Black & Decker BXEH60003GB User manual

BXEH60003GBwww.blackanddecker.co.uk

ENGLISH (Original instructions)
2
21
6
4
3
5
What’s in the box
Instruction Manual
Dehumidier
Features
1. Air outlet
2. Control panel
3. Air inlet
4. Filter
5. Water tank
6. Handle

ENGLISH
(Original instructions)
3
Intended Use
Your BLACK+DECKER BXEH60003GB 12L
Dehumidier has been designed for small and
medium spaces.
This appliance is intended for indoor household use
only.
Thank you for choosing BLACK+DECKER. We hope
that you will enjoy using this product for many years.
Safety Instructions
WARNING: Read all safety
warnings and all instructions. Failure
to follow the warnings and
instructions listed below may result in
electric shock, re and/or serious
injury.
♦ Read this manual carefully before
using the appliance.
♦ The intended use is described in
this manual.
♦ The use of any accessory or
attachment or the performance of
any operation with this appliance
other than those recommended in
this instruction manual may present
a risk of personal injury.
♦ Retain this manual for future
reference.
♦ WARNING: When using mains-
powered appliances, basic safety
precautions, including the following,
should always be followed to
reduce the risk of re, electric
shock, personal injury and material
damage.
Using Your Appliance
Please read the operating
instructions carefully before using
your appliance for the rst time.
♦ Check that the voltage of the main
circuit corresponds with the rating
of the appliance before operating.
♦ Children shall not play with the
appliance.
♦ Do not let the cable hang over the
edge of a table or counter or let
it come into contact with any hot
surfaces.
♦ The use of accessory attachments
is not recommended by the
appliance manufacturer, apart from
those supplied with this product.
♦ Do not pull the plug out by the
cable as this may damage the plug
and/or the cable.
♦ Do not use this product for anything
other than its intended use.
♦ This appliance is for household use
only.
♦ Do not carry the appliance by the
power cable.
♦ Do not use the appliance outdoors.
♦ Do not operate with wet hands.
♦ Use of an extension cable with this
appliance is not recommended.
However, if it is necessary to use
an extension lead, ensure that
the lead is suited to the power
consumption of the appliance to
avoid overheating of extension
cable, appliance or plug point. Do
not place the extension cable in a

ENGLISH (Original instructions)
4
position where it can be pulled on
by children or animals or tripped
over.
♦ Always unplug the unit when not in
use or before cleaning.
♦ The manufacturer does not accept
responsibility for any damage
or injury caused by improper or
incorrect use, or for repairs carried
out by unauthorised personnel.
Safety Of Others
♦ Close supervision is necessary
when any appliance is used by or
near children.
♦ Children should not play with the
appliance.
♦ This appliance can be used by
children aged from 8 years and
above and persons with reduced
physical, sensory or mental
capabilities or lack of experience
and knowledge if they have been
given supervision or instruction
concerning use of the appliance
in a safe way and understand the
hazards involved.
♦ Cleaning and user maintenance
should not be undertaken by
children without supervision.
♦ Take care when any appliance is
used near pets.
♦ Do not allow the cord to become
twisted.
After Use
♦ While cleaning, DO NOT use a wet
cloth or use water on any part of
the unit, as this may cause a short
circuit or electrical shock.
♦ Keep this unit clean. Do not allow
objects to enter the ventilation
opening as this may cause electric
shock, or damage to the unit.
Switch off the unit and then remove
the plug from the socket when not
in use or before cleaning.
♦ Check all inlets and outlets
regularly for accumulated dust.
♦ Disconnect the unit from mains
outlet when it is not in use, or
before relocating or cleaning it.
♦ Switch off and remove the plug
from the socket before leaving the
appliance unattended and before
changing, cleaning or inspecting
any parts of the appliance.
♦ When not in use, the appliance
should be stored in a dry place.
Children should not have access to
stored appliances.
Inspections And Repairs
♦ Do not attempt to dismantle, repair
or remould any part of the unit. This
should only be done by a qualied
service agent. Even the change of
power cable should be done by a
qualied person.

