Technical data
Supply voltage
RCM410R-24
Supply voltage Us....................................................................DC 24 V
Tolerance Us...................................................................-30…+25 %
Power consumption.................................................................. ≤ 2 W
RCM410R-2
Supply voltage Us............................AC/DC 100…240 V (47…63 Hz)
Tolerance Us.............................................................................±15 %
Power consumption.................................................≤ 2 W / ≤ 3.5 VA
Measuring circuit
Measuring current transf. type ...........................................................
..............................................CTAC…, W…, WF…*, WR…, WS…
* Can only be used when CT connection monitoring is disabled on the
RCM410R.
Load.............................................................................................33 Ω
Operating characteristics ..........................................................Type A
Rated voltage Un..........see datasheet measuring current transformer
Frequency range..............................................................42…70 Hz)
Measuring range RMS.....................................................2 mA…50 A
Residual operating current IΔn......................................10 mA…30 A
Operating uncertainty...................................±10 % (at 0.5…5 x IΔn)
Relative uncertainty.......................................................... 0…–20 %
Contact data acc. to IEC 60947-5-1:
Utilisation category..................AC 13 / AC 14 / DC-12 / DC-12 / DC-12
Rated op. voltage........................ 230 V / 230 V / 24 V / 110 V / 220 V
Rated op. current....................................5 A / 3 A / 1 A / 0.2 A / 0.1 A
Minimum contact rating................................1 mA at AC/DC ≥ 10 V *
* refers to relays that have not been operated with high contact currents.
Connection
Connection type...................................................................... push-in
Connection properties
rigid ................................................... 0.2…1.5 mm² (AWG 24…16)
flexible without ferrule...................... 0.2…1.5 mm² (AWG 24…16)
flexible with ferrule and plastic ferrule......................0.2…0.75 mm²
flexible with ferrule without plastic ferrule .............0.2…1.5 mm² *
* > 0.75 mm² use crimping pliers simlar CRIMPFOX 6 / Weidmüller PZ6/PZ6/5
only.
Technische Daten
Versorgungsspannung
RCM410R-24:
Versorgungsspannung Us........................................................DC 24 V
Toleranz von Us..............................................................-30…+25 %
Eigenverbrauch.........................................................................≤ 2 W
RCM410R-2:
Versorgungsspannung Us................AC/DC 100…240 V (47…63 Hz)
Toleranz von Us........................................................................±15 %
Eigenverbrauch....................................................... ≤ 2 W / ≤ 3,5 VA
Messkreis
Messstromwandlertyp........................................................................
..............................................CTAC…, W…, WF…*, WR…, WS…
* Einsatz nur bei deaktivierter Messstromwandler-Anschlussüberwachung am
RCM410R möglich.
Bürde...........................................................................................33 Ω
Ansprech-Charakteristik............................................................. Typ A
Bemessungsspannung Un...........siehe Datenblatt Messstromwandler
Frequenzbereich ............................................................... 42…70 Hz
Messbereich RMS............................................................2 mA…50 A
Ansprechdifferenzstrom IΔn...........................................10 mA…30 A
Betriebsmessabweichung...........................±10 % (bei 0,5…5 x IΔn)
Prozentuale Ansprechunsicherheit ................................... 0…–20 %
Kontaktdaten nach IEC 60947-5-1:
Gebrauchskategorie.................AC 13 / AC 14 / DC-12 / DC-12 / DC-12
Bem.betriebsspannung............... 230 V / 230 V / 24 V / 110 V / 220 V
Bem.betriebsstrom.................................5 A / 3 A / 1 A / 0,2 A / 0,1 A
Min. Kontaktbelastbarkeit ...........................1 mA bei AC/DC ≥ 10 V *
* bezieht sich auf Relais, die noch nicht mit hohen Kontaktströmen betrieben
wurden
Anschluss
Anschlussart............................................................................Push-In
Anschlussvermögen
starr .................................................. 0,2…1,5 mm² (AWG 24…16)
flexibel ohne Aderendhülse............... 0,2…1,5 mm² (AWG 24…16)
flexibel mit Aderendhülse und Plastikhülse...............0,2…0,75 mm²
flexibel mit Aderendhülse ohne Plastikhülse............0,2…1,5 mm² *
* > 0,75 mm² nur Crimpzange ähnlich CRIMPFOX 6 / Weidmüller PZ6/PZ6/5
verwenden.
LINETRAXX® RCM410R-24/-2
Alle Rechte vorbehalten.
Nachdruck und Vervielfältigung
nur mit Genehmigung des Herausgebers.
Bender GmbH & Co. KG
Postfach 1161 • 35301 Grünberg • Deutschland
Londorfer Str. 65 • 35305 Grünberg • Deutschland
Tel.: +49 6401 807-0 • Fax: +49 6401 807-259
All rights reserved.
Reprinting and duplicating
only with permission of the publisher.
Bender GmbH & Co. KG
PO Box 1161 • 35301 Grünberg • Germany
Londorfer Str. 65 • 35305 Grünberg • Germany
Tel.: +49 6401 807-0 • Fax: +49 6401 807-259