Demonstration Case DB 1
4.1 Measuring / testing
Connect the device to the mains. The IEC connector with two fuses and a mains
switch is situated at the rear. Connect it to the enclosed mains cable and a shock-
proof socket (230 V). The device is immediately ready for operation.
AC current measurement
AC current measurements are carried out by means of a current clamp. Set the switch
to position I (the lamp lights) and enclose the semicircular current loop by means of
the current clamp. The measured value is displayed (approx. 2.4A).
AC voltage measurement
Set the multimeter to AC voltage. The DUSPOL voltage tester automatically dis-
plays AC/DC voltage. Connect the COM measuring line (black) or the DUSPOL
probe handle to the blue jack "N" (0) and the red measuring line or the DUSPOL dis-
play handle to the desired voltage measuring jack (24 / 50 / 120 V - yellow; 230 /
400 / 690 V - red) and read the displayed value.
AC phase test
AC phase tests are carried out by means of the DUSPOL voltage tester (equipped for
single-pole phase tests). Bring the display handle of the voltage tester in contact with
the measuring jacks=> 230 V or with the right jack (L) of the test socket. The phase
will be displayed.
DC voltage measurement
Set the multimeter to DC voltage. The DUSPOL voltage tester automatically dis-
plays AC/DC voltage. Connect the COM measuring line (black) or the DUSPOL
probe handle to the black jack (0 V - 24 V) and the red measuring line or the DUS-
POL display handle to the red jack
(+ 24 V) and read the displayed value.
Reactive voltage measurement (simulation)
Reactive voltage measurements are carried out by means of the DUSPOL voltage
tester (with load connection!). Connect the voltage tester to the green jacks (reactive
voltage). Voltage signaling approx. 50 - 150 V. Activate both push-buttons (load
connection; voltage signaling approx. 6 V.
Voltage indication with a high-impedance multimeter is approx. 215 V AC. There-
fore, it is hardly appropriate for testing the absence of voltage!
FI safety switch release 30 mA
This test is carried out by means of the DUSPOL voltage tester (with load connec-
tion!). Connect the voltage tester to the test socket, the right jack (L) and a "protec-
tive conductor spring". Voltage signaling 230 V. Activate both push-buttons (load
connection), FI will be triggered!
Component test
The component test is carried out by means of a corresponding multimeter or a
DUSPOL voltage tester with continuity test.