ENGLISH
(Original instructions)
5
♦ In the unlikely event the appliance
develops a fault, stop using it
immediately and seek advice from
the manufacturer.
♦ In case of technical problems,
switch off the product and do not
attempt to repair it yourself. Return
the appliance to an authorised
service facility for examination,
adjustment or repair. Always
insist on the use of original spare
parts. Failure to comply with the
above mentioned precautions and
instructions, could affect the safe
operation of this product.
Additional safety instructions for
Dehumidifiers
♦ Install the unit on at and hard oor
to diminish vibration or noise.
♦ Always operate the appliance on a
smooth, even, stable surface. Do
not place the unit on a hot surface.
♦ Ensure that the unit is switched off
after use.
♦ Do not immerse cables, plugs or
any part of the appliance in water
or any other liquid.
♦ Operate the unit only at the voltage
specied.
♦ Do not use the unit near open
windows, as contact with rain and
other natural elements could cause
an electrical hazard
♦ Do not put heavy objects on the
appliance.
♦ Do not tip the unit on its side.
♦ Never insert any other object into
the unit body to avoid any hazard
or unit failure.
♦ Do not put the unit close to
heat-generating devices or
near ammable and dangerous
materials.
♦ If the supply cable is damaged,
it must be replaced by the
manufacturer or its service agent or
a similarly qualied person in order
to avoid a hazard
♦ The appliance must be positioned
so that the plug is accessible.
WARNING: Do not place the unit
on or near a hot gas electric burner.
Safety relating to refrigerant R290:
♦ These symbols on your device
mean:
♦ This appliance is lled with
Propane gas R290. ALWAYS follow
the manufacturer’s instruction
concerning use and repairs.
♦ Read the entire instruction manual
carefully before attempting to use
the appliance.
♦ Do not install, operate or store the
device in a room smaller than 4m2.
Warning: Risk of fire Please read operator’s
manual carefully! Please read operating
instructions carefully! Please read technical
manual carefully!
♦ Read these warnings carefully.

ENGLISH (Original instructions)
6
♦ This appliance contains
approximately 45g of R290
refrigerant. R290 is a refrigerant
that complies with the relevant
European Directives. Never
perforate the refrigerant circuit.
CAUTION: R290 is flammable
(GWP3)!
♦ DO NOT use any processes to
clean the unit or accelerate the
defrosting process, other than
those recommended by the
manufacturer.
♦ DO NOT store the appliance in a
room containing other continuously
operating ignition sources (for
example: open ames, an operating
gas appliance or an operating
electric heater).
♦ DO NOT pierce or burn any of the
components of the cooling circuit
of the unit. DO NOT set the unit on
re.
♦ Take care to store the appliance
in such a way as to prevent
mechanical faults or damage from
occurring.
♦ DO NOT install, operate or store
the appliance in a room with a oor
area of less than 4m2.
♦ Be aware that the refrigerant may
be odourless, and that leaks may
not be detectable by smell.
♦ ALWAYS take care to comply with
national gas regulations.
♦ Keep ventilation openings clear of
obstruction.
♦ Store the appliance in a well-
ventilated area where the room
size corresponds to the room area
specied for operation.
♦ Any person who is involved with
working on or breaking into a
refrigerant circuit should hold a
current valid certicate from an
industry-accredited assessment
authority, which authorises their
competence to handle refrigerants
safely in accordance with an
industry recognised assessment
specication.
♦ Servicing shall only be performed
on the grounds recommended
by the equipment manufacturer.
Maintenance and repair requiring
the assistance of other skilled
personnel shall be carried out
under the supervision of the person
competent in the use of ammable
refrigerants.
WARNING: Do not place the unit
on or near a hot gas electric burner.

