DPM-500 Digital Panel Meter Instruction Manual
8
Specifications
Except where noted all specifications apply to
operation at +25°C.
General
Display Line 1: 0.60" (15 mm) high, red LEDs
Line 2: 0.46" (12 mm) high, red LEDs
6 digits each (-99999 to 999999), with lead
zero blanking
Display
Intensity
Eight user selectable intensity levels.
Default value is six.
Display
Update Rate
5/second (200 ms)
Overrange Display flashes 999999
Display flashes -99999
Display
Assignment
Display lines 1 and 2 may be assigned to
PV1, PV2, PCT, d r-u, d gross, d nt-g,
max/min, max & min, set points, units
(display line 2 only), or Modbus input.
Programming
Methods
Four front panel buttons, digital inputs, PC
and MeterView Pro software, or Modbus
registers.
Noise Filter Programmable from 2 to 199
(0 will disable filter)
Filter Bypass Programmable from 0.1 to 99.9% of
calibrated span
Recalibration All ranges are calibrated at the factory.
Recalibration is recommended at least
every 12 months.
Max/Min
Display
Max/min readings reached by the process
are stored until reset by the user or until
power to the meter is turned off.
Rounding Select 1, 2, 5, 10, 20, 50, or 100
(e.g. rounding = 10, value = 123.45,
display = 123.50).
Tare Tare function zeros out the meter to
accommodate for weight of a container.
Tare function can be assigned to a
function key, F4 terminal, or a digital input.
Password Three programmable passwords restrict
modification of programmed settings.
Pass 1: Allows use of function keys and
digital inputs
Pass 2: Allows use of function keys, digital
inputs and editing set/reset points
Pass 3: Restricts all programming,
function keys, and digital inputs.
Non-Volatile
Memory
All programmed settings are stored in
non-volatile memory for a minimum of ten
years if power is lost.
Power
Options
85-265 VAC 50/60 Hz; 90-265 VDC, 20 W max;
12-24 VDC, 12-24 VAC, 15 W max.
Powered over USB for configuration only.
Fuse Required external fuse: UL Recognized,
5 A max, slow blow; up to 6 meters may
share one 5 A fuse
Greater than 60 dB at 50/60 Hz
Isolation 4 kV input/output-to-power line
500 V input-to-output or output-to-P+ supply
Overvoltage
Category
Installation Overvoltage Category II:
Local level with smaller transient
overvoltages than Installation Overvoltage
Category III.
Environmental
Operating temperature range:
-40 to 65°C (-40 to 149°F)
Storage temperature range:
-40 to 85°C (-40 to 185°F)
Relative humidity:
Connections Removable screw terminal blocks accept
12 to 22 AWG wire, RJ45 for external
relays, digital I/O, and serial
communication adapters.
Enclosure 1/8 DIN, high impact plastic, UL 94V-0,
color: black
Front Panel NEMA 4X, IP65
Mounting 1/8 DIN panel cutout required:
3.622" x 1.772" (92 mm x 45 mm)
Two panel mounting bracket assemblies
are provided.
Tightening
Torque
Screw terminal connectors: 5 lb-in
(0.56 Nm)
Overall
Dimensions
4.68" x 2.45" x 5.64"
(119 mm x 62 mm x 143 mm)
(W x H x D)
9.5 oz (269 g)
Warranty 3 years parts & labor. See Warranty
Information and Terms & Conditions on
www.binmaster.com for complete details.