FCS-320-TM Aspirating Smoke Detector Technical Specifications | en 9
Bosch Sicherheitssysteme GmbH Operation Guide F.01U.130.928 | 1.0 | 2009.11
Point-type detector projection
The system’s aspiration points can be equated with point-type smoke detectors. The
monitoring areas can therefore be planned in accordance with the applicable national
regulations.
Diagnostics
A system with FAS-ASD-DIAG Diagnostic Software, which enables quick and convenient error
containment, is available for maintenance and service. The current and stored (max. 72 hours)
unit status is read out to the diagnostic appliance via the unit's infrared port. The data is
transmitted from the diagnostic appliance to a laptop via a USB cable.
Selecting the fan voltage
The fan voltage can be increased from 9 V to 12 V for any special planning processes. In
addition, the fan voltage can be increased up to 13.5 V in intervals of 1 V via the
FAS-ASD-DIAG Diagnostic Software. The increase in the fan voltage causes an increase in the
air transport speed and therefore reduces detection time.
Extensive pipe accessories
The extensive range of accessories enables the FCS-320-TM aspirating smoke detectors to be
used even in the most difficult conditions. Products from air filters and condensate separators
to blowing-out systems increase the service life in extremely dusty, damp and cold
environmental conditions.
2.2 Areas of Application
Thanks to their detection principle, FCS-320-TM Aspirating Smoke Detectors provide an
extremely versatile fire alarm system.
Principle
Air samples are taken from the monitoring range by a pipe system with defined aspiration
borings and then fed to the detection unit.
This is especially well-suited for areas in which point-type detectors cannot be used or can
only be used under certain circumstances. These include:
– Areas that are difficult to access, in which point detectors are difficult to install and
maintain
– Air-conditioned areas
– Areas that require the earliest detection possible
– Areas with a height greater than that allowed for point detectors
– Areas in which point detectors are not desired for aesthetic reasons
– Areas in which strong electromagnetic fields occur
– Areas that are exposed to high or low temperatures
– Areas with contaminated air that require filter elements
– Areas that must be protected against vandalism.
Space protection
The FCS-320-TM series is suitable for monitoring areas such as
– Those with double floors, false ceilings
– Tunnels, ducts, barely accessible hollow spaces
– Storage, high-rise warehouses, elevator shafts
– Museums, cultural institutions
– Hotel rooms, hospital rooms, offices, prison cells, train compartments