ENGLISH
(Original instructions)
7
Electrical safety
Before use, check that the mains voltage
corresponds to the voltage on the rating plate.
This product must be earthed. Always
check that the mains voltage
corresponds to the voltage on the rating
plate.
♦ Appliance plugs must match the outlet. Never
modify the plug in any way.
♦ Do not use any adapter plugs with earthed (Class
1) appliances. Unmodied plugs and matching
outlets will reduce the risk of electric shock.
♦ To avoid the risk of electric shock, do not immerse
the cord, plug or appliance in water or other liquid.
Extension cables & class 1 product
♦ A 3 core cable must be used as your tool is
earthed and of class 1 construction.
♦ Up to 30m (100 ft) can be used without loss of
power.
♦ If the supply cord is damaged, it must be
replaced by the manufacturer or an authorised
BLACK+DECKER Service Centre in order to avoid
a hazard.
WARNING: Before assembling, switch the
appliance off and remove the plug from the socket.
Features
1. Air outlet
2. Control panel
3. Air inlet
4. Filter
5. Water tank
6. Handle
Use
About the Controls
♦ Dry clothes
♦ Normal Operation
♦ Continuos Operation
♦ Ventilation
♦ Sleep Mode
Operation and Efficiency
♦ This appliance operates in temperatures between
5-32°C.
Defrosting operation
♦ The evaporator in the dehumidier may
defrost automatically if it is operated in a room
temperature less than 18°C. Defrosting may start
up and operate for some time (about 5 minutes),
automatically approximately every 25 minutes.
The defrost light will illuminate.
♦ During the defrosting operation, the
dehumidication function and air purication
function may intermit.
♦ Please don’t turn off or pull out the power plug of
the dehumidier during the defrosting operation.
♦ The purpose of this dehumidier is to remove high
humidity and dampness, not to keep temperatures
low.
♦ This dehumidier doesn’t have a cooling function.
It will produce heat during the operation and
increase the room temperature by 1 to 4°C. This
temperature rise may be very distinct in small
spaces.

ENGLISH (Original instructions)
8
Control Panel
1. Low fan speed indicator
2. High fan speed indicator
3. Fan speed selector
4. LED display (Humidity, Timer & Modes)
5. Defrost indicator
6. Water tank full indicator
7. Sleep button
8. Timer button
9. Humidity & timer touch control slider
10. Mode button
11. ON/OFF button
Turning The Unit On Or Off
Note: To avoid damage, place the unit in an upright
position for at least 24 hours before rst use.
Note: Always ensure the water tank is empty and in
place before turning the unit on.
Note: During the operation, keep doors and
windows closed to save energy.
♦ To power the unit on, rst plug it into a mains
socket. A single beep will be heard. The unit will
be in stand-by mode.
♦ Press the ON/OFF button to turn the unit on.
The ON/OFF button and the fan speed light on the
unit’s control panel will illuminate and air will start
emitting from the top grille. The display screen will
show the current room humidity %.
♦ Press the ON/OFF button again to power the unit
off. Air will stop emitting from the grille to show the
unit has been powered down. All lights will go off.
♦ To shut the unit off completely, unplug it from the
mains socket.
WARNING: DO NOT store the unit immediately
after turning it off. Allow time for the unit to cool
down before storing.
Dehumidification Modes
There are 4 modes to select from:
- Normal dehumidication – adjustable fan
speed and adjustable humidity
- Continuous dehumidication – a set low fan
speed and humidity is not adjustable
- Ventilation mode – adjustable fan speed and
humidity is not adjustable
- Drying mode –a set high fan speed and set
humidity is not adjustable
Press the mode button to cycle through the
options, respective symbols will show in the display.
The mode selected will ash for 5 seconds and then
remain visible in the display.
Humidity Setting
♦ In Normal dehumidication mode, slide your nger
across the symbol horizontally to set
the humidity between 30%-80% (in increments
of 5%).
♦ The humidity selected will ash for 5 seconds in
the display.
♦ The display will then show the room’s current
humidity.
♦ To check the humidity selected at any time, press
the humidity setting symbol and it will ash in the
display for 5 seconds.
Timer Operation
♦ Whilst the unit is operating the timer is used to set
the time to turn the appliance off.
♦ Whilst the unit is in stand-by mode the timer is
used to set the time to turn the appliance on.
♦ Press the timer button to select a time
between 1-24hrs.
♦ With each press of the timer button the time will
increase by 1 hour. The time selected will ash for
5 seconds and the will illuminate in the display.
♦ To check the time selected at any time, press the
timer button and it will ash in the display for 5
seconds.
41 52 63
7 8 9 10 11

