BD Sensors DS 6 User manual

www.bdsensors.com
EN
Operating Manual
Pressure Switch DS 6
Headquarters
BD|SENSORS GmbH
BD-Sensors-Str. 1
D - 95199 Thierstein
Germany
Tel.: +49 (0) 9235-9811-0
Fax: +49 (0) 9235-9811-11
Eastern Europe
BD|SENSORS s.r.o.
Hradištská 817
CZ - 687 08 Buchlovice
Czech Republic
Tel.: +42 (0) 572-4110 11
Fax: +42 (0) 572-4114 97
Russia
BD|SENSORS RUS
39a, Varshavskoe shosse
RU - Moscow 117105
Russia
Tel.: +7 (0) 95-380 1683
Fax: +7 (0) 95-380 1681
China
BD|SENSORS China Co, Ltd.
Room B, 2nd Floor, Building 10,
No. 1188 Lianhang Rd.
201112 Shanghai,
China
Tel.: +86 (0) 21-51600 190
Fax: +86 (0) 21-33600 613
further agencies in:
EUROPE
Belgium
Denmark
Finland
France
Great Britain
Greece
Italy
Lithuania
Luxemburg
Netherlands
Norway
Poland
Portugal
Romania
Sweden
Switzerland
Slovakia
Spain
Turkey
UK
Ukraine
AFRICA
Egypt
South Africa
ASIA
India
Iran
Israel
Japan
Kazakhstan
Malaysia
Singapore
Taiwan
Thailand
Vietnam
AUSTRALIA
The addresses of our distribution partners are listed on our
homepage www.bdsensors.com. It is possible to download
data sheets, operating manuals, ordering codes and certifi-
cates, as well.
1. General information
1.1 Information on the operating manual
This operating manual contains important information on
proper usage of the device. Read this operating manual
carefully before installing and starting up the pressure
measuring device.
Adhere to the safety notes and operating instructions which
are given in the operating manual. Additionally applicable
regulations regarding occupational safety, accident preven-
tion as well as national installation standards and engineer-
ing rules must be complied with!
This operating manual is part of the device, must be kept
nearest its location, always accessible to all employees.
This operating manual is copyrighted. The contents of this
operating manual reflect the version available at the time of
printing. It has been issued to our best knowledge.
BD|SENSORS is not liable for any incorrect statements and
their effects.
– Technical modifications reserved –
1.2 Symbols used
DANGER! – dangerous situation, which may result in
death or serious injuries
WARNING! – potentially dangerous situation, which
may result in death or serious injuries
CAUTION! – potentially dangerous situation, which may
result in minor injuries
!
CAUTION! – potentially dangerous situation, which may
result in physical damage
NOTE – tips and information to ensure a failure-free
operation
1.3 Target group
WARNING! To avoid operator hazards and damages of
the device, the following instructions have to be worked
out by qualified technical personnel.
1.4 Limitation of liability
By non-observance of the operating manual, inappropriate
use, modification or damage, no liability is assumed and
warranty claims will be excluded.
1.5 Intended use
- The electronic pressure switch DS 6 has been designed
for universal use. Preferred areas of use are, among
others, machine building industry, hydraulics, meas-
urement, and controls. Media wetted materials are
stainless steel for the pressure port, ceramics Al2O3for
the pressure sensor, and FKM or EPDM for the seals.
These materials have been chosen particularly in order
to achieve high media compatibility even in standard
version. The new microcontroller switching electronics
offer – besides the standard functions – many additional
features for an optimal adaptation to the measuring re-
quirements. The one or two freely programmable con-
tacts whose status is indicated by differently coloured
LEDs can be quickly and comfortably configured either
by means of the optionally available configuration kits
CIS 685 or CIS 686 or the programming device P6.
- It is the operator's responsibility to check and verify the
suitability of the device for the intended application. If
any doubts remain, please contact our sales department
in order to ensure proper usage. BD|SENSORS is not
liable for any incorrect selections and their effects!
- It has to be ensured, that this medium is compatible with
the media wetted parts.
- The technical data listed in the current data sheet are
engaging. If the data sheet is not available, please order
or download it from our homepage.
(http://www.bdsensors.com)
WARNING! – Danger through improper usage!
1.6 Package contents
Please verify that all listed parts are undamaged included in
the delivery and check for consistency specified in your
order:
- pressure switch DS 6
- mounting instructions
2. Product identification
The device can be identified by its manufacturing label. It
provides the most important data. By the ordering code the
product can be clearly identified.
!
The manufacturing label must not be removed from the
device!
3. Mechanical installation
3.1 General mounting and safety instructions
WARNING! Install the device only when depressurized
and currentless!
WARNING! This device may only be installed by
qualified technical personnel who has read and under-
stood the operating manual!
!
Handle this high-sensitive electronic precision
measuring device with care, both in packed and
unpacked condition!
!
There are no modifications/changes to be made on the
device.
!
Do not throw the package/device!
!
To avoid damaging the diaphragm, remove packaging
and protective cap directly before starting assembly.
The delivered protective cap has to be stored!
!
Place the protective cap on the pressure port again
immediately after disassembling.
!
Handle the unprotected diaphragm very carefully - it is
very sensitive and may be easily damaged.
!
Do not use any force when installing the device to
prevent damage of the device and the plant!
!
For installations outdoor and in damp areas following
these instructions:
