BeaconMedaes Medipoint 125 Troubleshooting guide

Operation and Maintenance Instructions
Medical Gas Central Alarm
Medipoint 125 - Digital Alarm
Part number 4233500107
Revision 03
Jan, 2021

Atlas Copco Medical Ltd.
Telford Crescent, Staveley, Derbyshire, S43 3PF, UK
Personnel must make themselves familiar with the contents of this manual and the
function of the unit before installing, operating or maintaining.
Operation and Maintenance Manual
Medical Gas Central Alarm - Medipoint 125 Digital Alarm
This unit is purchased from:
Date purchased:
Model number:
Serial number:
Any information, service or spare parts requests should include the serial number and be directed to:
BeaconMedæs
Telford Crescent, Staveley
Derbyshire S43 3PF
Telephone: +44 (0) 1246 474242
Email: [email protected]
Website Contacts: www.beaconmedaes.com
BeaconMedæs reserves the right to make changes and improvements to update products sold previously without
notice or obligation.
Abbreviations
Abbreviation Full Description Abbreviation Full Description
BS British Standard Max Maximum
BSP British Standard Pipe Med Medical
CO2 Carbon dioxide MP26D Medipoint 26 Digital Alarm
°C Degree Celsius mMetre
øDiameter mm Millimetres
EN European Standards Min Minimum
1st First N2 Nitrogen
HTM Health Technical Memorandum N2O Nitrous oxide
ID Identication NRV Non-return valve
“Inch OD Outside Diameter
ISO International Standard Organisation O2 Oxygen
Kg Kilograms %Percentage
kPa Kilo pascals 2nd Second

3
Medical Gas Central Alarm - Medipoint 125 Digital Alarm
4233500107.03
Table of Contents
1.0 General Information.
1.1 Introduction.
1.2 Standards
1.3 AlarmPanels
1.4 Visualdisplays
1.5 Audiblewarning
1.6 Printedcircuitboards
1.7 Alarmcontactlinefault
1.8 Gasserviceconnections
1.9 DataConnection
1.10 Remoteaudiblewarningdevices
2.0 Installation
2.1 Installationofarstxpanel
2.2 InstallationofaSecondFixAssembly
3.0 Alarm Conguration.
3.1 DateTimesetup
3.2 MainScreen
3.3 AlarmSetupmenus
3.4 AlarmSetupScreen1
3.5 Gasservicesetupmainscreen
3.6 ExitSetupScreen
3.7 CongurationMenuMap
4.0 Commissioning
4.1 Alarmpaneltest
4.2 Checkingtheslaverelayoutput
4.3 Checkingtheremoteaudiblewarning
4.4 Medicalgasalarmfaults.
4.5 CheckingtheSYSTEMALARMindication
4.6 Finalcheck
5.0 Operation of the Medipoint 125
Digital medical gas area alarm
5.1 Useroperation
5.2 Additionaltechnicalfunctions
6.0 Maintenance Procedures
6.1 Replacementofalarmpanel
components
7.0 Maintenance Schedules
7.1 Weeklyinspection
7.2 Quarterlyinspection
7.3 5yearmaintenance
8.0 Recommended Spares
Products covered within this manual.
Part Number Description
MainProductgroup
8102371401 Medipoint125DigitalAlarm(MP125D)
1826481 MedicalGasAlarm1stFixbackbox
1826484 MedicalGasAlarmBezel

4
Medical Gas Central Alarm - Medipoint 125 Digital Alarm
4233500107.03
Safety Precautions
WARNING! DO NOT USE OIL OR GREASE on
any parts in contact with the medical gases for any
reason. This could lead to a FIRE or an EXPLOSION.
Only use approved OXYGEN COMPATIBLE lubricants,
which can be purchased from BeaconMedæs if
necessary.
Operatorshouldhavecarefullyreadandbecomefamiliar
withthecontentsofthismanualbeforemaintainingthe
Medipoint125DigitalAlarm.
Operator is expected to use common sense safety
precautions, good workmanship practices and follow
anyrelatedlocalsafetyprecautions.
Componentdescriptionsandpartslistsareavailableon
request.
Identication of symbols
Thefollowingsymbolsapplytothisproductandareused
intheseinstructionsandontheproductinquestion.The
meaningsofthesesymbolsareasspeciedbelow:-
Readinstructions
Ambienttemperaturerange
Ambienthumidityrange
Ambientpressurerange
Dateofmanufacture
Donotdisposeofingeneralwaste
Electromagnetic Interference
The panel has been tested to BS EN 61326-1-
Electromagneticcompatibility-Requirementsandtests.
Environmental Transport and Storage
Conditions
All products are separately packaged and stored in
controlledconditions.
Environmental Operating Conditions
Adverseenvironmentalconditionsandharshabrasives
orchemicalsmaycausedamagetotheunit.
Environmental Protection
Discard the unit and/or components in any standard
refusefacility.Theunitdoesnotcontainandhazardous
substances.
Cleaning
Thealarmcovershouldbewipedoverwithadampcloth
frequentlytoremoveanydustorforeignsubstances.
Electrical Details
CAUTION!Itisnecessarytochecktheintegrityof
thepowersourceforsafetyat regular intervals. These
checksshouldbecarriedoutannuallyandreplacement
powersuppliesusedasnecessary.
Powersource
Mains operated using 110V-230V, 50/60Hz, alternating
current.
Cablesize:
Frequency Voltage Minimum Cable Size
50Hz 230V 3x1.5mm2
60Hz 110V 33AWG14
Currentrequirements-3.0amps
Typeofprotectionagainstelectricshock.
Class 1 (Mains supplied equipment using a protected
earth).
RelativeHumidity90%max.
Altitudeupto2000m
PollusionDegree2
Modeofoperation:
• Indooruse.
• Continuous (equipment may be left switched on
indenitely).
Note - A double pole fused isolation switch or circuit
breaker must be installed locally to the medical gas
alarm. The isolationpoint must beclearly marked for
theequipmentitisintendedfor,andwithineasyreach.
The switch must require a tool or key to operate to
preventunauthorizedisolationofthedevice.