ENGLISH
(Original instructions)
9
♦ To cancel the timer, press the timer button until
the time shows 00.
Fan Speed
♦ The fan speed can only be changed in Normal
and Ventilation modes.
- Low fan speed
- High fan speed
♦ Press the fan speed button to cycle through
the low and high speed settings. The respective
light will illuminate.
Sleep
Press the sleep button to enter sleep mode. The
sleep button light illuminates and the display turns
off.
Press the sleep button again to switch the Sleep
function off. The light will go off and the display will
come on.
Removing The Water Tank
♦ Ensure the water tank is empty before turning the
unit on.
♦ WARNING: Do not drink the water or use for
other purposes.
Continuous drainage (optional)
♦ By connecting a water pipe in to the back of the
appliance water can be drained continuously.
♦ Remove the water tank. Insert the pipe, ensuring
that the pipe is rmly connected to the drainage
mouth.
Note: The drainage hose should not be installed
outdoors at low temperatures.
Drainage Manually
♦ When the water tank is full, the water-full indicator
is will illuminate and the unit will stop working.
♦ Pull out the water tank and pour away the water.
♦ Replace the water tank. The dehumidier will
restart.
Note: Before putting in the water tank, please
ensure the oat inside it moves freely.
Cleaning and maintenance
WARNING: Before cleaning and maintenance,
switch the appliance off and remove the plug from
the socket, to prevent electric shock.
♦ Do not immerse any part of the appliance, power
cord or plug in water or other liquids.
♦ Use only implements recommended by the
manufacturer for defrosting or cleaning.
♦ Use a soft damp cloth to wipe the casing of the
dehumidier. Avoid using abrasive sponges and
detergent, spray or chemicals as these may cause
damage to the appliance.
♦ Use a soft dry cloth to wipe the control panel.
♦ Clean the water tank with soft cloth.
♦ Clean the lter at least once every two weeks.
♦ Empty and replace the water tank, clean the lter
and unplug the dehumidier if it is not to be used
for a long time.

ENGLISH (Original instructions)
10
1. Remove the back cover from the unit and remove
the lter.
2. Use a vacuum cleaner or pat the lter lightly to
dislodge the dust. If necessary wash the lter in
water with a neutral detergent. Rinse well and
leave to dry thoroughly.
3. Replace the lter into the back cover, ensuring the
convex of the lter is upwards and the edges sit
under the four clips.
4. Push the back cover up and back into the
appliance until it clicks into place. The incorrect
setting of the lter or cover will prevent the cover
clicking into place.
If the appliance is not to be used for a long time:
♦ Unplug and the dehumidier
♦ Empty, dry and replace the water tank
♦ Clean the air lter
♦ Store the unit upright in a cool, dry place, away
from direct sunlight.
Storing The Unit
WARNING: Unplug the unit from the mains and
ensure it has fully cooled down before storing.
Store in a cool, dry place, out of the reach of
children.
Mains plug replacement
If a new mains plug needs to be tted:
♦ Safely dispose of the old plug.
♦ Connect the brown lead to the live terminal in the
new plug.
♦ Connect the blue lead to the neutral terminal.
♦ If the product is class I (earthed), connect the
green/yellow lead to the earth terminal.
Note! If your product is class II double insulated
(only 2 wires in the cord set), no connection is to be
made to the earth terminal.
Follow the tting instructions supplied with good
quality plugs. Any replacement fuse must be of the
same rating as the original fuse supplied with the
product.
WARNING: The above section on mains plug
replacement is for authorized service centre
persons.
Before Initiation
To avoid damage, place the unit in an upright
position for at least 24 hours before initiation. Make
sure that the air outlet and air inlet are never blocked.
Only operate the unit on a horizontal surface to
ensure no water leaks out.
WARNING:
♦ Do not exceed impedance greeter than
0.236Ohm in supply the appliance is connected
to.
♦ Failure to comply may lead the supply authority
to impose restrictions to connection.
♦ Please consult your energy supply authority if
the use of equipment exceeds 0.236 ohm.
♦ When the portable air conditioner or
dehumidier is turned on, the fan can work
continuously stable under normal conditions
to provide the minimum air volume of 100m3/h
even when the compressor is closed due to the
temperature controller.

