9424200772 Rev D 1
BE1-11 Quick Start Guide
Quick Start Guide
This guide provides basic installation and setup information about BE1-11 Protection Systems. BE1-11
protection systems are delivered with a BE1-11 product CD. Upon receipt of the BE1-11, check the model
and style number against the requisition and packing list for agreement. If there is evidence of shipping
damage, file a claim with the carrier, and notify the Basler Electric Regional Sales Office, your sales
representative, or a sales representative at Basler Electric, Highland, Illinois.
If the BE1-11 is not installed immediately, store it in the original shipping carton in a moisture- and dust-
free environment.
Included on the BE1-11 product CD:
•BESTCOMSPlus®Software
•BESTwave™Software
•BEST61850™Software
•Quick Start Guide
•Communications Quick Start Guide
•Instruction Manual
•Modbus®Instruction Manual
•DNP Instruction Manual
•IEC 61850 Instruction Manual
Do not connect a USB cable between the PC and the BE1-11 until
BESTCOMSPlus is installed. Connecting a USB cable before setup is
complete may result in errors.
Maintenance
Preventive maintenance consists of periodic replacement of the backup battery and periodically checking
that the connections between the BE1-11 and the system are clean and tight. The front cover should be
removed only when replacing the backup battery for the real-time clock. Ensure that the BE1-11 is
powered off and taken out of service before removing the front cover. BE1-11 units are manufactured
using state-of-the-art, surface-mount technology. As such, Basler Electric recommends that no repair
procedures be attempted by anyone other than Basler Electric personnel.
Storage
This device contains long-life aluminum electrolytic capacitors. For devices that are not in service (spares
in storage), the life of these capacitors can be maximized by energizing the device for 30 minutes once
per year.
Install BESTCOMSPlus®Software
BESTCOMSPlussoftware is built on the Microsoft®.NET Framework. The setup utility that installs
BESTCOMSPlus on your PC also installs the BE1-11 plugin and the required version of .NET Framework
(if not already installed). BESTCOMSPlus operates with systems using Windows®XP 32-bit SP3,
Windows Vista 32-bit SP1 (all editions), Windows 7 32-bit (all editions), Windows 7 64-bit (all editions),
Windows 8, and Windows 10. System recommendations for the .NET Framework and BESTCOMSPlus
are listed in Table 1.