75.5366.10 MAGLOCKS 600lb 20230828 Page 1 of 4
MAGLOCKS 600LB
USER’S GUIDE
ELECTROMAGNETIC LOCKS
ENGLISH
door conguration door status sensor
single double with without
10MAGLOCK3UL  
10MAGLOCK3ULDS  
10MAGLOCK6UL  
10MAGLOCK6ULDS  
DESCRIPTION 10MAGLOCK3UL
10MAGLOCK3ULDS
10MAGLOCK6UL
10MAGLOCK6ULDS
Lock: single double
Input Voltage: 12 or 24 VDC 12 or 24 VDC
Bond Status Relay (when
powered):
1.0 A @ 24 VDC
resistive
1.0 A @ 24 VDC
resistive
Relay Power Factor: 1 1
Door Status Switch: dry contacts: 3W (switching contact 0.25 amps
max, switching voltage 30VDC max; resistive load)
dry contacts: 3W (switching contact 0.25 amps
max, switching voltage 30VDC max; resistive load)
Reed Switch Power Factor: 1 1
Power Consumption: 500 mA @ 12 VDC /
250 mA @ 24 VDC
500 mA @ 12 VDC /
250 mA @ 24 VDC each
Dimensions: 9.84 × 1.66 × 1.04 in
250 × 42.2 × 26.5 mm
19.685 × 1.66 × 1.04 in
500 × 42.2 × 26.5 mm
Certication: UL294 UL294
Operating Temperature: 32 – 120 °F (0 – 49 °C) 32 – 120 °F (0 – 49 °C)
Operating Humidity: 0 – 85% 0 – 85%
UL 294 Performance Ratings:
(required per Chapter 10 of 2015 IBC)
Destructive: Level I Line Security: Level I
Endurance: Level IV Standby Power: Level I
Static Strength: 500 lb Dynamic Strength: 33 ft/lb
NOTE: The specications listed above are for an indoor, dry,
installation location.
The Electromagnetic Lock (Maglock) series is a surface-
mounted, magnetic-lock assembly. They are available in
single- and double-lock varieties, various sizes (i.e. force),
and also avaible with or without built-in Door Status Switch
(“DS” versions). All models are designed for standard
installation on most types of doors (1 3⁄8to 2” thickness).
1 Description
ATTENTION: This product must be powered from a UL-listed, regulated, power-limited, power supply!
2 Specications
12
2
345
6
7
8
75.5366.10 MAGLOCKS 600lb 20230828 Page 2 of 4
5Handle the equipment with care. Damaging the mating surfaces of the magnet and armature plate may reduce locking efciency.
5The MAGLCOK mounts rigidly to the door frame. The armature plate mounts to the door with the hardware provided. This allows the armature plate to pivot about its
center to compensate for door wear and misalignment.
5You must only use the template with the door in its normally closed position.
5Add threadlocker to all screws before installing, and rmly tighten screws.
5Install only for indoor, dry applications.
5Installation and wiring must be performed in compliance with ANSI / NFPA 70 / NFPA 101 / CSA C22.1, Canadian Electrical Code, Part I, safety standard for electrical
installations, section 32; and CAN/ULC-S524 installation of re alarm system requirements.
5The MAGLOCK shall be installed within the same room as other equipment and circuitry connecting to the MAGLOCK.
5Wiring must be cased to avoid outer cable damage, affect the insulation distance.
5An electric locking mechanism shall not impair the operation of panic hardware mounted on the door.
5An electric locking mechanism shall not impair the intended operation of an emergency exit.
5Shut off all power going to header before attempting any wiring procedures.
5Maintain a clean and safe environment when working in public areas.
5Constantly be aware of pedestrian trafc around the door area.
5Always stop pedestrian trafc through the doorway when performing tests that may result in unexpected reactions by the door.
5Always check placement of all wiring before powering up to ensure that moving door parts will not catch any wires and cause damage to equipment
or cable insulation.
5Ensure compliance with all applicable safety standards (i.e. ANSI A156.10) upon completion of installation.
DO NOT over-tighten the armature plate.
The rubber washer is designed to allow the armature plate to
automatically adjust position for best mating position between
the magnet and armature plate.
DOOR FRAME
MAGNET
DOOR
MOUNTING PLATE
Use the applicable mounting template.
ARMATURE PLATE
3 Precautions
4 Installation Notes
5 Installation – Mechanical
TYPICAL INSTALLATION
!
CAUTION
6 Armature Plate Installation
DOOR
nut
spacer
screw
(M8 45mm)
Apply threadlocker directly to all screws before
installing, and then rmly tighten the screws.
1. hole for nut
2. hole for guide pin
3. steel washer
4. rubber washer
5. steel washer
6. armature plate
7. permanent magnet (door status switch)
Ensure proper orientation of armature plate (i.e.
magnet positioned in upper left or right corner -
see diagram)
8. guide pin
DOOR
SIDE VIEW
armature plate
nut
rubber washer
Page 2 of 2 75.5366.02 20140401
5 Installation - Mechanical & Electrical
LOCK STATUS SWITCH (SPDT)
POWER
SUPPLY
+ -
POWER
SELECTOR
JUMPER
LED
MAG BOND SENSOR
MAGNET
TIMER (0-90 SEC)