ENGLISH
(Original instructions)
11
The following information is for qualied
technicians ONLY to tend any problems with the
BXEH60003GB
♦ Please do not attempt to x, repair or alter
this product in any way unless you are fully
qualied
♦ If you are concerned or want any further
advice please call 0333 220 6089
Instruction, Repairing Appliances Containing
R290
1. Checks to the area prior to beginning work on
systems containing ammable refrigerants,
safety checks are necessary to ensure that the
risk of ignition is minimised. For repair to the
refrigerating system, the following precaution
shall be completed prior to conducting work on
the system.
2. Work procedure shall be undertaken under a
controlled procedure so as to minimise the risk
of a ammable gas or vapour being present
while the work is being performed.
3. General work area - All maintenance staff
and others working in the local area shall be
instructed on the nature of work being carried
out. Work in conned spaces shall be avoided.
4. Checking for presence of refrigerant - The area
shall be checked with an appropriate refrigerant
detector prior to and during work, to ensure
the technician is aware of potentially toxic or
ammable atmospheres. Ensure that the leak
detection equipment being used is suitable
for use with all applicable refrigerants, i.e.
nonsparking, adequately sealed or intrinsically
safe.
5. Presence of re extinguisher - If any hot
work is to be conducted on the refrigerating
equipment or any associated parts, appropriate
re extinguishing equipment shall be available
to hand. Have a dry powder or CO2 re
extinguisher adjacent to the charging area.
6. No ignition sources - No person carrying out
work in relation to a refrigerating system which
involves exposing any pipe work shall use
any sources of ignition in such a manner that
it may lead to the risk of re or explosion. All
possible ignition sources, including cigarette
smoking, should be kept sufciently far away
from the site of installation, repairing, removing
and disposal, during which refrigerant can
possibly be released to the surrounding space.
Prior to work taking place, the area around
the equipment is to be surveyed to make sure
that there are no ammable hazards or ignition
risks. “No Smoking” signs shall be displayed.
7. Ventilated area - Ensure that the area is in the
open or that it is adequately ventilated before
breaking into the system or conducting any hot
work. A degree of ventilation shall continue
during the period that the work is carried out.
The ventilation should safely disperse any
released refrigerant and preferably expel it
externally into the atmosphere.
8. Checks to the refrigerating equipment - Where
electrical components are being changed, they
shall be t for the purpose and to the correct
specication. At all times the manufacturer’s
maintenance and service guidelines shall be
followed. If in doubt, consult the manufacturer’s
technical department for assistance. The
following checks shall be applied to installations
using ammable refrigerants:
♦ The actual refrigerant charge is in
accordance with the room size within
which the refrigerant containing parts are
installed;
♦ The ventilation machinery and outlets
are operating adequately and are not
obstructed;
♦ If an indirect refrigerating circuit is being
used, the secondary circuit shall be
checked for the presence of refrigerant;
♦ Marking to the equipment continues to be
visible and legible. Markings and signs that
are illegible shall be corrected;
♦ Refrigerating pipe or components are
installed in a position where they are
unlikely to be exposed to any substance
which may corrode refrigerant containing
components, unless the components
are constructed of materials which are
inherently resistant to being corroded or
are suitably protected against being so
corroded.

