R B G
R
G
B
W
1 2 3 4 5
+ - NO C NC 12VDC 24VDC
NOTE: The product should only be powered by a UL listed power supply.
NOTE: If power switch is not wired between DC source voltage and magnet,
it will take a longer time to de-energize the magnet simulating residual
magnetism.
1. 12 VDC INPUT
A. Required power 0.5A (Max).
B. Connect ground (-) lead from a 12 VDC power source to Terminal 2.
C. Connect positive (+) lead from a 12 VDC power source to Terminal 1.
D. Check jumper for 12 VDC operation.
2. 24 VDC INPUT
A. Required power 0.25A (Max).
B. Connect ground (-) lead from a 24 VDC power
source to Terminal 2.
C. Connect positive (+) lead from a 24 VDC power
source to Terminal 1.
D. Check jumper for 24 VDC operation.
3. CONTACTS
1. Relay dry contacts are rated 1A at 24 VDC for safe
operation, DO NOT exceed this rating.
2. If a NO switch is required, connect the wires from
the system to Terminal 4 & Terminal 3.
3. If a NC switch is required, connect the wires from
the system to Terminal 4 & Terminal 5.
Page 2 of 2 75.5367.01 20110715
5 Installation - Electrical
6 Company Contact
4 Installation - Mechanical (Cont’d)
Switch or solid
state switching
device
Switch or solid
state switching
device
AC110V
or
220V
AC110V
or
220V DC12V
or
24V
DC12V
or
24V
+
-
+
-
CORRECT
INCORRECT
DRY CONTACT
POWER
SUPPLY
POWER
SELECTOR
JUMPER
LED
MAG BOND SENSOR
MAGNET
TIMER (0-90 SEC)
C/L
DOOR FRAME
ARMATURE PLATE
MAGNET
ANGLE
BRACKET
MOUNTING
PLATE
MOUNTING
PLATE
STRINGER
HOLE FOR
GUIDE PIN
HOLE FOR NUT
RUBBER WASHER
STEEL WASHER
ARMATURE PLATE
SCREW M8 (35MM)
GUIDE PIN
DOOR
NUT
SPACER
WASHER
ARMATURE
PLATE
DOOR
NUT
DOOR FRAME DOOR FRAME
DOOR
ARMATURE PLATE ARMATURE PLATE
MAGNET MAGNET
DOOR DOOR
MOUNTING
PLATE
TYPICAL INSTALLATION
NOTE: DO NOT over-tighten the armature plate. The rubber washer is
designed to allow the armature plate to automatically adjust position
for best mating position between the lock and armature plate.
Our Service Technicians can be called 24 hours a day, 7 days a week. For more information visit www.beasensors.com.
Do not leave problems unresolved. If a satisfactory solution cannot be achieved after troubleshooting
a problem, please call BEA, Inc. If you must wait for the following workday to call BEA, leave the door
inoperable until satisfactory repairs can be made. Never sacrifice the safe operation of the automatic
door or gate for an incomplete solution.