- To prevent moisture admission in the plug the de-
vice should be installed electrically after mounting,
at once. Otherwise a moisture admission has to be
blocked e.g. by using a suitable protection cap.
(The ingress protection in the data sheet is valid
for the connected device.)
- Choose an assembly position, which allows the
flow-off of splashed water and condensation. Avoid
permanent fluid at sealing surfaces!
- Install the device in such a way that it is protected
from direct solar irradiation. Direct solar irradiation
can lead to the permissible operating temperature
being overstepped in the worst case. By this the
operability of the device can be affected or dam-
aged. If the internal pressure increases due to so-
lar irradiation, measurement errors may be caused.
In hydraulic systems, position the device in such a way
that the pressure port points upward (ventilation).
Provide a cooling line when using the device in steam
piping.
Take note that no inadmissibly high mechanical
stresses occur at the pressure port as a result of the
installation, since this may cause a shifting of the
characteristic curve or to the demage.
If there is any danger of damage by lightning or
overpressure when the device is installed outdoor, we
suggest putting a sufficiently dimensioned overpressure
protection between the supply or switch cabinet and the
device.
3.2 Mounting and safety instructions oxygen
DANGER! Explosion hazard, with devices for oxygen
applications, when used improperly. To ensure a usage
without danger, the following points must be adhered to:
- Make sure, your device has been ordered and de-
livered as a special version for oxygen applica-
tions. You can check the manufacturing label (see
figure 1). If the ordering code ends with "007", then
the device is suitable for oxygen applications.
- At time of delivery the device is packed into a plas-
tic bag in order to prevent it from impurity. Please
observe the indication label "Device for oxygen,
unpack only directly before assembling". Also,
avoid any skin contacts during unpacking and as-
sembly, in order to prevent greasy residues on the
device.
- During installation, the respective explosion protec-
tion regulations have to be met. Check, if ATEX-
approval is necessary for this type (oxygen) de-
vice. (the delivered device has no ATEX-approval)
- Note the entire design requirements meet the
standard demand of BAM (DIN 19247).
- Transmitters with o-rings of FKM Vi 567:
permissible maximum values: 25 bar / 150° C
(BAM approval)
3.3 Installation steps
- Carefully remove the pressure measuring device from
the package and dispose of the package properly.
- Check to ensure that the O-ring fits properly into the
groove (seal is supplied with device).
- Ensure that the surface on which the seal should be
placed is perfectly smooth and clean.
- Screw the pressure switch by hand into the thread and
tighten it with a wrench (torque approx. 5 Nm).
- The indicated tightening torques must not be
exceeded!
Fig.1 manufacturing label
pin
configuration
ordering
code
type
designation
supply
input
set point 1 and 2
with setting
serial
number
DS6_EDS_E_200418
4. Electrical Installation
WARNING! Install the device in currentless environ-
ments only!
Establish the electrical connection of the device according to
the technical data shown on the manufacturing label, the
following table and the respective wiring diagram.
Wiring diagrams:
1 contact
2 contacts
Pin configuration:
Electrical
connection M12x1 (4-pin),
metal
M8x1 (4-pin),
metal
Supply +
Supply –
Contact 1
Contact 2
1
3
4
2
1
3
4
2
Shield plug housing plug housing
For the electrical connection a shielded and twisted
multicore cable is recommended.
5. Initial start-up
WARNING! Before start-up, the user has to check for
proper installation and for any visible defects.
WARNING! The device can be started and operated by
authorized personnel only, who have read and under-
stood the operating manual!
WARNING! The device has to be used within the
technical specifications, only (compare the data in the
data sheet)!
6. Operation
Set point adjustment – factory set
The set points are factory set either to ordered values or to
BD|SENSORS standard:
Switching function n/o (normally opened)
Switching mode hysteresis mode
Switch on point 80 % FSO
Switch off point 75 % FSO
Switch on/switch off delay off
Set point adjustment – user specific
Every DS 6 can be quickly and comfortably configured either
by means of the optionally available configuration kits
CIS 685 or CIS 686 as well as the programming device P6.
These devices can be ordered as accessories from
BD SENSORS. In the following, a short description of these
possibilities is given:
Configuration via configuration kit
The DS 6 can be connected to a PC via the programming
adapter and configured by the programming-software P-Set.
The setting of the following parameters for both set points is
possible:
- operation mode (hysteresis or window mode)
- switch-on and switch-off point
- set point negation
- switch on and switch off delay
The programming adapter is part of the programming kits
CIS 685 and CIS 686 which contains i.a. a CD-ROM with the
configuration software P-Set. All cables required for connect-
ing the pressure switch have to be plugged to the program-
ming adapter (included in scope of delivery). The user only
requires a Windows®PC with serial interface (CIS 685) or
USB-interface (CIS 686). Installing the configuration soft-
ware P-Set is very easy. P-Set runs on all Windows®PC’s
(95, 98, ME, 2000, NT, XP, Win7).
Configuration via programming device P6
The programming device P6 is simply plugged between
DS 6 and the female connector. Via two push-buttons and a
