Bosch CM704B How to use

CM704B
8/16 Zone Expander Module
Security System
Installer Reference Guide
EN
Security Systems

Page 2 P/N: CM704BIRG Rev 1.6 E&OE Copyright © 2012
CM704B - 8/16 Zone Expander Module
The CM704B allows you to expand the hard wired zone capacity of se-
lected Vision control panels.
Table 1: lists the panels which are compatible with the CM704B and the
maximum number of expanders that can be supported on each.
Depending on the end of line (EOL) resistor option selected, each
CM704B installed will add 8 or 16 zones to the system.
CM704B Zone Expander Compatibility
Panel Supported Modules Supported
Solution 16i 1
Solution 144 8
Solution E 16
Table 1: CM704B Compatibility
The CM704B is supplied as a PCB module and can be installed in the
same cabinet as the main panel or remotely from the panel using the
encrypted, 4 wire RS485 LAN connection. The module requires only one
space in the enclosure and is supplied with all necessary EOL resistors
and mounting hardware. Sensors connected to the expander can be
powered from the Vision panel,(1) or from an external power supply like
the CM720B or CM723B power supply modules.(2)
Power is connected to the module dierently depending on the connec-
tion method required. Refer to Figure 2: and Figure 3: on page 5 for
LAN / Power wiring diagrams.
A dedicated service keypad and tamper input are provided. If the tamper
input is not required, you should t the supplied shunt to the tamper
input pins. To assist with installation, the module includes indicators to
show Module and Zone Power status at all times.
A four way dip switch is used to select the zone expander modules
address. The address setting determines the zone numbers for each
expander as shown in Table 2: and Table 3: on page 4. You should
consult these tables before you begin zone programming
Programming Considerations
1) The CM704B expander does not need to be enabled via panel pro-
gramming. The panel will recognise it after power cycle or after per-
forming a LAN scan function (MENU 6-0-2).
2) The EOL resistor value selected in the panel programming is global for
all zones in the system including zones on expanders.
3) Some zones are defaulted as Not Used in panel programming. These
must be programmed as valid zone types before they become active.
Figure 1: Zone Wiring Options
ZONE 2
N/C
N/C
ZONE 1
ZN 1
GND
ZN 2
N/C - No EOL Zone
ZONE 2
ZONE 1
N/C
N/C
ALARM
ALARM
ZN 1
GND
ZN 2
N/C - Single EOL Zone
(6K8 EOL)
(3K3 EOL)
N/C
N/C
ALARM
ALARM
ZN 1
GND
ZN 2
ZONE 1
ZONE 9
N/C - Split EOL Zone
1
2
TAMPER
(6K8 EOL)
TAMPER
(3K3 EOL)
N/C
N/C
ZN 1
GND
ZN 2
ALARM ZONE 1
N/C - Zone with Tamper
2
ZONE 2
N/O
N/O
ZONE 1
ZN 1
GND
ZN 2
N/O - No EOL Zone
ZONE 2
ZONE 1
N/O
N/O
ALARM
ALARM
ZN 1
GND
ZN 2
N/O - Single EOL Zone
(6K8 EOL)
(3K3 EOL)
N/O
N/O
ALARM
ALARM
ZN 1
GND
ZN 2
ZONE 9
ZONE 1
N/O - Split EOL Zone
TAMPER
(6K8 EOL)
TAMPER
(3K3 EOL)
N/C
N/O
ZN 1
GND
ZN 2
ALARM ZONE 1
N/O - Zone with Tamper
ZONE WIRING OPTIONS