ENGLISH (Original instructions)
12
9. Checks to electrical devices
♦ Repair and maintenance to electrical
components shall include initial safety checks
and component inspection procedures. If a
fault exists that could compromise safety, then
no electrical supply shall be connected to the
circuit until it is satisfactorily dealt with. If the
fault cannot be corrected immediately but it is
necessary to continue operation, an adequate
temporary solution shall be used. This shall be
reported to the owner of the equipment so all
parties are advised. Initial safety checks shall
include:
♦ That capacitors are discharged: this
shall be done in a safe manner to avoid
possibility of sparking;
♦ That no live electrical components and
wiring are exposed while charging,
recovering or purging the system;
♦ That there is continuity of earth bonding.
10. Repairs to sealed components.
♦ During repairs to sealed components, all
electrical supplies shall be disconnected from
the equipment being worked upon prior to any
removal of sealed covers, etc. If it is absolutely
necessary to have an electrical supply to
equipment during servicing, then a permanently
operating form of leak detection shall be
located at the most critical point to warn of a
potentially hazardous situation.
♦ Particular attention shall be paid to the
following to ensure that by working on electrical
components, the casing is not altered in such
a way that the level of protection is affected.
This shall include damage to cables, excessive
number of connections, terminals not made
to original specication, damage to seals,
incorrect tting of glands, etc.
♦ Ensure that the apparatus is mounted securely.
Ensure that seals or sealing materials have
not degraded to the point that they no longer
serve the purpose of preventing the ingress of
ammable atmospheres.
♦ Replacement parts shall be in accordance with
the manufacturer’s specications.
11. Repair to intrinsically safe components
♦ Do not apply any permanent inductive or
capacitance loads to the circuit without
ensuring that this will not exceed the
permissible voltage and current permitted for
the equipment in use.
♦ Intrinsically safe components are the only
types that can be worked on while live in the
presence of a ammable atmosphere. The test
apparatus shall be at the correct rating.
♦ Replace components only with parts specied
by the manufacturer. Other parts may result
in the ignition of refrigerant in the atmosphere
from a leak.
12. Cabling
♦ Check that cabling will not be subject to wear,
corrosion, excessive pressure, vibration, sharp
edges or any other adverse environmental
effects. The check shall also take into account
the effects of aging or continual vibration from
sources such as compressors or fans.
13. Detection of ammable refrigerants
♦ Under no circumstances shall potential sources
of ignition be used in the searching for or
detection of refrigerant leaks. A halide torch (or
any other detector using a naked ame) shall
not be used.
♦ Removal and evacuation
♦ When breaking into the refrigerant circuit
to make repairs – or for any other purpose
– conventional procedures shall be used.
However, for ammable refrigerants it is
important that best practice is followed since
ammability is a consideration. The following
procedure shall be adhered to:
♦ Remove refrigerant;
♦ Purge the circuit with inert gas;
♦ Evacuate;
♦ Purge with inert gas;
♦ Open the circuit by cutting or brazing.
♦ The refrigerant charge shall be recovered
into the correct recovery cylinders.
For appliances containing ammable
refrigerants the system shall be purged
with oxygen-free nitrogen to render the
appliance safe for ammable refrigerants.
This process may need to be repeated
several times.

