ISOMETER® IR420-D4
Caractéristiques techniques IR420-D4..
Coordination de l´isolement selon CEI 60664-1/CEI 60664-3
Tension assignée...................................................................................................................... 250 V
Qualité diélectrique / degré de pollution ........................................................................... 4 kV / III
Séparation sûre (isolation renforcée) entre:
............................................................... (A1, A2) - (L1, L2, E, KE, T/R) - (11-12-14) - (21-22-24)
Essai diélectrique selon CEI 61010-1 .................................................................................. 2,21 kV
Tension d´alimentation
IR420-D4-1:
Tension d´alimentation Us.................................................................. AC 16...72 V / DC 9,6...94 V
Gamme de fréquences Us...................................................................................... 42...460 Hz / DC
IR420-D4-2:
Tension d´alimentation Us................................................................................... AC/DC 70...300 V
Gamme de fréquences Us........................................................................................ 42...460 Hz, DC
Consommation propre ......................................................................................................... ≤4 VA
Réseau IT surveillé
Tension réseau Un........................................................................................................ AC 0... 300 V
Fréquence nominale fn.................................................................................................. 42...460 Hz
Valeurs de seuil
Valeur de seuil Ran1 (ALARM 1) ..................................................................................... 1...200 k
Ω
Valeur de seuil Ran2 (ALARM 2) ..................................................................................... 1...200 k
Ω
Fonction Preset :
Un≤72 V: Ran1 (ALARM 1)/ Ran2 (ALARM 2) ........................................................ 20 k
Ω
/ 10 k
Ω
Un>72 V: Ran1 (ALARM 1)/ Ran2 (ALARM 2) ........................................................ 46 k
Ω
/ 23 k
Ω
Tolérance du seuil (1...5 k
Ω
) / (5...200 k
Ω
) ................................................... ±0,5 k
Ω /
±15 %
Hystérèse (1...5 k
Ω
) / (5...200 k
Ω
) .................................................................. +1 k
Ω /
+25 %
Temps de réponse
Temps de réponse tan pour RF= 0,5 x Ran et Ce= 1 μF....................................................... ≤1 s
Temporisation de démarrage t ............................................................................................ 0...10 s
Durée de fermeture ton ........................................................................................................ 0...99 s
Circuit de mesure
Tension de mesure Um............................................................................................................ ±12 V
Courant de mesure Im(pour RF= 0
Ω
).......................................................................... ≤200 μA
Résistance interne DC Ri..................................................................................................... ≥62 k
Ω
Impédance Zipour 50 Hz................................................................................................... ≥60 k
Ω
Tension DC maxi. étrangère Ufg .................................................................................... ≤DC 300 V
Capacité de fuite Ce.............................................................................................................. ≤20 μF
Affichage, mémoire
Affichage ....................................................................... écran LC, multi fonctions, non rétroéclairé
Zone d´affichage, valeur mesurée ............................................................................. 1 k
Ω
...1 M
Ω
Erreur maximale de fonctionnement (1...5 k
Ω
) ............................................................. ±0,5 k
Ω
Erreur maximale de fonctionnement (5 k
Ω
...1 M
Ω
) ........................................................ ±15 %
Mot de passe ................................................................................................................. off / 0...999
Mémorisation des défauts (relais d´alarme) ....................................................................... on / off
Entrées
Longueur du câble touche Test- / Reset externe ................................................................. ≤ 10 m
Nombre et type
Nombre .......................................................................................................... 2 (inverseurs K1, K2)
Mode de travail ................................................................... courant de repos / courant de travail
Durée de vie électrique sous des conditions assignées de fonctionnement.... 10000 manoeuvres
Données des contacts selon CEI 60947-5-1:
Tension de fonctionnement nominale AC .......................................................... 230 V....... 230 V
Catégorie d´utilisation AC ................................................................................... AC 13....... AC 14
Courant de fonctionnement nominal AC ................................................................ 5 A............ 3 A
Tension de fonctionnement nominale DC ....................................... 220 V ....... 110 V.......... 24 V
Catégorie d´utlisation DC ................................................................. DC 12 ....... DC 12....... DC 12
Courant de fonctionnement nominal DC ........................................ 0,1 A ........ 0,2 A............ 1 A
Courant minimal ..................................................................................... 1 mA pour AC/DC ≥10 V
Technical data IR420-D4..