P/N: CM704BIRG Rev 1.6 Page 3
Copyright © 2012 E&OE
Zone Conguration
On panels with a zone capacity greater than 16, (Solution 144, Solution E) each CM704B zone expander module
installed on the system will occupy 16 zones regardless of the EOL resistor conguration selected. See “Table 3:
CM704B Address Conguration On Solution E and Solution 144 Panels” on page 4 for more information.
Depending on the EOL resistor option selected, only one CM704B can be installed on panels with a maximum zone
count of 16 zones. (Solution 16i). See “Table 2: CM704B Address Conguration On Solution 16i Panel” on page 4
for more information.
Single EOL Monitoring
If single EOL resistor conguration has been selected and one CM704B zone expander has been installed at address
1, the system provide zones 1 to 8 on the main panel and zones 17 to 24 on the expander module.
Split EOL Monitoring
If the Split EOL resistor conguration has been selected and one CM704B zone expander has been installed at ad-
dress 1, the system provides zones 1 to 16 on the main panel and zones 17 to 32 on the expander module.
Alarm + Tamper Monitoring
If the Alarm + Tamper monitoring EOL resistor conguration has been selected and one CM704B zone expander has
been installed at address 1, the system will provide zones 1 to 8 on the main panel and then zones 17 to 24 on the
expander module. 2K2 + 6K8 and 10K + 10K EOL resistor values options can also be selected for Alarm and Tamper
Monitoring.
RF Zones
If an RF receiver has been installed, then all zones up to the maximum number supported by the panel become avail-
able for use as RF zones.
An RF zone can be assigned or mapped to any spare zone input allowing zone parameters to be programmed.
Assigning an RF zone to a physical zone will override or ignore the hard wired zones physical input terminals. For
example if zone 7 is congured as an RF zone then any devices connected to the zone 7 terminals will be ignored.
i
Note
The EOL resistor value setting is a global panel option. This means that all zones on the system must use the same
EOL resistor values. EOL resistors are not required for RF Zones.
Module Address Switches and Zone Numbering
Table 2: and Table 3: list the module address settings and corresponding zone numbers that apply when adding zone
expanders to the listed panels. Each zone expander module added to the Solution 16i will provide a maximum of
8 additional zones. Zone expanders should not be tted to this panels when the Split EOL resistor option has been
selected.
i
Note
Only one CM704B can be assigned to each address. All mod-
ules are supplied from the factory set to address 1. You must
power cycle the panel or perform a LAN scan whenever you
change the module address. The LAN must be in the unlocked
state or the LAN scan will not nd new modules.
ON
Position
Figure 2: Address Switch Activation
(1): Provided the maximum available LAN current is not exceeded. See Installer Reference Guide for more information.
(2): The CM720B is a LAN Monitored 1 amp Switch Mode Power Supply with Pulse Battery Charger and the CM723B is a LAN Monitored 5 amp
Power Supply/Battery Charger.

Page 4 P/N: CM704BIRG Rev 1.6 E&OE Copyright © 2012
Panel Zone Assignments
The following tables list the zone numbers which become available when adding zone expander modules to the
system.
Solution 16i Panel
Module
Number
Address Setting Zone Numbers
(Single EOL)
Zone Numbers
(Alarm+Tamper)
Zone Numbers
(Split EOL)
SW1 SW2 SW3 SW4
Control Panel 1 to 8 1 to 8 1 to 16
1 = OFF OFF OFF OFF 9 to 16 9 to 16 N/A
1 x CM704B can be tted to the Solution 16i panel.
Table 2: CM704B Address Conguration On Solution 16i Panel
i
Note
When single EOL or Alarm + Tamper EOL options have been congured the rst 8 zones are available on the con-
trol panel zone terminals. If Split EOL monitoring is selected there is no need to install the zone expander as all 16
zones are available on the control panel zone terminals.
Each zone expander module added to the Solution 144 and Solution E panels occupies 16 zones regardless of the
EOL conguration selected. In Single or Alarm + Tamper EOL mode each expander only provides 8 hard wired zone
inputs.
Solution E and Solution 144 Panels
Module
Number
Address Setting Zone Numbers
(Single EOL)
Zone Numbers
(Alarm+Tamper)
Zone Numbers
(Split EOL)
SW1 SW2 SW3 SW4
Solution 144 Panel
Solution E Panel
Control Panel 1 to 8 1 to 8 1 to 16
1 = OFF OFF OFF OFF 17 to 24 17 to 24 17 to 32
2 = ON OFF OFF OFF 33 to 40 33 to 40 33 to 48
3 = OFF ON OFF OFF 49 to 56 49 to 56 49 to 64
4 = ON ON OFF OFF 65 to 72 65 to 72 65 to 80
5 = OFF OFF ON OFF 81 to 88 81 to 88 81 to 96
6 = ON OFF ON OFF 97 to 104 97 to 104 97 to 112
7 = OFF ON ON OFF 113 to 120 113 to 120 113 to 128
8 = ON ON ON OFF 129 to 136 129 to 136 129 to 144
9 = OFF OFF OFF ON 145 to 152 145 to 152 145 to 160
10 = ON OFF OFF ON 161 to 168 161 to 168 161 to 176
11 = OFF ON OFF ON 177 to 184 177 to 184 177 to 192
12 = ON ON OFF ON 193 to 200 193 to 200 193 to 208
13 = OFF OFF ON ON 209 to 216 209 to 216 209 to 224
14 = ON OFF ON ON 225 to 232 225 to 232 225 to 240
15 = OFF ON ON ON 241 to 248 241 to 248 241 to 256
16 = ON ON ON ON 257 to 264 257 to 264 257 to 272
Up to 16 x CM704B can be tted to the Solution E panel.
Up to 8 x CM704B can be tted to the Solution 144 panel.
Table 3: CM704B Address Conguration On Solution E and Solution 144 Panels
i
Note
When Single EOL or Alarm + Tamper EOL options have been congured the rst 8 zones are available on the con-
trol panel zone terminals. If Split EOL monitoring is selected the rst 16 zones are available on the control panel
zone terminals.

