LIM2010
Installation Bulletin / Reference Guide
This document is intended as a reference guide to installing and setting a BENDER LIM2010 Line Isola-
tion Monitor. This document includes installation instructions and typical front plate display indica-
tions of the device. For complete details, including installation, setup, settings, and troubleshooting,
refer to the LIM2010 user manual.
Only qualied maintenance personnel shall operate or service this equipment. These instructions
should not be viewed as sucient for those who are not otherwise qualied to operate or service this
equipment. This document is intended to provide accurate information only. No responsibility is as-
sumed by BENDER for any consequences arising from use of this document.
Installation
Mounting
The front plate provides four holes with a diameter of 1/8” (3.2 mm) for screw mounting. Use
the four (4) provided screws for mounting. Use minimum 2.6 lb-in (0.3 N-m), maximum 3.5 lb-
in (0.4 N-m) torque. Before mounting, plug the connector plate into the LIM. Refer to Figures 1
and 2 for dimensions, listed in inches (mm).
Wiring
The LIM2010 connects to a connector plate assembly. Use the proper wiring diagram to con-
nect to the assembly. Before mounting the LIM, plug the connector plate into the LIM.
Figure 4 shows wiring the connector plate for basic in-
stallation with no accessories. If other equipment is to
be installed, such as remote indicators, fault location, or
load monitoring, or for more information on the con-
nector plate and installation, refer to the LIM2010 user
manual.
Connector plate L1 and L2 connect to the main lines
of the system, on the secondary of the isolation trans-
former. Connector plate LIMGND and GND2 are sepa-
rate connections to the system ground.
!DANGER
• Disconnect all power before servicing.
• Reference NFPA 99 / CSA Z32 for
Installation Standard.
HAZARD OF ELECTRIC SHOCK,
EXPLOSION, OR ARC FLASH
4” (101.5)
7” (177)
6.5” (164)
4.4” (112)
5.3” (134.5)
2.4” (62)
3.1” (79.5)
Figure 1 - LIM2010 dimensions, front view Figure 2 - LIM2010 dimensions, rear isometric view
Figure 3 - Connecting connector plate plugs to LIM2010
L1
L2
GND
Figure 4 - LIM2010 connector plate wiring - basic installation with no accessories
Connector Plate
Actual cable length for connector cables is 20” (50.8 cm). Both plugs are connected to
LIM2010. Connector plate must only be installed in a grounded, metallic enclosure.
Figure 5 - CP-LIM2010 connector plate
Connector plate terminals
Type Description
L1, L2 Connected to secondary of isolation transformer
12 VDC Com. Common connection for remote indicators
A, B RS-485 communication interface
RI1 Test button source for remote indicators
K1/NC Alarm relay K1, N/C
K1/Common Alarm relay K1, common
K1/NO Alarm relay K1, N/O
SAFE "SAFE" light connection for remote indicators
HAZARD "HAZARD" light connection for remote indicators
RI2 Local and system muting from LIM and remote indicators
GND2, LIM GND Separate ground connections
TEST Connection for remote test
Z1/M+, Z2/M- Connection for overtemperature sensor or analog meter
K2/Common Alarm relay K2, common
K2/NC Alarm relay K2, N/C
K2/NO Alarm relay K2, N/O
T M
Document NAE2028421 • 07.2016 • © Bender Inc. • Page 1/1 • Side 2/2Bender Inc. • USA: 800.356.4266 / 610.383.9200 / medical@bender.org • Canada: 800.243.2438 / 905.602.9990 / [email protected] • www.bender.org
LIM2010
Installation Bulletin / Reference Guide
Front Panel Display - Normal Condition
SAFE
HAZARD
MUTE
ESC
TEST
RESET
MENU
1
2
3 4 5 6 7 8
9
10
11
12
1. HAZARD LED (red): Not illuminated.
2. SAFE LED (green): Illuminated. Will be in
the normal condition when the dis-
played Total Hazard Current is below
the set response value (2 mA or 5 mA).
