10 User Level Dialog
(xxxx = 125% v. f. s.)
Dialog
item
Value Description
MENU -1... 9999 Primary display, e.g. the value selected in the DISP menu
DISP ----- Display value which should be permanently in the display:
act actually measured value
sp1 switching point SP1
SP2 switching point SP2
max maximum peak value
min minimum peak value
ACT. -1... 9999 Display of actually measured value in bar
UNIT
(only
V7.X)
Fixing the unit
(The unit is shown in the display appr. every 30 sec for appr. 5 sec)
bar bar = bar
psi psi x = psi x 10
psi psi = psi
hPa hPa = Hekto-Pascal
mbar mbar = millibar
NOTE: no choice of the unit possible at UTS 7. Only °C possible!
SP.1 ----- none switching output SP1 deactivated
wind window technology
stnd standard evaluation SP1
erro error output
ON-1 -1... xxxx Switch-on point for SP1;
NOTE: if the ON-value is set smaller than the OFF-value you receive a decreasing
switch point evaluation.
OFF-1 -1... xxxx Switch-off point for SP1
DLY1 0.0... 9.9 s Switch-on / switch-off delay for SP2 in seconds
INV-1 ----- Inversion of switching output SP1
hlfs high-level-fail-save (normally open function)
Ilfs low-level-fail-save (normally closed function)
SP.2 ----- none Switching output deactivated
wind window technology
stnd standard evaluation SP2
erro error output
Dialog
item
Value Description (continued)
ON-2 -1... xxxx Switch-on point for SP2
NOTE: if the ON-value is set smaller than the OFF-value you receive a
decreasing switch point evaluation.
OFF-2 -1... xxxx Switch-off point for SP2
DLY2 0.0... 9.9 s Switch-on / switch-off delay for SP2 in seconds
INV-2 ----- Inversion of switching output SP2
hlfs high-level-fail-save (normally open function)
llfs low-level-fail-save (normally closed function)
MAX -1 ... xxxx Display of the peak value "max“
CLRH ----- Delete the maximum value memory
----- no deletion
clr delete value
CDLY 0.0... 9.9 s Time setting to delete the maximum value memory after switching
point SP1 is reached (manual deletion is still possible)
MIN -1... xxxx Display of the peak value "min“
CLRL ----- Delete the minimum value memory
----- no deletion
clr delete value
OFFS -9.9... +xx Measured value offset in bar
CUT 0.0... +xx Cut-off i.e. signal suppression at measuring range start in bar
DLDS 0.0... 9.9 s Time delay for currently displayed value in seconds
ERRC ----- Error display:
0: -ok- no error
1: max exceeding pos. meas. range
2: min exceeding neg. meas. range
3: dig1 switching output 1 error
4: dig2 switching output 2 error
5: anao analog output error
6: sens sensor error
7: data data error (EEProm)
8: prog program error
9: cal calibration error