5
Medical Gas Central Alarm - Medipoint 125 Digital Alarm
4233500107.03
Medipoint125consistsof:-
No. Description
Control Fascia
1PoweronLED.
2Temperarymutebutton.
3SystemFaultLED.
4Testbutton.
LCD Touch Screen
5Informationscreen.
6Dataloggingscreen.
7SettupMenus.
8Alarmservicelocation.
9Emergencybatterysupplystatus.
10 Gasservicetype
11 Gasservicecolouridenticationbar
12 Gasservicestatusarea
13 Indicationthatdate/timeisnotset
14 Muteactivated
1. General Information.
1.1 Introduction.
The BEACONMEDÆS Medipoint 125 digital (MP125D)
medicalgascentalalarmissuitableforboththeUnited
Kingdom and International markets, and fully satises
the requirements the requirements of the HTM02-01,
HTM2022andISO7396-1applications..
TheCentralAlarmisdenedinISO7396-1as‘‘Operating
Alarms’. The intention of the alarm is to indicate to
technical sta that it is necessary to replenish the gas
supplyortocorrectamalfunctionwithintheMedicalGas
PipelineSystemthatrequiresanimmediateresponse.
EachalarmpanelrequiresastandardACelectricalpower
supplyof115/230volts±10%at50or60Hz,andfused
at3Amps.
Thecentralalarmcanbeprogrammedfromonscreen
menustoprovideafullyexiblealarmsystem.Allowing
thepanelstobeadaptedtosuitanyhospital’smedical
gas monitoring requirements (see section 1.12 for
programmingdetails).
Anindividualcentralalarmpanelhas5inputsorupto
1
4
2
3
6columnsfordisplayingasarepeaterpanelconsisting
of‘normal’and4‘fault’conditions.Thesecolumnscan
besetuptomonitoreitherupto5medicalgassource
equipment, or up to 20 individual point alarms, or a
combinationofthe2.
Onecentralalarmpanelisdesignatedthemasterpanel
for control purposes. Any number of panels may be
programmedasa‘centralacknowledgepanel’andcause
allashingdisplaysonthesystemtochangetosteady
when the MUTE switch on the central acknowledge
panelisoperated.
Each central alarm panel incorporates ashing alarm
displays, a POWER ON indication, a SYSTEM ALARM
indication, MUTE and TEST switches and an audible
warning programmed to operate depending upon the
9
12
10
11
5 6 7
8
Figure 1 - Medipoint125DigitalAlarm (MP125D).
13 14
Safety Notice
Personsundertakinganyinstallationand/ormaintenance
mustbefullytrainedinspecialistworkofthisnature.
The“PERMITTOWORK”proceduremustbeadheredto
forallinstallationsoncecommissioned.
ThealarmisdesignedandbuiltinaccordancewithHTM
02-01andISO7396-1regulationsandthereforeshould
beinstalledassuch.

6
Medical Gas Central Alarm - Medipoint 125 Digital Alarm
4233500107.03
Figure 2 - Medipoint125DigitalAlarm Components.
1 42
3
Medipoint125consistsof:-
No. Description
1Alarmenclosurehingeddoor.
2LCDtouchscreen.
3Controlfascia.
4Securityaccessfastener.
5Enclosurebackbox.
6PowersupplyPCB.
7ProcessorPCB.
8Speaker.
9Controlfasciamountingplate.
10 LCDscreenclamp.
11 PCBribboncableconnections.
12 LCDscreencableconnection.
13 Speakerconnection.
14 Controlfasciaconnection.
15 Batterypackconnection.
16 Earthbondingpoints.
17 Maintenancemutebutton
7 568 9
10 16
12 14 11
16
13
15
alarm condition displayed (see gure 1 for operating
interface image). Alarm panels are interconnected
by data transmission cable. Relay interface units are
availabletoinputconditionsintoexistingalarmsystems
orbuildingmanagementsystems.
Thealarmpanelalsoconstantlymonitorstheintegrityof
the internal circuits, interconnected wiring and system
monitoringsourceequipment.Intheeventofanydefect
within the monitored functions, the SYSTEM ALARM
LED illuminates (ashing) accompanied by the audible
warning, and the defective gas service alarm display
statusbarilluminates.
An internal maintenance push-button is provided
for use when the plant or pipeline is shut-down for
prolonged periods (see See gure 2). This facility
enables’permanent’mutingoftheaudiblewarningfor
aparticulargasserviceandisautomaticallyresetwhen
pipeline pressure returns to NORMAL or a new fault
statusoccurs.
Seegure2foridenticationofmaincomponents.
Figure3showstheelectricalconnections.
1.2 Standards
Centralalarmpanelsarefullytestedpriortodispatchand
packedtoprovide maximum protectionduringtransit.
Thealarmpanelsaredesignedtooperateinanambient
temperature of between 0°C and +40°C. Component
assemblies must be stored in their packaging in dry
conditionsandstoragetemperaturesmustbebetween
-10°C and +50°C. Alarm panel enclosures can only be
accessed with the use of a tool, mains terminals have
recessedscrewstopreventngercontactevenwiththe
dooropen,andelectricallybondedtoearthisprovideto
backboxanddoorforasafeinstallation.
17

