ISOMETER® iso685…CN
技术数据
( )* = 出厂设置
绝缘协调性 (IEC 60664-1/IEC 60664-3)
额定电压..........................................................................................................1000 V
过电压分类 (OVC)................................................................................................. III
额定脉冲电压 (IEC 60664-1) ....................................................................... 8 kV
额定绝缘电压 (IEC 60664-1) ................................................................... 1000 V
污染等级 (Un< 690 V) ......................................................................................... 3
污染等级 (Un< 1000 V) ....................................................................................... 2
保护隔离介于 (≤ 2000 m NN) 和.............................(L1/+,L2,L3/-) 之间 –
.....................................(A1,A2) – (11,12,14) – (21,22,24) – (E, KE), (X1, ETH, X3, X4)
电压测试、常规测试 (IEC 61010-1) .............................................. AC 2.2 kV
电源电压
电源通过 A1/+, A2/-:
电源电压范围 Us................................................................... AC/DC 24…240 V
Us的频率范围 ........................................................................... DC, 50…400 Hz
功耗,典型地 50 Hz (400 Hz)............................ ≤12 W/21 VA (≤12 W/45 VA)
电源通过 X1:
电源电压 Us .................................................................................................. DC 24 V
被监视的 IT 系统
标称系统电压范围 Un.................................... AC 0…690 V, DC 0…1000 V
......................................................................... AC/DC 0…600 V ( 用于 UL 应用 )
Un的公差............................................................................................. AC/DC +15 %
Un的频率范围 ............................................................................. DC, 1…460 Hz
响应值
响应值 Ran1 (Alarm 1) ......................................................... 1 kΩ…10 MΩ (40 kΩ)*
响应值 Ran2 (Alarm 2) ......................................................... 1 kΩ…10 MΩ (10 kΩ)*
操作的不确定性 (符合 IEC 61557-8) ..相关的配置 , ±15 %, min. ±1 kΩ
测量回路
测量电压 Um.................................................... 相关的配置 , ±10 V, ±50 V
测量电流 Im................................................................................................≤ 403 μA
内部电阻 Ri, Zi............................................................................................ ≥ 124 kΩ
允许外部直流电压 Ufg....................................................................... ≤ 1200 V
允许系统泄露电容 Ce.................... 取决于相关配置 , 0…1000 μF
接口
现场总线 : 接口 / 协议........................... web server/Modbus TCP/BCOM
开关元件
接触器数据符合 IEC 60947-5-1
适用类别.................................................................AC-13AC-14DC-12DC-12DC-12
额定操作电压........................................................ 230 V230 V 24 V 110 V 220 V
额定操作电流..................................................................... 5 A3A 1 A 0,2 A 0,1 A
额定绝缘电压 ≤2000 m NN .......................................................................250 V
额定绝缘电压 ≤3000 m NN .......................................................................160 V
最小接触率....................................................................... 1 mA 在AC/DC ≥10 V
其他
EMC ....................................................................................................... IEC 61326-2-4 (1
保护等级,内置组件 (DIN EN 60529) .................................................. IP40
保护等级,端子 (DIN EN 60529) .............................................................. IP20
选项 "W"
带有 "W“ 后缀的产品
额定操作电流 开关元件.................................. 最大 3 A (UL 应用 )
1) 这是一个 A类产品。 在德国,这种产品可能会引起无线电
干扰。在这种情况下,用户可能需要采取纠正措施。
ISOMETER® 设计符合如下标准 :
DIN EN 61557-8 , DIN EN 61557-9 (iso685…-P-CN).
Technical data
( )* = factory setting
Insulation co-ordination (IEC 60664-1/IEC 60664-3)
Rated voltage ..........................................................................................................1000 V
Overvoltage category (OVC) ............................................................................................III
Rated impulse voltage (IEC 60664-1) ....................................................................... 8 kV
Rated insulation voltage (IEC 60664-1) ............................................................... 1000 V
Pollution degree (Un< 690 V) ....................................................................................... 3
Pollution degree (Un< 1000 V) ..................................................................................... 2
Protective separation (≤ 2000 m NN) between.................................. (L1/+,L2,L3/-)–
.....................................(A1,A2) – (11,12,14) – (21,22,24) – (E, KE), (X1, ETH, X3, X4)
Voltage test, routine test (IEC 61010-1) .......................................................... AC 2.2 kV
Supply voltage
Supply via A1/+,A2/-:
Supply voltage range Us.................................................................... AC/DC 24…240 V
Frequency range of Us.......................................................................... DC, 50…400 Hz
Power consumption typically 50 Hz (400 Hz) ..............≤12 W/21 VA (≤12 W/45 VA)
Supply via X1:
Supply voltage Us ..................................................................................................DC 24 V
IT system being monitored
Nominal system voltage range Un.................................. AC 0…690 V, DC 0…1000 V
.............................................................................AC/DC 0…600 V (for UL applications)
Tolerance of Un............................................................................................AC/DC+15%
Frequency range of Un............................................................................ DC, 1…460 Hz
Response values
Response value Ran1 (Alarm 1) ................................................. 1 kΩ…10 MΩ (40 kΩ)*
Response value Ran2 (Alarm 2) ................................................. 1 kΩ…10 MΩ (10 kΩ)*
Operating uncertainty (acc. to IEC 61557-8)...profile-dependent, ±15 %, min. ±1 kΩ
Measuring circuit
Measuring voltage Um............................................... profile dependent, ±10 V, ±50 V
Measuring current Im..........................................................................................≤ 403 μA
Internal resistance Ri, Zi......................................................................................≥ 124 kΩ
Permissible extraneous DC voltage Ufg ..............................................................≤ 1200 V
Permissible system leakage capacitance Ce..... dependent on the profile, 0…1000 μF
Interfaces
Field bus:Interface/protocol........................................... web server/Modbus TCP/BCOM
Switching elements
Contact data acc. to IEC 60947-5-1
Utilisation category........................................................ AC-13AC-14DC-12DC-12DC-12
Rated operational voltage ................................................ 230 V230 V 24 V 110 V 220 V
Rated operational current ............................................................. 5 A3A 1 A 0,2 A 0,1 A
Rated insulation voltage ≤2000 m NN ................................................................... 250 V
Rated insulation voltage ≤3000 m NN ................................................................... 160 V
Minimum contact rating .............................................................. 1 mA at AC/DC ≥10 V
Other
EMC ........................................................................................................ IEC 61326-2-4 (1
Degree of protection, built-in components (DIN EN 60529) .................................... IP40
Degree of protection, terminals (DIN EN 60529) ...................................................... IP20
Option "W"
Für devices with a „W“ in the device name:
Rated operational current of the Switching elements .....max. 3 A (for UL applications)
1) This is a class A product. In a domestic environment, this product may cause radio
interference. In this case, the user may be required to take corrective actions.
The ISOMETER® has been developed in compliance with the following standards:
DIN EN 61557-8 , DIN EN 61557-9 (iso685…-P-CN).