P/N: CM704BIRG Rev 1.6 Page 5
Copyright © 2012 E&OE
N12138
N12138
EARTH
POWER OUTPUT
POWER OUTPUTS
CAUTION
When powering sensors and other
devices from the panel’s power supply
you must ensure that the MAXIMUM
available LAN+ current is not exceeded.
If in doubt you should use a separate
power supply (CM720 or equivalent)
MODULE LAN
CONTROL PANEL
A
-
+B
T
o
C
o
n
t
r
o
l
P
a
n
e
l
BK
RD
WH
BL BK
RD
WH
BL
N12138
N12138
EARTH
POWER OUTPUT
POWER OUTPUTS
T
o
C
o
n
t
r
o
l
P
a
n
e
l
T
o
P
o
w
e
r
S
u
p
p
l
y
CAUTION
Do NOT connect the positive feed
from separate power supplies
together when powering this module.
GND
+12V
EXTERNAL
POWER SUPPLY
MODULE LAN
CONTROL PANEL
A
-
+B
BK
RD
WH
BL
BK
RD
WH
BL
BK
Figure 2: Connection Diagram With Power Supplied By System LAN+
Figure 3: Connection Diagram With Power Supplied By External Supply
To power the module and sensors from the panel LAN connect the wiring as shown. Care must be taken to
ensure that the load does not exceed the maximum LAN+ current. When the module is located more than 100m
from the panel the use of an external power supply (CM720B or CM723B) is recommended. See the Installer Refer-
ence Guide for more information on available current and wiring options.
To power the module and sensors etc from an external power supply (CM720B or CM723B) connect the wiring as
shown. In this situation, the LAN+ terminal of the module is connected to the external power supply (CM720B or
similar) and must NOT be connected to the panel LAN+ terminal. See the Installer Reference Guide for more infor-
mation on available current and wiring options.
Powering The CM704B From An External Power Supply
Powering The CM704B From The LAN
i
Note
The power source connected to the LAN+ terminal on the module is internally connected to the +12V power output
terminals via a 1 amp resetting fuse. This means that devices powered from these terminals are eectively being
supplied from the power supply connected to the LAN+ terminal.
When the Power OK LED is on the power output is OK. The fuse will open and the LED extinguish if the power out-
put terminals are overloaded.
The maximum continuous current drawn from the (+12V) power output terminals should not exceed 500 mA when
being powered from the LAN or 1 Amp when powered via an external power supply.