3. Trip value indication light (yellow):
Indicates that the 2 mA trip level has
been activated.
4. Trip value indication light (yellow):
Indicates that the 5 mA trip level has
been activated.
5. LED bar graph: In a normal condition,
only the green bars are illuminated.
6. Seven-segment display of Total Hazard
Current: Green in color for the normal
condition.
7. MUTE button / ESC key: To go to a high-
er level in the built-in menu.
8. MUTE LED: Not illuminated in the nor-
mal condition.
9. TEST button: Activates self-test. / UP
key: To move up in the menu and to in-
crease values.
10. DOWN key: Moves down in the menu
and to decrease values.
11. MENU key: Enters the main menu. /
ENTER key: To confirm entries.
12. Digital display: Reads SAFE in the nor-
mal condition. Also displays menu op-
tions when in the device‘s menu.
Front Panel Display - Alarm Condition
SAFE
HAZARD
MUTE
ESC
TEST
RESET
MENU
1
2
3 4 5 6 7 8
9
10
11
12
1. HAZARD LED (red): Flashes red.
2. SAFE LED (green): Not illuminated.
3. Trip value indication light (yellow):
Indicates that the 2 mA trip level has
been activated.
4. Trip value indication light (yellow):
Indicates that the 5 mA trip level has
been activated.
5. LED bar graph: In the alarm condition,
the red bars will be illuminated.
6. Seven-segment display of Total Hazard
Current: Red in color for the alarm con-
dition.
7. MUTE button / ESC key: To go to a high-
er level in the built-in menu.
8. MUTE LED: When in the alarm condi-
tion, will be illuminated yellow after the
MUTE button has been pressed.
9. TEST button: Activates self-test. / UP
key: To move up in the menu and to in-
crease values.
10. DOWN key: Moves down in the menu
and to decrease values.
11. MENU key: Enters the main menu. /
ENTER key: To confirm entries.
12. Digital display: Reads HAZARD in the
alarm condition.
Figure 4 - LIM2010 in the normal condition
Figure 5 - LIM2010 in the alarm condition
Navigating the Main Menu
Accessing the main menu
Hold the“MENU”button for at least one second.The device will enter into menu mode.The rst
item in the menu,“VALUES,” will appear. The number “1” will ash.
Entering the password prior to menu navigation
Many submenu options may be password protected. Passwords are entered as three digit
numbers. The default password is 807. When applicable, follow the below procedure to enter
the password:
1. A ashing number illustrates which number is currently in focus.
2. Use the UP/DOWN arrow key to select the correct number.
3. Conrm with the ENTER button.
4. Repeat for the next numbers until the last number is conrmed.
5. Settings may now be modied until the menu is exited. Reentering the menu will require
a reentry of the password.
When a parameter is changed and conrmed with the enter key, the change will have an im-
mediate eect. The LIM2010 will continue to operate while settings are modied.
Exiting the menu
Press the ESC key to return to the last step in the menu. Repeat this step until the display has
returned to the main screen. If the LIM2010 is idle in the menu for 5 minutes, the device will
automatically return to the main screen.
Menu structure
Refer to the LIM2010 user manual for a complete diagram of the LIM2010 menu.
Initializing The Clock (Message Code 8.80)
The LIM2010 utilizes date/time stamping. When initially energized, use the menu diagram be-
low to set the date and time. If message code 8.80 appears on the LIM2010, setting the time
and date will clear this alarm automatically.
MENU
Level 1
MENU
Level 2
MENU
Level 3Meaning
EXIT
4. SETTING 7. Clock Tm 10.34
ATime: am/pm
Dy 12/23 Date: month/day
Yr 2011 Year
DST auto Daylight saving time: auto/o
(North America time zones only)
EXIT
Figure 6 - Menu structure for changing date and time