7
Medical Gas Central Alarm - Medipoint 125 Digital Alarm
4233500107.03
CONFIDENTIAL:
copied, used for manufacturing or communicated to any other person or company.
This document is our property and shall not without our permission be altered,
ATLAS COPCO STANDARD Class
Tolerances,if not indicated,according to:
Modified from
tion
Note Posi- Intr./Appd.
Date Parent 3D Model
Kg
Version Drwg
Des checked
STATUS
Material
Treatment
Name
Drawn by
Scale
Kg
Family
Blank nr.
Approved
Prod checked
Blank wt.
Date
Fini wt.
Drawing owner
Designation Sheet ( )
Secrecy Class
1102 K/
Replaces
Compare
ACD
Ed.Version 3D
12356 7 8 9
G
4 10
A
B
C
D
E
F
1
MEDIPOINT125 DIGITAL ELECTRICAL SERVICE DIAGRAM
ISSUED
A3
2
GCF
0101
4233500119
09/08/2020
PB
N/A
PB
09/08/2020IAR10067 - FIRST ISSUE
1.0
Figure 3 - Electrical Schematic Diagram

8
Medical Gas Central Alarm - Medipoint 125 Digital Alarm
4233500107.03
1.3 Alarm Panels
Each alarm panel consists of a rst and second x
assembly, and are suitable for use with either surface
orconcealedinstallations.Abezelplateisprovidedfor
usewithconcealedinstallationsandisttedtotherst
xassemblytogiveaneatappearancebycoveringthe
plasterjoint.Thefrontcoveroftheenclosureishinged
and retained by a security fastener, which prevents
unauthorisedaccess(seegure4).
The assembly contains two printed circuit boards and
provides a gas service display from the LCD touch
screen. Each gas service is displayed in the NORMAL
(green,steady)anduptofourfaultconditions(yellowor
red,ashing)alarmconditions toshowthegasservice
status.Allalarmconditionsareilluminatedbyaashing
display and accompanied by an audible warning. Each
alarmpanellocatesallelectricalcomponentsoneither
the power supply or processor printed circuit boards,
whichareinterconnectedbyaribboncable.
OveralldimensionsaredetailedatTable1&Figure3.
TABLE 1: Medipoint 125 – DIMENSIONS
AlarmPanel Bezel
Height(mm) 150.0 200.0
Length(mm) 260.0 310.0
Depth(mm) 61.8 1.2
Chasedepth(mm) 45.0 -
Figure 4 -Medipoint 125 assembly
Medipoint125consistsof:-
No. Description
12ndxalarmPanel.
21stxbackbox.
3Flushmountedbezel.
4Securityaccessfastener.
1
2
3
4
Figure 5 - Medipoint 125 dimension drawing
VIEW A
VIEW B
VIEW C
A
B
C
45
150
17
30 200 30
2 x 20 CABLE GLAND KNOCKOUTS
17
50 40 40 40 40 50
260
2 x 20 CABLE GLAND KNOCKOUTS

9
Medical Gas Central Alarm - Medipoint 125 Digital Alarm
4233500107.03
1.4 Visual displays
Colour LCD touch screen display provides the visual
display detailed in paragraph 1.1, gure 1. All ashing
displaysashatarateof0.4secondson,0.4secondso
inaccordancewithISO7396-1andHTM02-01/HTM2022.
1.5 Audible warning
Theaudiblewarningspeakerttedtotheinsideofthe
alarmpaneldoorandconnectedtotheprocessorPCBby
plugandsocket(seegure2)operatessimultaneously
with any HIGH PRESSURE, LOW PRESSURE or SYSTEM
ALARMindication. The audiblewarning may bemuted
bypressingtheMUTEswitch(seegure1).Iffollowing
a mute condition another alarm condition occurs, the
audible warning will operate simultaneously with the
indication.Followingamuteconditionandacontinuing
alarmindication,theaudiblewarningwillresoundafter
15minutesinaccordancewithHTM02-01/HTM2022and
C11. When the audible re-sounds further operation of
theMUTEswitchisnecessarytocanceltheaudible.
If following an alarm condition no action is taken to
MUTEtheaudible,theaudiblewarningwillautomatically
switchowhenthealarmconditionrevertstoNORMAL.
The audible tone consists of a modulation between
twotones(F1andF2).F1=440HzandF2=880Hz.The
modulationrateis4HzinaccordancewithHTM02-01/
HTM2022andC11.
1.6 Printed circuit boards
Twoprintedcircuitboardsarettedinsidemedicalgas
centralalarm;apowersupplyPCBandaprocessorPCB.
AllcomponentsaremountedonthesePCB’s,whichare
interconnected by means of a multi-way ribbon cable
and polarised connector (see gure 2 & 3). The area
central alarm internal electrical installation complies
with all relevant British Standard specications, IET
wiringregulationsandcurrentUKlegislation.
1.6.1 Processorprintedcircuitboard
The Processor PCB is retained inside the alarm panel
frontcoverwithfourretainingstuds.ThisPCBissupplied
witharibboncableforconnectiontothepowersupply
PCB,andconnectorforlinkingtothecontrolfascia,LCD
touchscreenandinternalspeaker(seegure6).
Theblockindicatorisaplug-incomponentenablingeasy
replacementorsubsequentupdatingoftheinstallation.
Theribboncableispermanentlyattachedtotherearface
ofthelightdisplayPCBandenablesinterconnectionof
circuitswiththepowersupplyPCB.Theaudiblewarning
speaker is connected by plug and socket to the light
display PCB and locates within the alarm panel front
coverwheninstalled.
1.6.2Displaypositions
Toprovideanaestheticdisplayandmaintainconsistency
inaccordancewithrecognisedandestablishedmedical
gasservicesequencing,itisrecommendedthatdisplays
arepositionedinthefollowingsequenceoneachalarm
panelcommencingwithfromlefttoright(seegure7
example):-
Gas Type Legend
MedicalOxygen O2
NitrousOxide N2O
Oxygen/NitrousOxideMix(50/50) O2/N2O
MedicalAir400kPa Air
MedicalAir700kPa Air-800
MedicalVacuum Vacuum
Figure 6 - Processor PCB
1
2
3 4
Medipoint125consistsof:-
No. Description
1ProcesstopowersupplyPCBribboncable
2Controlfasciaconnector
3LCDtouchscreenconnector
4Audiblespeakerconnector
Figure 7 - Gas source layout example.