TYPICAL INSTALLATION
NOTE: DO NOT over-tighten the armature plate. The rubber washer is designed to allow the armature
plate to automatically adjust position for best mating position between the lock and armature plate.
DOOR FRAME
ARMATURE PLATE
MAGNET
ANGLE
BRACKET
MOUNTING
PLATE
MOUNTING
PLATE
STRINGER
HOLE FOR
GUIDE PIN
HOLE FOR NUT
RUBBER WASHER
STEEL WASHER
ARMATURE PLATE
SCREW M8 (35MM)
GUIDE PIN
DOOR
NUT
SPACER
WASHER
ARMATURE
PLATE
DOOR
NUT
DOOR FRAME DOOR FRAME
DOOR
ARMATURE PLATE ARMATURE PLATE
MAGNET MAGNET
DOOR DOOR
MOUNTING
PLATE
CAUTION: Observe proper
circuit board orientation!
NOTE: The product must be powered from a UL listed, regulated, power limited, power supply.
NOTE: If power switch is not wired between DC source voltage and magnet,
it will take a longer time to de-energize the magnet simulating residual magnetism.
1. 12 VDC INPUT
A. Required power 0.5A (Max).
B. Connect ground (-) lead from a 12 VDC power source to Terminal 2.
C. Connect positive (+) lead from a 12 VDC power source to Terminal 1.
D. Check jumper for 12 VDC operation.
2. 24 VDC INPUT
A. Required power 0.25A (Max).
B. Connect ground (-) lead from a 24 VDC power source to Terminal 2.
C. Connect positive (+) lead from a 24 VDC power source to Terminal 1.
D. Check jumper for 24 VDC operation.
3. CONTACTS
1. Relay dry contacts are rated 1A at 24 VDC for safe operation, DO NOT exceed this
rating.
2. If a NO switch is required, connect the wires from the system to Terminal 4 & Terminal 3.
3. If a NC switch is required, connect the wires from the system to Terminal 4 & Terminal 5.
DS VERSION
24/7 Tech Support: 1-800-407-4545 | Customer Service: 1-800-523-2462 | General Tech Questions: T[email protected] | Tech Docs: www.beasensors.com
75.5366.10 MAGLOCKS 600lb 20230828 Page 3 of 4
7 Installation – Electrical
power selector jumper
magnet
24 VDC
12 VDC
power
supply
CIRCUIT BOARD
NOTE: Terminals ratings: 16~22AWG (copper wire)
lock status switch
(SPDT)
timer
1 90
1~90s ±15s
bond sensor
red green
black
C
NO NC
red
green
LED
With lock sensor, LED, and timer
With lock sensor and LED
Reed switch (door sensor type) - optional
Unmonitored
2 (-)
1 (+)
3 N.O.
4 COM
5 N.C.
The product must be powered from a UL-listed, regulated, power-limited, power supply.
12 VDC INPUT
- Required power: 0.5 AMP / 12 VDC
- Connect positive (+) lead from a 12 VDC power source to Terminal 1.
- Connect negative (-) lead from a 12 VDC power source to Terminal 2.
- Check jumper for 12 VDC operation.
24 VDC INPUT
- Required power: 0.25 AMP / 24 VDC
- Connect positive (+) lead from a 24 VDC power source to Terminal 1.
- Connect negative (-) lead from a 24 VDC power source to Terminal 2.
- Check jumper for 24 VDC operation.
POWER
If power switch is not wired between DC source voltage(+) and magnet, it will take a longer time to de-energize the magnet simulating
residual magnetism.
75.5366.10 MAGLOCKS 600lb 20230828 Page 4 of 4
LOCK STATUS RELAY CONTACT (SPDT) AND DOOR STATUS SWITCH
- Relay dry contacts are rated 1A at 24 VDC for safe operation, DO NOT exceed this rating.
- The reed switch dry contacts are rated at 3W (switching contact 0.25 amps max, switching
voltage 30VDC max; resistive load) for safe operation.
- If a NO switch is required, connect the wires from the system to Terminal 3 and Terminal 4.
- If a NC switch is required, connect the wires from the system to Terminal 4 and Terminal 5.
7 Installation – Electrical (cont.)
SWITCHES (optional)
BEA Inc., the sensor manufacturer, cannot be held responsible for incorrect installations or incorrect adjustments of the sensor/device; therefore, BEA Inc.
does not guarantee any use of the sensor/device outside its intended purpose.
BEA Inc. strongly recommends that installation and service technicians be AAADM-certified for pedestrian doors, IDA-certified for doors/gates, and
factory-trained for the type of door/gate system.
Installers and service personnel are responsible for executing a risk assessment following each installation/service performed, ensuring that the sensor/
device system performance is compliant with local, national, and international regulations, codes, and standards.
Once installation or service work is complete, a safety inspection of the system shall be performed and documented per the manufacturer’s
recommendations or industry guidelines. Examples of compliance may apply to ANSI 156.10, ANSI 156.19, ANSI/DASMA 102, ANSI/DASMA 107,
UL294, UL325, and International Building Code.
BEA, INC. INSTALLATION/SERVICE COMPLIANCE EXPECTATIONS
Tech Support & Customer Service: 1-800-523-2462 | General Tech Questions: [email protected] | Tech Docs: www.BEAsensors.com
* Switch changes state when door is open

