximum
Discrete Output Load Rating
200 mA
Supply Protection Circuitry
Protected against reverse polarity and transient voltages
Leakage Current Immunity
400 µA
Construction
Coupling Material: Nickel-plated brass
Connector Body: PVC translucent black
Vibration and Mechanical Shock
Meets IEC 60068-2-6 requirements (Vibration: 10 Hz to 55 Hz, 0.5 mm
amplitude, 5 minutes sweep, 30 minutes dwell)
Meets IEC 60068-2-27 requirements (Shock: 15G 11 ms duration, half sine
wave)
Environmental Rating
IP65, IP67, IP68
NEMA/UL Type 1
Indicators
Green: Power
Amber: IO-Link communications
Amber: 2x Discrete IN/OUT status
Connections
(8) Integral 4-pin M12 female quick disconnect
(1) Integral 4-pin M12 male quick-disconnect connector
Operating Conditions
Temperature: –40 °C to +70 °C (–40 °F to +158 °F)
90% at +70 °C maximum relative humidity (non-condensing)
Storage Temperature: –40 °C to +80 °C (–40 °F to +176 °F)
Supply Wiring (AWG) Required Overcurrent Protection (A) Supply Wiring (AWG) Required Overcurrent Protection (A)
20 5.0 26 1.0
22 3.0 28 0.8
1
5
2
6
3
7
4
8
Com LED
(on either side)
Power LED
(on either side)
Device LEDs x16
(on either side)
LED 1 = Discrete 1 In/Out
LED 2 = Discrete 2 In/Out
1
1
2
2
1
1
2
2
1
1
2
2
1
1
2
2
5RWDWHÛ
4
8
3
7
2
6
1
5
2
2
1
1
2
2
1
1
2
2
1
1
2
2
1
1

© Banner Engineering Corp. www.bannerengineering.com 5
BANNER ENGINEERING CORP R95C 8-PORT 2-CHANNEL DISCRETE IO-LINK HUB INSTRUCTION MANUAL
Certifications
FCC Part 15 Class B
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to
provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and,
if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interfer-
ence will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning
the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
• Consult the dealer or an experienced radio/TV technician for help.
Industry Canada
This device complies with CAN ICES-3 (B)/NMB-3(B). Operation is subject to the following two conditions: 1) This device may not cause harmful interference; and 2)
This device must accept any interference received, including interference that may cause undesired operation.
Cet appareil est conforme à la norme NMB-3(B). Le fonctionnement est soumis aux deux conditions suivantes : (1) ce dispositif ne peut pas occasionner d'inter-
férences, et (2) il doit tolérer toute interférence, y compris celles susceptibles de provoquer un fonctionnement non souhaité du dispositif.
Dimensions
All measurements are listed in millimeters [inches], unless noted otherwise.
24 1.0 30 0.5
Banner Engineering BV
Park Lane, Culliganlaan 2F
bus 3, 1831 Diegem,
BELGIUM
Turck Banner LTD Blenheim
House, Blenheim Court, Wickford,
Essex SS11 8YT, Great Britain
Supply Wiring (AWG) Required Overcurrent Protection (A) Supply Wiring (AWG) Required Overcurrent Protection (A)

6 © Banner Engineering Corp. www.bannerengineering.com
R95C 8-PORT 2-CHANNEL DISCRETE IO-LINK HUB INSTRUCTION MANUAL BANNER ENGINEERING CORP.
Accessories
Cordsets
Banner Engineering Corp. Limited Warranty
Document title: R95C 8-Port 2-Channel Discrete Bimodal IO-Link Hub Instruction Manual
Part number: 233582
Revision: B
Original Instructions
© Banner Engineering Corp. All rights reserved.
4-Pin Threaded M12 Cordsets—Double Ended
Model Length Style Dimensions Pinout
MQDEC-401SS 0.31 m (1 ft)
Male
Straight/Female
Straight
Female
Male
1 = Brown
2 = White
3 = Blue
4 = Black
MQDEC-403SS 0.91 m (2.99 ft)
MQDEC-406SS 1.83 m (6 ft)
MQDEC-412SS 3.66 m (12 ft)
MQDEC-420SS 6.10 m (20 ft)
MQDEC-430SS 9.14 m (30.2 ft)
MQDEC-450SS 15.2 m (49.9 ft)
Banner Engineering Corp. warrants its products to be free from defects in material and workmanship for one year following the date of shipment. Banner
Engineering Corp. will repair or replace, free of charge, any product of its manufacture which, at the time it is returned to the factory, is found to have been
defective during the warranty period. This warranty does not cover damage or liability for misuse, abuse, or the improper application or installation of the Banner
product.
THIS LIMITED WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES WHETHER EXPRESS OR IMPLIED (INCLUDING, WITHOUT
LIMITATION, ANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE), AND WHETHER ARISING UNDER COURSE OF
PERFORMANCE, COURSE OF DEALING OR TRADE USAGE.
This Warranty is exclusive and limited to repair or, at the discretion of Banner Engineering Corp., replacement. IN NO EVENT SHALL BANNER ENGINEERING
CORP. BE LIABLE TO BUYER OR ANY OTHER PERSON OR ENTITY FOR ANY EXTRA COSTS, EXPENSES, LOSSES, LOSS OF PROFITS, OR ANY
INCIDENTAL, CONSEQUENTIAL OR SPECIAL DAMAGES RESULTING FROM ANY PRODUCT DEFECT OR FROM THE USE OR INABILITY TO USE THE
PRODUCT, WHETHER ARISING IN CONTRACT OR WARRANTY, STATUTE, TORT, STRICT LIABILITY, NEGLIGENCE, OR OTHERWISE.
Banner Engineering Corp. reserves the right to change, modify or improve the design of the product without assuming any obligations or liabilities relating to any
product previously manufactured by Banner Engineering Corp. Any misuse, abuse, or improper application or installation of this product or use of the product for
personal protection applications when the product is identified as not intended for such purposes will void the product warranty. Any modifications to this product
without prior express approval by Banner Engineering Corp will void the product warranties. All specifications published in this document are subject to change;
Banner reserves the right to modify product specifications or update documentation at any time. Specifications and product information in English supersede that
which is provided in any other language. For the most recent version of any documentation, refer to: www.bannerengineering.com.
For patent information, see www.bannerengineering.com/patents.
40 Typ.
[1.58"]
ø 14.5 [0.57"]
M12 x 1
44 Typ.
[1.73"]
ø 14.5 [0.57"]
M12 x 1
2
3
4
1
1
4
3
2
233582
Table of contents
Other Banner Switch manuals

Banner
Banner PICO-GUARD SFI-D1EDPXT6 User manual

Banner
Banner R95C Series User manual

Banner
Banner SI-GL42 Series User manual

Banner
Banner SI-RF Series User manual

Banner
Banner SI-HG63 Series User manual

Banner
Banner SI-HG63FQDR User manual

Banner
Banner R95C User manual

Banner
Banner SI-RFST-UP8 User manual

Banner
Banner RP-LS42F LE Series User manual

Banner
Banner RP-LS42F LE Series User manual