10
Medical Gas Central Alarm - Medipoint 125 Digital Alarm
4233500107.03
1.6.2 Powersupplyprintedcircuitboard
ThepowersupplyPCBisretainedinsidethealarmpanel
backboxwithfourretainingstudsandconnectstothe
processor PCB multi-way ribbon cable by polarised
connectors. The power supply PCB incorporates four
mains terminals (2 Earth, Neutral and Live, see gure
8) connected to a matching plug/socket combination
to accept the mains electrical power supply, which
preferably should be from an essential circuit, and
enablesconnectionofyingearthleadswhichelectrically
bondtheassembly.
Alterprotectsthealarmsystemfrompossiblespikes
ordisturbancesoftheincomingelectricalpowersupply
andanintegraltransformerprovides24Vd.c.Supplies
to operate the alarm circuits and power the pressure
sensors. A 5x20mm fuses to BS EN 60127 protect the
power supply circuits. F1 is rated at 500mA for 230V
suppliesand(seegure8).
In order to prevent inadvertent cross connection, the
mains electrical power supply plug and socket is not
mechanically compatible with any other connection to
thePCB.
A miniature ’Maintenance Mute’ push button (see
gure 8) is tted on the power supply PCB and is
accessiblewiththealarmpanelfrontcoveropen.With
an alarm condition displayed, operation of this button
’permanently’ disables audible reinstatement for that
particular displayed alarm condition only. This facility
isdesignedforusewhentheplantorpipelineisshut-
o for a prolonged period. On returning the pipeline
pressuretoNORMALthisfeatureautomaticallyre-sets
withoutfurthermanualselection.
Each channel (designated 1 to 5) incorporates ve
terminals (gure 8) which are for connecting to the
medicalgassourceequipment.
Arelay(completewithoptionallinecontactmonitoring
circuit)suitableforswitching50Vandamaximumof0.5
Amps is tted to the power supply PCB (see gure 8).
Therelayhasvoltfree,normallyopencontactsandtwo
terminals(N/OandC)enableconnectionbyamatching
plug/socket combination to either a Medipoint central
alarmsystemorothersuitablesystem.Thelinecontact
monitoring circuit can be from the on screen setup
menus. The relay is de-energised and contacts open
when any of the twelve alarm conditions are initiated.
Terminalsare also provided to enableconnection of a
remote audible warning device (AUD+ and AUD-) (see
gure8).
Itisrecommendedthattheinputcablesfromthesource
equipmentanddatatransmissionareinstalledseparate
fromthemainscable.
Figure 8 - Power supply PCB.
Mains
Fuse[F1]
Mains
Filter
24VDC
Powersupply
Remote Audible
Connection [+] [-]
Output Relay For Transmitting Single Event Alarm
[COMMON] [N/O]
Gas Service Connections, Channel 1-5
Data Transmission connections
IN [A] [B], out [A] [B] and [Screen]
Main Power Connection
[BONDING EARTH]
[MAINS EARTH]
[NEUTRAL] [LIVE]
Maintenance
Mute
Multiwayribboncable
connectortoprocessorPCB
Backup
BatteryPack
EndofLine
Resistors
Switches