4-digit LED display, all possible settings can be realized. The
menu system of the device includes 27 menus and is easy
to handle. The following menus are – among others –
available for configuration:
- read all and store all
- operation mode
- switch-on and switch-off point
- set point negation
- switch on and switch off delay
- teach switch-on and switch-off point
- load of stored configurations
- storage off current configurations
- showing the current pressure value
- showing the limits of the measuring range
7. Maintenance
In principle, this device is maintenance-free. If desired, the
housing of the device can be cleaned when switched of
using a damp cloth and non-aggressive cleaning solutions.
With certain media, however, the diaphragm may be polluted
or coated with deposit. It is recommended to define corre-
sponding service intervals for control. After placing the
device out of service correctly, the diaphragm can usually be
cleaned carefully with a non-aggressive cleaning solution
and a soft brush or sponge. If the diaphragm is calcified, it is
recommended to send the device to BD|SENSORS for
decalcification. Please read therefore the chapter “Service/
repair” below.
!An incorrect cleaning can cause irreparable damages
on diaphragm. Never use spiky objects or pressured air
for cleaning the diaphragm.
8. Troubleshooting
In case of malfunction, it must be checked whether the
device has been correctly installed mechanically and electri-
cally. Use the following table to analyse the cause and
resolve the malfunction, if possible.
!Improper action and opening can damage the device.
Furthermore, dangers may arise for the operator.
Therefore repairs on the device may only be executed
by the manufacturer!
Fault: no output signal although LEDs are working
Possible cause Fault detection / remedy
line break inspect all connecting lines
of the contacts (including
the connecting plugs)
Fault: no output signal and LEDs are not working
Possible cause Fault detection / remedy
wrong setting of the set points verify that all switch param-
eters are useful and
permitted (e.g. the set
parameters must lie within
the applied pressure range)
Fault: device does not respond to pressure change
Possible cause Fault detection / remedy
defective sensor please send the device for
inspection to BD|SENSORS
Fault: little shift of the output signal
Possible cause Fault detection / remedy
diaphragm is calcified or
crusted if suspected, please send
the device to BD|SENSORS
for cleaning, if possible
Fault: large shift of the output signal
Possible cause Fault detection / remedy
diaphragm is damaged if a damage (e. g. by over-
pressure) is suspected,
please send the device
BD|SENSORS for repair
9. Placing out of service
WARNING! When dismantling the device, it must
always be done in the depressurized and currentless
condition! Check also if the medium has to be drained
off before dismantling!
WARNING! Depending on the medium, it may cause
danger for the user. Comply therefore with adequate
precautions for purification.
10. Service / repair
Information on service / repair:
- www.bdsensors.com
- [email protected]
- Service phone: +49 (0) 92 35 98 11 0
10.1 Recalibration
During the life-time of a transmitter, the value of offset and
span may shift. As a consequence, a deviating signal value
in reference to the nominal pressure range starting point or
end point may be transmitted. If one of these two phenome-
na occurs after prolonged use, a recalibration is recom-
mended to ensure furthermore high accuracy.
10.2 Return
Before every return of your device, whether for recalibration,
decalcification, modifications or repair, it has to be cleaned
carefully and packed shatter-proofed. You have to enclose a
notice of return with detailed defect description when
sending the device. If your device came in contact with
harmful substances, a declaration of decontamination is
additionally required.
Appropriate forms can be downloaded from our homepage.
Download these by accessing www.bdsensors.com or
request them:
[email protected] | phone: +49 (0) 92 35 / 98 11 0
In case of doubt regarding the fluid used, devices without a
declaration of decontamination will only be examined after
receipt of an appropriate declaration!
If the device came in contact with hazardous
substances, certain precautions have to be
complied with for purification!
11. Disposal
The device must be disposed of according to the
European Directive 2012/19/EU (waste electrical
and electronic equipment). Waste equipment
must not be disposed of in household waste!
WARNING! Depending on the measuring medium,
deposit on the device may cause danger for the user
and the environment. Comply with adequate precau-
tions for purification and dispose of it properly.
12. Warranty Terms
The warranty terms are subject to the legal warranty period
of 24 months, valid from the date of delivery. If the device is
used improperly, modified or damaged, we will rule out any
warranty claim. A damaged diaphragm will not be accepted
as a warranty case. Likewise, there shall be no entitlement to
services or parts provided under warranty if the defects have
arisen due to normal wear and tear.
13. EU Declaration of conformity / CE
The delivered device fulfils all legal requirements. The
applied directives, harmonised standards and documents are
listed in the EC declaration of conformity, which is available
online at: http://www.bdsensors.com.
Additionally, the operational safety is confirmed by the CE
sign on the manufacturing label.
Fig. 4 programming device P6
supply +
supply –
contact
VS
RL
supply +
supply –
contact 1
contact 2
VS
RL
RL
Fig. 2 programming software Fig. 3 programming adapter