ENGLISH
(Original instructions)
13
♦ Compressed air or oxygen shall not be used for
purging refrigerant systems.
♦ For appliances containing ammable
refrigerants, refrigerants purging shall be
achieved by breaking the vacuum in the system
with oxygen-free nitrogen and continuing to
ll until the working pressure is achieved, then
venting to atmosphere, and nally pulling down
to a vacuum. This process shall be repeated
until no refrigerant is within the system.
When the nal oxygen-free nitrogen charge
is used, the system shall be vented down to
atmospheric pressure to enable work to take
place. This operation is absolutely vital if
brazing operations on the pipe-work are to take
place.
♦ Ensure that the outlet for the vacuum pump is
not close to any potential ignition sources and
that ventilation is available.
♦ Charging procedures
In addition to conventional charging procedures, the
following requirements shall be followed.
♦ Ensure that contamination of different
refrigerants does not occur when using
charging equipment.
♦ Hoses or lines shall be as short as possible to
minimise the amount of refrigerant contained
in them.
♦ Cylinders shall be kept in an appropriate
position according to the instructions.
♦ Ensure that the refrigerating system is earthed
prior to charging the system with refrigerant.
♦ Label the system when charging is complete
(if not already).
♦ Extreme care shall be taken not to overll the
refrigerating system.
♦ Prior to recharging the system, it shall
be pressure-tested with the appropriate
purging gas. The system shall be leak-
tested on completion of charging but prior to
commissioning. A follow up leak test shall be
carried out prior to leaving the site.
14. Decommissioning
♦ Before carrying out this procedure, it is
essential that the technician is completely
familiar with the equipment and all its detail.
It is recommended good practice that all
refrigerants are recovered safely.
♦ Prior to the task being carried out, an oil and
refrigerant sample shall be taken in case
analysis is required prior to re-use of recovered
refrigerant. It is essential that electrical power
is available before the task is commenced.
a. Become familiar with the equipment and its
operation.
b. Isolate system electrically.
c. Before attempting the procedure, ensure
that:
♦ Mechanical handling equipment is
available, if required, for handling
refrigerant cylinders;
♦ All personal protective equipment is
available and being used correctly;
♦ The recovery process is supervised at all
times by a competent person;
♦ Recovery equipment and cylinders conform
to the appropriate standards.
d. Pump down refrigerant system, if possible.
e. If a vacuum is not possible, make a
manifold so that refrigerant can be removed
from various parts of the system.
f. Make sure that cylinder is situated on the
scales before recovery takes place.
g. Start the recovery machine and operate in
accordance with instructions.
h. Do not overll cylinders (no more than 80%
volume liquid charge).
i. Do not exceed the maximum working
pressure of the cylinder, even temporarily.
j. When the cylinders have been lled
correctly and the process completed, make
sure that the cylinders and the equipment
are removed from site promptly and all
isolation valves on the equipment are
closed off.
k. Recovered refrigerant shall not be charged
into another refrigerating system unless it
has been cleaned and checked.