11
Medical Gas Central Alarm - Medipoint 125 Digital Alarm
4233500107.03
Communication terminals IN [A][B], OUT [A][B] and
Screen[S]areprovidedtolinktheinputalarmtorepeater
units.Endoflineresisterdipswitchesaremountedon
thePCBtobesettoONfortherstandlastalarminthe
networkchain.
1.6.3 Standbybattery
ThepowersupplyPCB alsocontainsastandbybattery
(seegure8),batterychargingandpowerfaildetection
circuits.ThebatteryprovidespowerforboththeSYSTEM
ALARMindicationandtheaudiblewarningintheevent
ofanelectricalpowerfailure.Thebatteryisfullycharged
after72hoursandprovidessucientpowertooperate
thespecicalarmindicationsforaminimumof4hours.
Thebatteryisexpectedtohaveaminimum5yearlife.
1.7 Alarm contact line fault
Integrity of the interconnecting wiring and pressure
sensorsareconstantlymonitoredbythefaultdetection
circuits.Thefaultdetectioncircuitisdesignedtodetect
an wiring fault or in the data transmission network as
wellasconnections to source equipment.Inthe event
of a line fault the Power LED remains illuminated, the
SYSTEM ALARM indicator will illuminate (ashing) and
the audible warning sounds. The aected gas service
badge status bar will turn red (steady). When a line
contact fault is detected the ash rate of the aected
gas fault slows to half speed when the TEST switch is
operated.
1.8 Gas service connections
The5gasserviceconnectionshave5terminalseach.See
table2fordetailsforstandardoptions.Eachgasservice
andfaultlegendisalsofullycustomisablethroughthe
onscreensetupmenus.
TABLE 2: GAS SERVICE CONNECTION TERMINALS
Equipment
Type FaultType C 1234
AirPlant
Common ü
PlantFault ü
PlantEmergency ü
Reservelow ü
PressureFault ü
Vacuum
Plant
Common ü
PlantFault ü
PlantEmergency ü
NotUsed
PressureFault ü
Manifolds
Common ü
ChangeCylinders ü
ChangeImmediately ü
Reservelow ü
PressureFault ü
VIE
Common ü
LiquidLow ü
FillImmediately ü
Reservelow ü
PressureFault ü
1.9 Data Connection
Thepower supply PCB incorporatesa data connection
thatallowsslavecentralalarmtobeconnectedwithdata
cable.Theseslavepanelswillrepeatthesignalsreceived
from the master panel, allowing additional panels to
beinstalledformonitoringthroughout thehospital,or
insideoperatingtheatrepanels(seegure8).
1.10 Remote audible warning
devices
Remote audible warning devices may be tted in
locations where warnings are necessary and alarm
panels are not tted. Remote audible warning devices
arehousedinasurfacemountedenclosurecontaininga
warningbuzzer.Theaudiblewarningdeviceisconnected
byinputcabletothepowersupplyPCBwithinthealarm
panel (alarm terminals AUD+ and AUD-) (see gure
8). When the alarm panel audible sounds the remote
audiblealsosounds.Amaximumoffourremoteaudible
warningdevicescanbettedtoanalarmpanelandthe
totalcablelengthshouldnotexceed50metres.
MP125D
Channel1
C1234
Figure 9 - Source equipment connection, example air
plant.
Common
PlantFault
PlantEmergency
Reservelow
PressureFault
AlarmOutputs
Air Plant

12
Medical Gas Central Alarm - Medipoint 125 Digital Alarm
4233500107.03
2. Installation
2.1 Installation of a rst x panel
Thealarmpanelbackboxissuitableforbothsurfaceand
concealed installation and is annotated ‘TOP’ inside to
ensurecorrectorientation.Withaconcealedinstallation
achasedepthof45mmisrequiredandabezelistted
tocovertheplasterjoint.Theproceduretoinstallarst
xalarmpanelbackboxisasfollows:-
2.1.1 Backbox.Locate(seegure10).
Ensure the backbox is the correct way up. Locate
the backbox at the correct position and mark out for
securingscrews.
2.1.2 Wall.Fitanchors.
Drillwallandtanchorsinposition.
CAUTION! Ensure selected wall anchors are
suitable for the type of wall and weight of the alarm
panel.Alarmpanelweightis1.5kg.
2.1.3 Backbox.Fit(seegure10).
Select cable entry/exit points and remove the desired
knock-out segments from the inside. Fit suitable
grommets/cable glands as required by the contract
specication.Feedcablesintotheboxleaving400mmto
75
150
105 105 7
260
5
TOP
40 40 40 40
17
20
KNOCKOUT SEGMENTS
200
17
45
20
KNOCKOUT SEGMENTS
BACKBOX SURFACE
Figure10-BackBoxdetails.
enableconnectiontoprintedcircuitboard.Secureback
boxtowallwithsuitablescrews.
Select cable entry/exit points and remove the desired
knock-out segments from the inside. Fit suitable
grommets/cable glands as required by the contract
specication.Feedcablesintotheboxleaving400mmto
enableconnectiontoprintedcircuitboard.Secureback
boxtowallwithsuitablescrews.
CAUTION! With a concealed installation, the
plasterdepthmustbeushwiththeboxsurface,leaving
thewaterchannelproudoftheplaster.
2.2 Installation of a Second Fix
Assembly
WARNING! Ensure that the electrical power
supply to the alarm is o and remains isolated until
required during the commissioning procedure.
2.2.1 Backbox.Check.
Ensurethattheinsideofthebackboxiscleanandfree
fromdebris.
Fitbezelplatetobackboxandretainwithsecuringscrew
engagedinrighthandanchornut.
Concealedinstallation.Fitbezelplate(seegure11).