This manual suits for next models

1

Other BD Sensors Switch manuals

BD Sensors DS 6 User manual

BD Sensors

BD Sensors DS 6 User manual

BD Sensors DS 230 User manual

BD Sensors

BD Sensors DS 230 User manual

BD Sensors DM01 User manual

BD Sensors

BD Sensors DM01 User manual

BD Sensors iS4 User manual

BD Sensors

BD Sensors iS4 User manual

BD Sensors DS 4 User manual

BD Sensors

BD Sensors DS 4 User manual

BD Sensors DM 200 User manual

BD Sensors

BD Sensors DM 200 User manual

BD Sensors DS 4 User manual

BD Sensors

BD Sensors DS 4 User manual

BD Sensors DS 200 User manual

BD Sensors

BD Sensors DS 200 User manual

BD Sensors DS 6 User manual

BD Sensors

BD Sensors DS 6 User manual

BD Sensors DS 6 User manual

BD Sensors

BD Sensors DS 6 User manual

Popular Switch manuals by other brands

SIIG JU-H70411-S2 Quick installation guide

SIIG

SIIG JU-H70411-S2 Quick installation guide

RJM Y-Not user manual

RJM

RJM Y-Not user manual

Analog way Pulse LE quick start guide

Analog way

Analog way Pulse LE quick start guide

Manhattan MES-08G instructions

Manhattan

Manhattan MES-08G instructions

SMC Networks ZSE20B-L Operation manual

SMC Networks

SMC Networks ZSE20B-L Operation manual

Juniper EX Series manual

Juniper

Juniper EX Series manual

LEGRAND Soliroc 778 51 manual

LEGRAND

LEGRAND Soliroc 778 51 manual

Qubic System QS-210 user manual

Qubic System

Qubic System QS-210 user manual

Luxul AGS-1024 Quick install guide

Luxul

Luxul AGS-1024 Quick install guide

Digital Watchdog DW-POE496M quick start guide

Digital Watchdog

Digital Watchdog DW-POE496M quick start guide

Commercial Electric HPSA11CWB user guide

Commercial Electric

Commercial Electric HPSA11CWB user guide

Allied Telesis x950 Series installation guide

Allied Telesis

Allied Telesis x950 Series installation guide

Dell Networking S5000 Deployment/configuration guide

Dell

Dell Networking S5000 Deployment/configuration guide

H3C S5120-EI Series IRF Command Reference

H3C

H3C S5120-EI Series IRF Command Reference

Potter PS120 Series manual

Potter

Potter PS120 Series manual

Ruijie RG-S5000-E Series Release notes

Ruijie

Ruijie RG-S5000-E Series Release notes

UUGear Zero4U user manual

UUGear

UUGear Zero4U user manual

Luxul XGS-1024S Quick install guide

Luxul

Luxul XGS-1024S Quick install guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.