
Temperature PI controller TCY- FT-U
Temperature PI controller TCY- FT-U
Temperature PI controller TCY- FT-U
Doc: 70-00-0130C, V1.3, 20141030 © Vector Controls GmbH, Switzerland Subject to alterations
Configuration parameters for firmware version 1.3
The TCY-FT-U is preset to work for most applications. For special requirements it can be fine tunedto work
ideal with a simple parameter setup routine.The parameterscan be changed on the unit without the need of
additional equipment.
Identifying the firmware version
The parameters andfunctionality of controller depend on its firmwareversion and revision. Itis therefore
important to use a matching product version and parameter set. The Firmwareversion and revision version
can be found when pressing simultaneously the and keys during several seconds. On the upper 7
segment display, the firmware version can be found, on the lower 7 segment display the current revision
index (or “sub-version”).
Setting of user parameters
The TCY-FT-U can be adapted to fit perfectly into your application. The control operation isdefined by
parameters. The parameters are set during operation by using the control buttons.
The parametersmay only be accessed by entering a code. There aretwo levels of parameters: User
operation parametersfor access control settings, and Expert parameters for controlfunctions and unit setup.
The codes for user levels and expert levels are different. Only control experts should be given the control
parameter code.
The parameters can be changed as follows:
1. PressUP and DOWN button simultaneously for three seconds. The display shows the software
version in the large digitsand the product codein the small digits.
2. Pressing the OPTION button will indicate CODE on the small digits and 000 on thelarge digits.
3. The code for accessing the user parameters is 009
4. Select this using UP or DOWN buttons.
5. Press OPTION button after selecting the correct code.
6. Once logged in, the parameter is displayed immediately.
7. Select the parameters with the UP/DOWN buttons. Change a parameter by pressing the OPTION
button. Three triangleswill show up on the lower right and indicate thatthe parametermay be
modified now. Use UP or DOWN buttonsto adjust the value.
8. After you are done, press OPTION or POWER in order to returnto the parameter selection level.
Press the POWER button again so as to leave the menu. The unit will return to normal operation if no button
is pressed for more than 5minutes.
User Parameters (Password 09)
Enable access to operation modes
Enable access to set points
Enable manual change of Heating/Cooling Mode.
No influence on TCY-FT2-U-W1 (cooling only) or
TCY-FT2-U-W2 (heating only)
State after power failure:
0 = off, 1 = on, 2 = state before powerfailure
Enable Economy (unoccupied) Mode.
Shift the setpoint to a lower temperature in winter or
higher temperature in summer in order to save energy.
May be activated through the POWER button, or with
the external input (typically for key card switches in hotel
rooms or motion detectors for meeting rooms.)
ON = Fahrenheit, OFF = Celsius
Calibrate internal temperature sensor
–10° to +10° in 0.1° steps. (Sensor is factory calibrated,
use this feature for field adjustment only as required.)
Enable Frost Protection.
Activates the output independent of operation mode
when the control temperature drops below5°C or 41°F.
The controller returns to normal operation when the
temperature increases above 10°C or 50°F.
TCY-FT2-W1: OFF
TCY-FT2-W2: ON
TCY-FT2: ON
TCY-FT4: ON
Control Parameters (Access Code: 241)
Warning! Only expertsshould change these settings! See user parameters for login procedure.
Minimum setpoint limit in Heating mode
Maximum setpoint limit in Heating mode
Minimum setpoint limit in Cooling mode
Maximum setpoint limit in Cooling mode
Economy (unoccupied) Mode temperature shift:
The comfort (occupied) setpoint is shifted by the value set
with parameter. If heating is active the comfort setpoint will
be decreased, if cooling is active, the setpoint will be
increased. (Enable with UP06.)
Dead Zone Span (TCY-FT4-U only):
The Dead Zone Span lies between the heating and the
cooling setpoint. The output is off while the temperature is
within the dead zone span. A negative dead zoneis not
possible.