Insulation coordination acc. to IEC 60664-1/IEC 60664-3
Rated insulation voltage........................................................................................................... 250 V
Rated impulse voltage / Pollution degree........................................................................ 2.5 kV / III
Protective separation (reinforced insulation) between:
.............................................................. (A1, A2) - (L1, L2, E, KE, T/R) - (11, 12, 14) - (21, 22, 24)
Voltage test acc. IEC 61010-1 .............................................................................................. 2.21 kV
Supply voltage
IR420-D4-1:
Supply voltage Us................................................................................ AC 16...72 V / DC 9.6...94 V
Frequency range Us................................................................................................ 42...460 Hz / DC
IR420-D4-2:
Supply voltage Us................................................................................................. AC/DC 70...300 V
Frequency range Us................................................................................................. 42...460 Hz, DC
Power consumption .............................................................................................................. ≤4 VA
IT System being monitored
Nominal system voltage Un......................................................................................... AC 0... 300 V
Nominal frequency fn..................................................................................................... 42...460 Hz
Response values
Response value Ran1 (ALARM 1).............................................................................. 1 k
Ω
...200 k
Ω
Response value Ran1 (ALARM 2).............................................................................. 1 k
Ω
...200 k
Ω
Preset function:
Un≤72 V: Ran1 (ALARM 1)/ Ran2 (ALARM 2) ........................................................ 20 k
Ω
/ 10 k
Ω
Un>72 V: Ran1 (ALARM 1)/ Ran2 (ALARM 2) ........................................................ 46 k
Ω
/ 23 k
Ω
Operating error (1...5 k
Ω
) / (5...200 k
Ω
) ........................................... ±0.5 k
Ω /
±15 %
Hysteresis (1...5 k
Ω
) / (5...200 k
Ω
) ....................................................................+1 k
Ω /
+25 %
Time response
Response time tan at RF= 0,5 x Ran and Ce= 1 μF ............................................................... ≤1 s
Starting delay t ...................................................................................................................... 0...10 s
Response delay ton ................................................................................................................ 0...99 s
Measuring circuit
Measuring voltage Um............................................................................................................ ±12 V
Measuring current Im(RF= 0
Ω
) .................................................................................. ≤200 μA
Internal d.c. resistance Ri.................................................................................................... ≥62 k
Ω
Internal impedance Zi(50 Hz) ........................................................................................... ≥60 k
Ω
Admissible extraneous d.c. voltage Ufg ......................................................................... ≤DC 300 V
System leakage capacitance Ce............................................................................................ ≤20 μF
Displays, memory
Display ..................................................................... LC display, multi-functional, non-illuminated
Display range, measuring value ................................................................................ 1 k
Ω
...1 M
Ω
Operating error (1...5 k
Ω
) ................................................................................................ ±0.5 k
Ω
Percentage operating error (5 k
Ω
...1 M
Ω
) ........................................................................ ±15 %
Password ........................................................................................................................ off / 0...999
Fault memory (alarm relay) ................................................................................................. on / off
Inputs
Cable length external test / reset button.............................................................................. ≤10 m
Switching elements
Number of....................................................................................... 2 (changeover contacts K1, K2)
Operating principle....................................................................... (N/O operation) (N/C operation)
Electrical endurance ............................................................................ 10000 switching operations
Contact data according IEC 60947-5-1
Rated operational voltage AC ............................................................................... 230 V ....... 230 V
Utilization category AC ........................................................................................ AC 13 ....... AC 14
Rated operational current AC .................................................................................. 5 A ........... 3 A
Rated operational voltage DC ............................................................ 220 V....... 110 V ......... 24 V
Utilization category DC ...................................................................... DC 12........DC 12 ....... DC 12
Rated operational current DC ............................................................ 0.1 A........ 0.2 A ........... 1 A
Minimum current ..........................................................................................1 mA at AC/DC ≥10 V