13
Medical Gas Central Alarm - Medipoint 125 Digital Alarm
4233500107.03
310
200
25 (ALL ROUND)
45
1.20
Figure11-Bezeldetails.
BEZEL
BACKBOX
SECURINGSCREW
(M4x12PANHEAD)
2.2.2 Powersupplycircuitboard.Fit(seegure12).
Fitaplasticspacerovereachofthefourretainingstuds
inthebackboxandlocatetheboardonthestuds.Fitthe
washersandtighten nuts inplacejust enough to hold
theboard.
CAUTION! Printed circuit boards are
susceptible to damage by static electricity and must
remain enclosed in their anti-static packaging until
immediately required for use. Removed printed
circuit boards must be placed in their anti-static
packaging immediately on removal. To prevent
damage to printed circuit boards, handle with care
and do not over torque retaining nuts.
Figure12-PowersupplyPCBinstallation.
No. Description QTY
1BackBox(1stxsupply) N/A
2PowersupplyPCB(2ndx,suppliedloose) 1
3PCBSpacer(2ndx,suppliedloose) 4
4M3Nut(2ndx,suppliedloose) 4
5M3Washer(2ndx,suppliedloose) 4
CONFIDENTIAL:
This document is our property and shall not without our permission be altered,
copied, used for manufacturing or communicated to any other person or company.
1 2 3 4 5678 9 10 11
A
B
C
D
E
F
G
H
Parent 3D Model 8102371401_MP125_01_Install
All materials supplied are in compliance with the
requirements of the List of Prohibited Substances
Title:
Material:
Finish:
Status
Work in Progress
REMOVE ALL BURR AND
SHARP EDGES UNLESS
OTHERWISE STATED
DO NOT SCALE
IF IN DOUBT ASK
---
As per order
DIMENSIONS IN MILLIMETERS
TOLERANCES UNLESS OTHERWISE
STATEDMACH. FAB.
0.25 1.0
0.1
0.05
0.5
0.5
1.0
-
NO DECIMAL PLACE:
ONE DECIMAL PLACE:
TWO DECIMAL PLACE:
ANGULAR:
SURFACE FINISH:
A3
DRAWING SCALE: 1 : 1.5
Third angle
DRAWING OWNER
SHEET:
PART NUMBER:
8102371401_MP125
_
11 OF
PGC CODE:
GBNPBA
Revision history
Zone Rev Description IAR No.Drawn By Checked By Approved Date
1
23
5
4

14
Medical Gas Central Alarm - Medipoint 125 Digital Alarm
4233500107.03
Figure13-2ndxdoorinstallation.
2.2.3 Alarmpanelfrontcover.Fit(seegure13).
Securethe2ndx door to backboxangebysecuring
hinge to backbox with screws provided. Plug in the
ribbon cable from the processor PCB to the power
supplyPCB No. Description QTY
12ndFixdoor(2ndxsuppliedassembled) 1
2M4x12panhead(2ndx,suppliedloose) 2
3M4washer(2ndx,suppliedloose) 2
2.2.4 EarthBonding.
Connection the earth cable assembly to the power
supply terminal block and earth stud on the backbox
andalarmdoorassembly.Seegure14.
Figure14-Earthbondingconnections
No. Description QTY
1Earthcable(2ndx,suppliedassembled) 1
2M3xNut(2ndx,suppliedloose) 4
3M3washer(2ndx,suppliedloose) 4
Typicalearthstudassembly
22
3
1
Alarm Door
Earth Stud
Backbox
Earth Stud
Power Supply
Terminal Block
CONFIDENTIAL:
This document is our property and shall not without our permission be altered,
copied, used for manufacturing or communicated to any other person or company.
1 2 3 4 5678 9 10 11
A
B
C
D
E
F
G
H
Parent 3D Model 8102371401_MP125_Open
All materials supplied are in compliance with the
requirements of the List of Prohibited Substances
Title:
Material:
Finish:
Status
Work in Progress
REMOVE ALL BURR AND
SHARP EDGES UNLESS
OTHERWISE STATED
DO NOT SCALE
IF IN DOUBT ASK
---
As per order
DIMENSIONS IN MILLIMETERS
TOLERANCES UNLESS OTHERWISE
STATEDMACH. FAB.
0.25 1.0
0.1
0.05
0.5
0.5
1.0
-
NO DECIMAL PLACE:
ONE DECIMAL PLACE:
TWO DECIMAL PLACE:
ANGULAR:
SURFACE FINISH:
A3
DRAWING SCALE: 1 : 1.5
Third angle
DRAWING OWNER
SHEET:
PART NUMBER:
8102371401_MP125
_
11 OF
PGC CODE:
GBNPBA
Revision history
Zone Rev Description IAR No.Drawn By Checked By Approved Date
1 2 3
Ribbon Cable connections

15
Medical Gas Central Alarm - Medipoint 125 Digital Alarm
4233500107.03
2.2.5 MultiplePanelDataConnection(seegure15
andtable3).
For multi-panel installations link the alarms together
usingtheIN[A][B]andOUT[A][B]inachainasshown
ingure15.
Forthetwopanelsattheendpointsofthenetworkthe
termination resistor should be switched “ON” with S1.
Forallotherpanels,S1shouldbeswitched“OFF”.See
gure15.
The alarm uses the EIA/TIA-485 (RS-485) data
communicationsspecication.Cableusedforthealarm
datamustbesuitableforthesesignals.Thefollowcable
typesarerecommends,seetable3.
TABLE3:RECOMMENDEDDATACABLE
Manufacturer / Reference Part Number
Belden8132(2pr,Non-Plenum) 2005421
Belden82842(2pr,Plenum)
Alphawire6455(2pr,Non-Plenum)
Figure15-Alarmdataconnection.
MP125D (1)
S1:ON
IN OUT
ABABS
MP125D (2)
S1:OFF
IN OUT
ABABS
MP125D (3)
S1:ON
IN OUT
ABABS
Note - “S” terminal is for connecting the screen
cable.
2.2.6 Remoteaudible(s).Connect(seegure16).
Connect remote audible device(s), if tted, to power
supplyPCBplug(terminals+and-).
Remote Audible
Connection [+] [-]
Figure16-Remoteaudibleconnection.
2.2.7 Alarmoutputfaultrelayconnection(seegure
17)
For outputting an alarm fault to another MP125D or
alternativealarmsconnecttothe“Salve”powersupply
plug.
Data Transmission connections
IN [A] [B], out [A] [B] and [Screen] End of line switch
[S1]
Figure17-Outputalarmrelaysignalconnection.
Output Relay For Transmitting Single Event Alarm
[COMMON] [N/O]
2.2.8 Sourceequipmentalarmconnections(seegure
18)
Sourceequipmentalarmconnectionsareconnectedto
Channel1throughtoChannel5powersupplyplug.
Gas Service Connections, Channel 1-5
Figure 18 - Source equipment alarm electrical
connections.