Heat/Cool Changeover Delay (TCY-FT4-U only):
A demand to switch between heating and cooling must
persist for thelength of time set with this parameter before
the controller switches. Prevents activation of a sequence
during a short-term change in temperaturein order to
protect equipment (with control overshoot for example)
KIH, Integral gain heating, in 0.1 steps, (TI is fixed to 4s)
0 disables ID part
low value = slow reaction
high value = fast reaction
KIC, Integral gain cooling, in 0.1 steps, 0 disables I part
Configuration of operation mode
0 = TCY-FT2-U-W1 = Cooling mode YC1
1 = TCY-FT2-U-W2 = Heating mode: YH1
2 = TCY-FT2-U = Heating and Cooling (2 pipe system)
3 = TCY-FT4-U = Heating and Cooling (4 pipe system)
TCY-FT2: 0 - 2
TCY-FT4: 0 –3
TCY-FT2-W1: 0
TCY-FT2-W2: 1
TCY-FT2: 2
TCY-FT4: 3
Manual Override Mode:
Allows manual control of thefloating outputsfor using the
controller as positioner or during commissioning.
Running time FO1 (TCY-FT4 = heating output)
The total time it takesfor the actuator to runfrom fully open
to fully closed or from fully closed to fully open.
Setting this value to 0, converts the output to on/off control.
Open output will activate if there is demand; close output
will stay active if there is no demand. The p-band functions
as hysteresis.
Minimum running time FO1 (TCY-FT4-U = heating output)
The minimum time the output runs once it starts. This
setting preventsfrequent switches with very short running
times.
Running time FO2 (TCY-FT4-U = cooling output)
The total time it takesfor the actuator to runfrom fully open
to fully closed or from fully closed to fully open
Setting this value to 0,converts the output to on/off control.
Open output will activate if there is demand; close output
will stay active if there is no demand. The p-band functions
as hysteresis.
Minimum running time FO2 (TCY-FT4-U = cooling output)
The minimum time the output runs once it starts. This
setting preventsfrequent switches with very short running
times.
Maximum Output in Economy (unoccupied) Mode
Reduces the load on the system when is the space is
unoccupied.
Configuration of remote control input (X1)
0 = Control input if temperature sensor connected
1 = Occupation sensor –Comfort / Standby
2 = Remote enable –Comfort / OFF
3 = Keycard function:fixed setpoint
Activation delay (Minutes) = the time the binary input needs
to be open before standby/off mode is activated.
Fixed setpoint for key card function in heating mode
Fixed setpoint for key card function in cooling mode
For TCY-FT2-U only: Enable Auto changeover
For TCY-FT2-U only: Auto-changeover limit heating
For TCY-FT2-U only: Auto changeover limit cooling
Configuring the function of the external input X1
The external input X1 may be configured for several functions:
The control input is provided by the external input. The
internal input will not be used.
Switching Economy
and Comfort modes
Economy (unoccupied) and Comfort (occupied) modes
are controlled through an external contact by connecting
X1 through a dry contactto signal common. This function
may be used together with key card switches for hotels or
motion detectors for offices.
Switching Energy
Hold OFF and
Comfort modes
Opening the external temperature input will force the unit
into the OFF operation mode. The operation mode cannot
be overridden by using theterminal. Connectingthe
binary input to GND returns control of the operation mode
to the terminal. Thisfunction may be used as window
contact to prevent loss of energy.
As with CP18 = 1, the key card function switches
economy (unoccupied) and comfort (occupied) modes.
Instead of using the setpoint shift, the setpoints in
unoccupied mode are defined by parameter CP20 and
CP21.
This may be used for a dewpoint sensor input. Output will
switch off if contact opens.
Configuring auto changeover input X2 (TCY-FT2-U only):
The auto changeover function automatically changes heating and cooling mode based on supply
media temperature or outdoor temperature.The difference between the two is in the values of the
changeover limits CP23 and CP24. See table below for recommended settings.
Heating and cooling may be as well changed by an open contact switched to signal ground. Note: all
signal ground levelsof involved controllersmust be the same in case more than one controller is
switched.
Recommended settings for CP23 and CP24:
Dry contact: Heating if contact closed
Dry contact: Cooling if contactclosed