9 Installer Manual
No.
Installer Setting
Displayed
Default
Available
Description of
Setting
Settings
Available Settings
8System Type SYSTEM CONV 11
Select the type of equipment you are controlling. The HP 32 system type is for a 2-stage heat pump compressor
(stage 1 and 2) with auxiliary heat (stage 3). System types CONV 22 and HP 32 are not available in model 4030.
91st Stage Differential DEGREE 0.5
DIF1
Selects a 1st stage temperature differential which controls the degree of separation between the setpoint temperature
and the 1st stage of heating or cooling.
10 2nd Stage Differential DEGREE 2.0
DIF2
[Only available if a 2 or 3 stage system was selected in
setting
8] Selects a 2nd stage temperature differential
which controls the degree of separation between the 1st and 2nd stage of heating or cooling.
11 3rd Stage Differential DEGREE 2.0
DIF3
[Only available if a 3 stage system was selected in
setting
8] Selects a 3rd stage temperature differential which
controls the degree of separation between the 2nd and 3rd stage of heating.
12 Conventional Heat FAN 1 GAS
Fan Control
[Only available if a conventional system was selected in
setting
8] Selects a 1st stage fan control of either
gas or electric heat. If Electric is selected, the thermostat turns on the system fan with a call for heating.
13 Emergency Heat EMER FAN ELEC
Fan Control
[
Only available if a 2 or 3 stage heat pump system was selected in setting 8] Selects emergency heat fan control
of either gas or electric heat. If Electric is selected, the thermostat turns on the system fan with a call for emergency heat.
14 Finish with High Stage AUX FNSH NO
[Only available if a 2 or 3 stage system was selected in setting 8] When Finish with High Stage is enabled, once
engaged, the supplemental heat source (2nd or 3rd stage) will remain on until temperature is satisfied. When disabled, these
supplemental heat source(s) will turn off approximately 0.5 degrees before setpoint to let the 1st stage heat source complete
the heat call.
15
Reversing Valve R VALVE 0
(O/B Terminal)
[Only available if a heat pump system was selected in setting 8] Selects the output state of the O/B terminal. Select
O for this terminal to be active in the cool mode or select B for this terminal to be active in the heat mode.
16 Fossil Fuel
AUX HEAT ELEC
Backup Heat
[Only available if a 2 or 3 stage heat pump system was selected in
setting
8] When set to electric, both the
compressor and auxiliary stage will run when a call for auxiliary heat is made. When set to gas, the compressor stage(s)
will be locked out one minute after a call for auxiliary heat. This setting can be overridden if setting an auxiliary heat
balance point in setting 34.
CONV 11 Select for 1H/1C Conventional system
CONV 22 Select for 2H/2C Conventional system (4235)
HP 11 Select for 1H/1C Heat Pump system
HP 21
Select for 2H/1C Heat Pump system
HP 32 Select for 3H/2C Heat Pump system (4235)
HD 1 Select for heat-only Hydronic system
HD 11 Select for Hydronic system with cooling
0.5, 1.0, 2.0
Select a 1st stage temperature differential of 0.5°,
1° or 2° F (0.2°, 0.5° or 1.0° C)
1.0, 2.0, 3.0
Select a 2nd stage temperature differential of 1°, 2°, 3°,
4.0, 5.0, 6.0
4°, 5° or 6° F (0.5°, 1.0°, 1.5°, 2.0°, 2.5° or 3.0° C)
1.0, 2.0, 3.0
Select a 3rd stage temperature differential of 1°, 2°, 3°,
4.0, 5.0, 6.0
4°, 5° or 6° F (0.5°, 1.0°, 1.5°, 2.0°, 2.5° or 3.0° C)
GAS
Select for conventional Gas heating
ELEC
Select for conventional Electric heating
ELEC
Select for Electric Emergency Heat
GAS
Select for Gas Emergency Heat
N
0
Finish with High Stage is disabled
YES
Finish with High Stage is enabled
0
Select for cool active Reversing Valve
B
Select for heat active Reversing Valve
ELEC
Select for Electric Auxiliary heat (with compressor)
GAS
Select for Gas Auxiliary heat
(without compressor)