16
Medical Gas Central Alarm - Medipoint 125 Digital Alarm
4233500107.03
See table 4 and gure 19 for dierent wiring
congurations.
TABLE4:GAS SERVICE CONNECTION TERMINALS
Equipment
Type FaultType C 1234
AirPlant
Common ü
PlantFault ü
PlantEmergency ü
Reservelow ü
PressureFault ü
Vacuum
Plant
Common ü
PlantFault ü
PlantEmergency ü
NotUsed
PressureFault ü
Manifolds
Common ü
ChangeCylinders ü
ChangeImmediately ü
Reservelow ü
PressureFault ü
VIE
Common ü
LiquidLow ü
FillImmediately ü
Reservelow ü
PressureFault ü
Figure20-Electricalpowersupplyconnection.
Main Power Connection
[BONDING EARTH]
[MAINS EARTH]
[NEUTRAL] [LIVE]
Backup Battery
Connection
2.2.9 Electricalpowersupply.Connect(seegure20).
Ifthealarmpanelisnottobecommissionedimmediately,
disconnectthestandbybattery.
Connectelectricalpowersupplywirestoelectricalpower
supplyplug(terminalsE,NandL).
1
2
Figure21-Alarmdoorsecurityfastener.
No. Description QTY
1Securityfastener(2ndx,suppliedloose) 1
2Retainingwasher(2ndx,suppliedloose) 1
WARNING! The connection to the electrical
power supply should only be carried out by a
suitably qualied electrician, and tested in line with
national electrical safety standards before the unit
is powered up.
2.2.10 Backupbattories(Figure20).
Fitthe4AAArechargablebatteries.
2.2.11 SecurityFastener.Fit(gure21)
Fitthespecialfastenerandretainingpiecetothecover.
Closethefrontcoverandsecurewithspecialfastener.
MP125D
Channel1
C1234
Figure 19 - Source equipment connection, example air
plant.
Common
PlantFault
PlantEmergency
Reservelow
PressureFault
AlarmOutputs
Air Plant
Backup Batteries

17
Medical Gas Central Alarm - Medipoint 125 Digital Alarm
4233500107.03
3. Alarm Conguration.
WARNING! Personnel carrying out the
following procedure must be qualied and fully
conversant with the information contained in this
manual.
WARNING! Before commencing the alarm
conguration ensure that all installation procedures
are complete and that all wiring is correctly
connected. Before switching on the mains electrical
power supply, ensure the supply is correctly fused.
Allcongurationfunctionsaresetupwithinthesoftware
setupscreensusingtheLCDtouchscreen.
Aftercompletingallpointswithinsection2thealarmcan
bepoweredup.
Seesection3.8foranoverviewofthesetupconguration
menumap.
3.1 Date Time setup (Figure 22)
ThealarmwillstartupontheDate/Timesetupscreen.
Note...
• Thedate&timewillnotaectthefunctionalityof
thealarm,itisonlyrequiredfrothedatalogging.
• Ifanalarmconditionoccursthedatetimescreen
the unit will automatically take you to the main
screen.
• If the date/time is not set the main screen will
showacalendericoninyellow.
Figure22-Date/Timesetup.
SpecialCharacters/Icons:
Icon Description
EnterKey
TABkey.
Movestonexteldandhighlightstext.Highlighted
textwillbeoverwrittenonnextkeypress.
Tickkey.
Applyupdate,andtakesyoutothemainscreen.
Press on the rst eld (Day), hold down to highlight
current text ready to overwrite. Use the num-pad to
entertheday.
PresstheTABkeytogotothenexteld(Month).Use
thenum-padtoenterthemonth.
Repeatfrothefollowingelds,year>hours>minutes>
seconds.
PresstheTickkeywhencomplete,whichwilltakeyouto
themainscreen.
3.2 Main Screen (Figure 23).
Fromthemainscreenyoucanaccessthesetupmenus,
logscreenandinfoscreen.
Figure23-Mainscreen
SpecialCharacters/Icons:
Icon Description
Date/TimeIcon.
OnlydisplayediftheDate/Timehasnotbeensetup.
Datetimecanbesetfromthe“SettingsMenus”
InfoIcon.
Takesyoutotheinfoscreen
LogsIcon.
Takesyoutothelogsscreens.
SettingsIcon.
Takesyoutothesettingsmenuscreens.
Fromthemainscreenpressonthe“InfoIcon” togo
totheInfoscreen(Detailedintheoperatinginstructions
section).
Press on the “Logs Icon” to go to the Logs Screen
(Detailedintheoperatinginstructionssection).
Pressonthe“SettingsIcon” togotothesetupmenus
(Detailedinthefollowingsections).
3.3 Alarm Setup menus.
Press the “Settings icon” to go to the alarm setup
menuscreen.