Other Bender Measuring Instrument manuals

Bender ISOMETER isoNAV685-D-B User manual

Bender

Bender ISOMETER isoNAV685-D-B User manual

Bender ISOMETER isoHR685W-x-I-B User manual

Bender

Bender ISOMETER isoHR685W-x-I-B User manual

Bender ISOMETER isoCHA425HV User manual

Bender

Bender ISOMETER isoCHA425HV User manual

Bender LINETRAXX RCM410R-1 User manual

Bender

Bender LINETRAXX RCM410R-1 User manual

Bender LANTRAXX CMS460-D User manual

Bender

Bender LANTRAXX CMS460-D User manual

Bender ISOMETER isoRW425 User manual

Bender

Bender ISOMETER isoRW425 User manual

Bender ISOMETER IR425-D4 User manual

Bender

Bender ISOMETER IR425-D4 User manual

Bender ISOMETER isoPV with AGH-PV User manual

Bender

Bender ISOMETER isoPV with AGH-PV User manual

Bender ISOMETER isoPV425 with AGH420 User manual

Bender

Bender ISOMETER isoPV425 with AGH420 User manual

Bender NGRM700 User manual

Bender

Bender NGRM700 User manual

Bender ISOMETER isoRW425 User manual

Bender

Bender ISOMETER isoRW425 User manual

Bender ISOMETER isoRW685W-D User manual

Bender

Bender ISOMETER isoRW685W-D User manual

Bender VMD420 User manual

Bender

Bender VMD420 User manual

Bender MK2007CBM User manual

Bender

Bender MK2007CBM User manual

Bender ISOMETER IRDH275 User manual

Bender

Bender ISOMETER IRDH275 User manual

Bender MK2418 User manual

Bender

Bender MK2418 User manual

Bender ISOMETER isoNAV685-D User manual

Bender

Bender ISOMETER isoNAV685-D User manual

Bender ISOMETER isoHV525 User manual

Bender

Bender ISOMETER isoHV525 User manual

Bender iso685 User manual

Bender

Bender iso685 User manual

Bender A-ISOMETER IR425 User manual

Bender

Bender A-ISOMETER IR425 User manual

Bender ISOMETER IR425-D4 User manual

Bender

Bender ISOMETER IR425-D4 User manual

Bender ISOMETER isoNAV685-D User manual

Bender

Bender ISOMETER isoNAV685-D User manual

Bender ISOMETER iso1685FR User manual

Bender

Bender ISOMETER iso1685FR User manual

Bender COMTRAXX MK800 User manual

Bender

Bender COMTRAXX MK800 User manual

Popular Measuring Instrument manuals by other brands

geo-FENNEL FKL 44 user manual

geo-FENNEL

geo-FENNEL FKL 44 user manual

Jadak Photo Research PR-810 user manual

Jadak

Jadak Photo Research PR-810 user manual

BROSE Systeme PM 984 instruction manual

BROSE Systeme

BROSE Systeme PM 984 instruction manual

Horiba Scientific LAQUAact-PH110 instruction manual

Horiba Scientific

Horiba Scientific LAQUAact-PH110 instruction manual

KROHNE OPTIFLEX 2200 C/F Supplementary instructions

KROHNE

KROHNE OPTIFLEX 2200 C/F Supplementary instructions

GREISINGER GMH 3151 user manual

GREISINGER

GREISINGER GMH 3151 user manual

AL-KO 2LINK Translation of the original operating manual

AL-KO

AL-KO 2LINK Translation of the original operating manual

Wabtec NI 10R manual

Wabtec

Wabtec NI 10R manual

Honeywell 854 ATG Series instruction manual

Honeywell

Honeywell 854 ATG Series instruction manual

wtw Multi 3620 IDS operating manual

wtw

wtw Multi 3620 IDS operating manual

PRECISION DIGITAL ProVu Series instruction manual

PRECISION DIGITAL

PRECISION DIGITAL ProVu Series instruction manual

janitza UMG 511 Installation and commissioning

janitza

janitza UMG 511 Installation and commissioning

Arizona Instrument COMPUTRAC MAX 4000 user manual

Arizona Instrument

Arizona Instrument COMPUTRAC MAX 4000 user manual

Solartron Analytical 1260 operating manual

Solartron Analytical

Solartron Analytical 1260 operating manual

Amit RRU-WTB/AN01 Operation manual

Amit

Amit RRU-WTB/AN01 Operation manual

Dynojet 200i installation guide

Dynojet

Dynojet 200i installation guide

Proceq canin+ operating instructions

Proceq

Proceq canin+ operating instructions

TENSITRON STX-1 Series operating instructions

TENSITRON

TENSITRON STX-1 Series operating instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.