ENGLISH (Original instructions)
14
15. Labelling
♦ Equipment shall be labelled stating that it
has been de-commissioned and emptied
of refrigerant. The label shall be dated and
signed. For appliances containing ammable
refrigerants, ensure that there are labels on
the equipment stating the equipment contains
ammable refrigerant.
16. Recovery
♦ When removing refrigerant from a system,
either for servicing or decommissioning,
it is recommended good practice that all
refrigerants are removed safely.
♦ When transferring refrigerant into cylinders,
ensure that only appropriate refrigerant
recovery cylinders are employed. Ensure that
the correct number of cylinders for holding the
total system charge is available. All cylinders
to be used are designated for the recovered
refrigerant and labelled for that refrigerant
(i.e. special cylinders for the recovery of
refrigerant). Cylinders shall be complete with
pressure-relief valve and associated shut-off
valves in good working order. Empty recovery
cylinders are evacuated and, if possible, cooled
before recovery occurs.
♦ The recovery equipment shall be in good
working order with a set of instructions
concerning the equipment that is at hand
and shall be suitable for the recovery of all
appropriate refrigerants including, when
applicable, ammable refrigerants. In addition,
a set of calibrated weighing scales shall be
available and in good working order. Hoses
shall be complete with leak-free disconnect
couplings and in good condition. Before
using the recovery machine, check that it is in
satisfactory working order, has been properly
maintained and that any associated electrical
components are sealed to prevent ignition
in the event of a refrigerant release. Consult
manufacturer if in doubt.
♦ The recovered refrigerant shall be returned to
the refrigerant supplier in the correct recovery
cylinder, and the relevant waste transfer note
arranged. Do not mix refrigerants in recovery
units and especially not in cylinders.
If compressors or compressor oils are to be
removed, ensure that they have been evacuated to
an acceptable level to make certain that ammable
refrigerant does not remain within the lubricant.
The evacuation process shall be carried out prior
to returning the compressor to the suppliers. Only
electric heating to the compressor body shall be
employed to accelerate this process. When oil is
drained from a system, it shall be carried out safely.
Protecting the environment
Separate collection. Products and
batteries marked with this symbol must
not be disposed of with normal household
waste.
Remember the environment when disposing of
packaging around the appliance and when the
appliance is no longer required.
Products and batteries contain materials that can
be recovered or recycled, reducing demand for
raw materials. Please recycle electrical products
and batteries according to local provisions. Further
information is available at www.2helpU.com.
Technical data
BXEH60003GB
Input voltage V AC 220 - 240
Frequency Hz 50
Power input W210
Refrigerant R290 G45
Degree of protection IPX1
Permissible operational
pressure (High/Low)
Mpa 1.2
Maximum allowable
pressure (High/Low)
Mpa 2.5
Noise dB (A) 42
Weight KG 10
Extraction Litres/Day 20
Water tank Litres 2.5
Size L x W x H (mm) 250 x 250 x 460

ENGLISH
(Original instructions)
15
Product Guarantee
This product comes with a 2 Year guarantee from the
original date of purchase. If any defect arises due to
faulty materials of workmanship, the faulty products
must be returned to the place of purchase. Refund or
replacement is at the discretion of the retailer. This
guarantee is in addition to and in no way prejudices
your statutory rights.
The Following Conditions Apply:
♦ The product must be returned to the retailer
with proof of purchase or a receipt within the
1st year of purchase. For any product related
issues after 12 months please contact our
customer services team.
♦ The product must be installed and used in
accordance with the instructions contained in
this instruction guide.
♦ It must be used only for domestic purposes.
♦ It does not cover wear and tear, damage,
misuse or consumable parts.
♦ This guarantee is valid in the UK and Republic
of Ireland.
For all customer service enquires please contact
us below;
RKW,
Sutton House,
Berry Hill Road,
Stoke-on-Trent,
ST4 2NL
Email blackanddecker@rkwltd.com
Tel 0333 220 6089
Black & Decker® and BLACK+DECKER™ and the
Black & Decker® and BLACK+DECKER™ logos
are registered trademarks of The Black & Decker®
Corporation and are used under licence. All rights
reserved. Imported and Distributed by RKW LTD,
Sutton House, Berry Hill Industrial Estate, Berry Hill
Road, Stoke-on-Trent, ST4 2NL

11/2020
Table of contents
Other Black & Decker Dehumidifier manuals

Black & Decker
Black & Decker BDT20WTB User manual

Black & Decker
Black & Decker BDT50 Series User manual

Black & Decker
Black & Decker BDT30WTA User manual

Black & Decker
Black & Decker BXDH12E User manual

Black & Decker
Black & Decker BDT70PWT User manual

Black & Decker
Black & Decker BXHU050 Quick reference guide

Black & Decker
Black & Decker BDT30 Series User manual
Popular Dehumidifier manuals by other brands

TriStar
TriStar AC-5410 instruction manual

German pool
German pool KD-708B2 operating instructions

Drieaz
Drieaz LGR 3500i owner's manual

thermastor
thermastor QUEST Dry 105 Installation, operation and maintenance instructions

Arctic Aire
Arctic Aire ADR30A1G Owner's use and care guide

HOMEDEPOT
HOMEDEPOT MRS-LKEX-66AAK instruction manual