Other BEA Lock manuals

BEA 10MAGLOCK1UL User manual

BEA

BEA 10MAGLOCK1UL User manual

BEA 10MAGDE1 User manual

BEA

BEA 10MAGDE1 User manual

BEA 10MAGLOCK1UL User manual

BEA

BEA 10MAGLOCK1UL User manual

BEA UL MAGLOCKS 600LB User manual

BEA

BEA UL MAGLOCKS 600LB User manual

BEA UL MAGLOCKS Series User manual

BEA

BEA UL MAGLOCKS Series User manual

BEA UL294 User manual

BEA

BEA UL294 User manual

Popular Lock manuals by other brands

Masterlock 4400 instructions

Masterlock

Masterlock 4400 instructions

Burtonsafes Burton Duo FPC-1808-II VdS operating instructions

Burtonsafes

Burtonsafes Burton Duo FPC-1808-II VdS operating instructions

Masterlock Select Access 5412EURD user manual

Masterlock

Masterlock Select Access 5412EURD user manual

Lock4Safe HOME10 instructions

Lock4Safe

Lock4Safe HOME10 instructions

INSYS EloStar Master 3X0 Assembly instructions

INSYS

INSYS EloStar Master 3X0 Assembly instructions

Yale Narrow Profile Series installation instructions

Yale

Yale Narrow Profile Series installation instructions

Kaadas Lamborghini Legends user manual

Kaadas

Kaadas Lamborghini Legends user manual

Mottura XFREE 49 P24 Series manual

Mottura

Mottura XFREE 49 P24 Series manual

iLoq S50 user guide

iLoq

iLoq S50 user guide

Westinghouse RTS Series Installation quick guide

Westinghouse

Westinghouse RTS Series Installation quick guide

Burg Coreo Pro operating manual

Burg

Burg Coreo Pro operating manual

Ardi BKL16 user manual

Ardi

Ardi BKL16 user manual

Orno OR-ZS-825 manual

Orno

Orno OR-ZS-825 manual

CODELOCKS 4000 Series manual

CODELOCKS

CODELOCKS 4000 Series manual

ViziT ML240-40 Operating	 instruction

ViziT

ViziT ML240-40 Operating instruction

Schlage AD-200 instruction manual

Schlage

Schlage AD-200 instruction manual

Simons Voss Technologies SmartLocker AX SmartIntego manual

Simons Voss Technologies

Simons Voss Technologies SmartLocker AX SmartIntego manual

Tecnosicurezza AuditLine T6530/DL User instructions

Tecnosicurezza

Tecnosicurezza AuditLine T6530/DL User instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.