Page 6 P/N: CM704BIRG Rev 1.6 E&OE Copyright © 2012
N12138
N12138
VISION
Powered by
P/Nº:
MFG:
CM704
01-Jan-10
8/16 LAN Zone Expander
D
IGIFLE
X
VER: 2.00
EARTH
ZONE 8
ZONE 7
N/C
N/C
ZONE 6
ZONE 5
N/C
N/C
ZONE 4
ZONE 3
N/C
N/C
ZONE 2
ZONE 1
N/C
N/C
POWER OUTPUT
POWER OUTPUTS
N12138
N12138
P/Nº:
MFG:
CM704B
24-Jun-12
8/16 LAN Zone Expander
VER: 2.00
RoHS
CM704B Connection Diagram - Rev B PCB
Connection point for
installer service keypad.
CM704B Expander Board Address Select Switch.
Modules must be set to a unique address as
shown in Table 2 and Table 3.
Expander earthing point.
Connect to communications earth
for maximum lightning protection.
See the LAN Wiring and System
Earthing sections of the Installer
Reference Guide for more information
Tamper Connection.
Fit shunt if not required.
Power Output Terminals.
Used to power sensors etc.
Five individual output
power terminals are
provided on the CM704B
Expander.
Zone Power LED lights to
show that Zone power is
present on terminals and not
overloaded.
LAN Termination Shunt.
Only t the shunt if this
module is one of the two
modules furthest from the
Control Panel.
See Figure 2: and Figure 3: on
page 5 for the LAN / Power
wiring instructions.
Figure 4: CM704B Connection Diagram (REV B PCB)
Expander Status LED pulses
to indicate that the Expander
is functioning correctly and
communicating with the
panel.
If the light is on steady it
means that the module is
not communicating with
the panel.
i
Note
You must power cycle the panel or perform
a LAN scan after connecting the CM704B
for the system to initialise the expander.
i
Note
The +12V outputs are fuse protected on
board via a 1Amp resetting fuse.
The maximum continuous current drawn
from the (+12V) power output terminals
should not exceed 500mA when being
powered from the LAN or 1Amp when
powered via an external power supply.
Single EOL
Connection Shown

P/N: CM704BIRG Rev 1.6 Page 7
Copyright © 2012 E&OE
CM704B Specications
Part Number: CM704B - 8/16 Zone Expander Module (RS485 LAN)
Operating Voltage: 10.0V DC. - 14.5V DC. @ 50mA Max
Module Connection:
(RS485 LAN)
Max total LAN length using multi strand security cable = 300m ,
Max total LAN length using 2 pair twisted shielded data cable (Belden 8723) = 1200m.
See manual for complete wiring instructions.
Operating
Environment: 0˚ to 55˚C RH 5 to 85% at 30˚C non-condensing.
Fixing Method: The CM704B can be mounted in the MW700, MW710, MW720 or MW730 enclosures using clip in
PCB mounts supplied.
Warranty: 3 years from date of manufacture (return to base)
N12138N12138 RoHS
In the interest of ongoing product development this
document is subject to change without notice.
The Solution 144 and Solution E panels also support the CM705B Universal Expander Modules. The CM705B is like
having 1 x CM704B zone expander, 1 x CM710B output expander and 1 x CM720B power supply module all in one
and as such each universal expander added to the system will consume the address of the corresponding single
function module.
For example if a universal expander is assigned to address 4, then you cannot assign a CM704B, CM710B or CM720B
module to address 4 and the zones corresponding to module 4 will be provided on the universal expander as per the
table below.
See the CM705B installation guide for more information.
Module
Number
Address Setting Zone Numbers
(Single EOL)
Zone Numbers
(Alarm+Tamper)
Zone Numbers
(Split EOL)
SW1 SW2 SW3 SW4
Control Panel 1 to 8 1 to 8 1 to 16
4 = ON ON OFF OFF 65 to 72 65 to 72 65 to 80
Table 4: Zones Allocated To Module Address 4
Zone Allocation When Using the CM705B Universal Expander

Bosch Security Systems
25 Huntingwood Drive
Huntingwood, NSW 2148
Australia
Phone: +612 9672 1777
Facsimile: +612 9672 1717
© 2012 Bosch Security Systems
CM704BIRG
Issue FTR1.6
Table of contents
Other Bosch Computer Hardware manuals

Bosch
Bosch LTC 2380 User manual

Bosch
Bosch D5370-USB User manual

Bosch
Bosch B820 User manual

Bosch
Bosch AC-EXP User manual

Bosch
Bosch FPE-1000-SLC User manual

Bosch
Bosch MADI Card Plus Series User manual

Bosch
Bosch SMB365 Installation and operating instructions

Bosch
Bosch G10-1W User manual

Bosch
Bosch CL300 User manual

Bosch
Bosch ADC 0064 A User manual
Popular Computer Hardware manuals by other brands

Siemens
Siemens CP 1243-8 IRC operating instructions

Trinamic
Trinamic TMCM-351 Firmware manual

Thermaltake
Thermaltake V3 Black Edition VL8000 Series user manual

Cypress Semiconductor
Cypress Semiconductor CY7C1217H Specification sheet

Alphacool
Alphacool GPX-N 1080-M16 instruction manual

Renesas
Renesas H8SX/1650 Hardware manual