18
Medical Gas Central Alarm - Medipoint 125 Digital Alarm
4233500107.03
ThiswilltakeyoutothePasswordScreen.Seegure25.
Figure25-PasswordScreen
Usethenum-padtoenterthe4digitnumericalpassword
(Default:1234).
Press the ENTER key to conrm the password and
takeyoutothesetupmenus.
SettupmenusstartontheAlarmsetup1screen.
Figure26-Alarmsetup1screen
SpecialCharacters/Icons:
Icon Description
PreviousIcon.
Takesyoutothepreviousmenusscreen.
NextIcon.
Takesyoutothenextmenusscreen.
ExitIcon.
Takesyoubacktothemainscreen.
RejectIcon.
Rejectschanges.
AcceptIcon.
AcceptsChanges
From the “Alarm setup 1” screen click the “Next Icon”
to go to the “Gas service setup” screen, press the
“PreviousIcon” togotothe“Alarmsetup2”screen,or
pressthe“ExitIcon” togobacktothemainoperating
screen.
3.4 Alarm Setup Screen 1 (Figure
26).
Thefollowingstepsdescribesthesetupprocessforthe
alarmsetupscreen1.
3.4.1 Date:
Pressonthersteld(Day),thenum-padwillappear.
Holddowntohighlightcurrenttextreadytooverwrite.
Usethenum-padtoentertheday.
PresstheTAB keytogotothenexteld(Month).Use
thenum-padtoenterthemonth.
PresstheTAB keytogotothenexteld(Year).Use
thenum-padtoentertheyear.
PresstheENTER keyorpressanywhereonthescreen
awayfromtheNUM-PADtoremovetheNUM-PAD.
3.4.2 Time.
Pressonthersteld(Hours),thenum-padwillappear.
Holddowntohighlightcurrenttextreadytooverwrite.
Usethenum-padtoenterthehours.
PresstheTAB keytogotothenexteld(Minutes).
Usethenum-padtoentertheminutes.
PresstheTAB keytogoothenexteld(Seconds).
Usethenum-padtoentertheseconds.

19
Medical Gas Central Alarm - Medipoint 125 Digital Alarm
4233500107.03
PresstheENTER keyorpressanywhereonthescreen
awayfromtheNUM-PADtoremovetheNUM-PAD.
3.4.3 PanelID:
ThiseldsetsthealarmIDnumberusedforidentication
withinanalarmnetwork.Allalarmsconnectedwithina
networkmusthaveauniqueIDnumber.
Press the up arrow to increase the ID number, down
arrowtoreducetheIDnumber.
3.4.4 Language:
Press on the down arrow to show the drop down list.
Pressureonthelanguageofchoicetoselect.
Note-CurrentlyEnglishonlyisavailable.
3.4.5 RelayMode.
Thiseldsetstheslaverelayoutputconditiontoeither
normally open or Line Contact Monitoring (LCM), see
section2.2.7.
Presson the left or rightarrow toswitch between the
twooptions.
3.4.6 NewPassword&Conrm.
Thiseldsetsthenewpasswordforaccessingthesetup
menusscreensanddatalogscreens.
Pressonthersteld(Newpassword),thenum-padwill
appear.
Usethenum-padtoenterthenewnumericalpassword.
Press the TAB key, or press the next eld to go to
thenexteld(Conrm).Usethenum-padtoenterthe
passwordagain.
PresstheENTER keyorpressanywhereonthescreen
awayfromtheNUM-PADtoremovetheNUM-PAD.
3.4.7 InputPanel.
Thisoptiondeterminesifthealarmpanelisthemaster
panelonthenetwork.Thereshouldonlybeonemaster
alarmpanelonthenetwork.Themasterpanelshallbe
setasthehighestalarmIDnumber.Thedefaultsetting
isticked.
Selectthetickboxtosetaccordingly.
3.4.8 MasterMute.
Thisoptiondeterminesifthe master mute function as
perHTMisactivatedonthispanel.
If the master mute is active and the mute button is
pressure during a fault condition, all fault conditions
stopashingonallalarmpanelsonthenetwork.This
istoindicatetoallareasonthe networkthatthefault
hasbeendetectedandbeingattendedtoo.Thedefault
settingisunchecked.
Selectthetickboxtoselectaccordingly.
3.4.9 GraphicsDarkMode.
This option determines the alarm panel main screen
coloursceme.
Selectthetickboxtoselectaccordingly,whichwilltoggle
betweenthefollowingtypicalmainscreen.
Typicaldarkmodeview

20
Medical Gas Central Alarm - Medipoint 125 Digital Alarm
4233500107.03
Typicalnormalmodeview
3.4.10 Conrm/rejectchanges.
Clickthetick toconrmandsavethechanges.Click
the cross to cancel the changes. The following
message box will appear to conrm the changes have
beensavedorrejectedaccordingly.
Clickthewindowtoclosetheconrmationmessage.
3.5 Gas service setup main screen
(gure 27).
Thefollowingstepsdescribesthesetupprocessforthe
maingasservicesetupscreen.
Figure27-MainGasServiceSetupscreen.
SpecialCharacters/Icons:
Icon Description
PreviousIcon.
Takesyoutothepreviousmenusscreen.
NextIcon.
Takesyoutothenextmenusscreen.
ExitIcon.
Takesyoubacktothemainscreen.
AddGasserviceBadge.
Takesyoubacktothegasservicesetupscreen.
3.5.1 GasServiceBadgeSetupScreen(Figure28).
Thefollowingstepsdescribesthesetupprocessforeach
gasservicebadge.
Figure28-GasServicebadgeSetupscreen.
3.5.2 GasTypeSelection(Figure29).
Press on the “Select” icon to open the
GasTypeSelectionScreen
Figure29-GasTypeSelectionscreen.
This manual suits for next models
2