Bryant SYSTXBBSMS01--E User manual

SYSTXBBSMS01--E
EvolutionrSmart Sensor for Zoning
Installation Instructions
NOTE: Read the entire instruction manual before starting the
installation.
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance,
or use can cause explosion, fire, electrical shock, or other
conditions which may cause death, personal injury or property
damage. Consult a qualified installer, service agency or your
distributor or branch for information or assistance. The qualified
installer or agency must use factory--authorized kits or accessories
when modifying this product. Refer to the individual instructions
packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing,
and work gloves. Have a fire extinguisher available. Read these
instructions thoroughly and follow all warnings and cautions
included in literature and attached to the unit. Consult local
building codes and the current edition of the National Electrical
Code (NEC) NFPA 70. In Canada, refer to the current editions of
the Canadian Electrical Code CSA C22.1.
Recognize safety information. When you see this symbol on
the unit and in instructions or manuals, be alert to the potential for
personal injury. Understand the signal words DANGER,
WARNING,andCAUTION. These words are used with the
safety--alert symbol. DANGER identifies the most serious hazards,
which will result in severe personal injury or death. WARNING
signifies hazards, which could result in personal injury or death.
CAUTION is used to identify unsafe practices, which may result
in minor personal injury or product and property damage. NOTE
is used to highlight suggestions which will result in enhanced
installation, reliability, or operation.
INTRODUCTION
Bryant’s EvolutionrSmart Sensors are optional replacements for
Remote Room Sensors used with Evolution Zoning systems. It
provides a temperature display and buttons to adjust the desired
temperature within the zone. It also displays outdoor temperature
and indoor humidity. When used with an Evolution Connext
Control wall control-- FAN, HOLD and HOLD UNTIL features are
available. When used with an Evolution User Interface (UIZ) wall
control-- FAN, HOLD, OVERRIDE, UNOCCUPIED features are
available.
INSTALLATION CONSIDERATIONS
Any zone may use an Evolution Smart Sensor. The Evolution
Smart Sensor can be “home run” wired directly to the Damper
Control Module, or “daisy chained” from the wall control or
another Smart Sensor via 4--wire ABCD communication bus.
Ordinary thermostat wire is recommended; however, solid
conductor, stranded, or shielded wire may be used. Use 22 AWG or
larger for normal wiring applications. Continuous wire lengths
over 100 ft. should use 20 AWG or larger. Plan the connection of
each Smart Sensor to provide easiest wiring route.
NOTE: Whenever possible, it is suggested to always “home run”
wires back to the Damper Control Module for convenience of
troubleshooting. Using a “pig--tailed” connection, or a field
supplied terminal block may be helpful in achieving proper wire
termination at the Damper Control Module.
An Evolution Smart Sensor may now be used to control Zone 1. In
addition, a Remote Room Sensor may also be used in the same
zone. If a Remote Room Sensor is applied in the same zone, the
Remote Room Sensor has temperature priority over the Smart
Sensor.
HOLD
A04148
Fig. 1 -- Evolution Smart Sensor
SYSTXBBSMS01--E
INSTALLATION
Step 1 — Select Smart Sensor Location
Sensor should be mounted:
SApproximately 5 ft. (1.5m) from floor.
SClose to center of zone, preferably on inside partitioning wall.
SOn section of wall without pipes or ductwork.
SWhere wiring can be routed to it within wall. Avoid running
directly next to other AC power.
Sensor should NOT be mounted:
SClose to a window, on outside wall, or next to a door leading to
the outside.
SExposed to direct light and heat from a lamp, sun, fireplace, or
other temperature radiating object which may cause a false
reading.
SClose to or in direct airflow from supply registers and return--air
grilles.
SIn areas with poor air circulation, such as behind a door or in an
alcove.
SDo not run wires next to AC power lines.

2
Outside Temp /
Indoor Humidity
Hold/Unoccupied
Time (+/-) Temp (+/-)
COOL / HEAT
Setpoint
Room Temperature
Fan Control
Fan Status
Humidity/OAT
HOLD
A04136
Fig. 2 -- Smart Sensor Functions
Step 2 — Install Evolution Smart Sensor
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury
or death.
Before installing sensor, turn off all power to unit. There may
be more than 1 power disconnect.
!WARNING
1. Turn OFF all power to unit.
2. If an existing thermostat or sensor is being replaced:
a. Remove existing device from wall.
b. Disconnect wires from existing device, 1 at a time. Be care-
ful not to allow wires to fall back into wall.
c. Discard or recycle old device.
d. If 4 wires exist in wall, they may be used. If not, plan and
route wiring to connect with either the Damper Control
Module, or User Interface. Multiple Evolution Smart
Sensors may be daisy chained together, but somewhere
chain must connect to either Damper Control Module or
the Evolution Connex Control/Evolution User Interface
wall control. (Smart Sensor daisy chain wire limit is 100
ft.)
Recommended connection is:
A -- Green = Data A
B -- Yellow = Data B
C -- White = 24vac (com)
D -- Red = 24vac (hot)
NOTE: It is not mandatory that the above color code be used, but
each ABCD connection in the system MUST be wired consistently.
3. To mount Smart Sensor, remove rear mounting base. Route
wires through hole in mounting base and level base against
wall.
4. Mark wall through 2 mounting holes and drill two 3/16--in.
holes. Secure assembly to wall with 2 anchors and screws
provided, making sure all wires properly extend through
opening.
5. Adjust length and routing of thermostat wire to reach each
terminal entry on the connector. Strip 1/4--in. of insulation
from each wire and properly connect to A--B--C--D.
6. Push any excess wire into the wall. Seal hole in wall to pre-
vent any air leaks. Leaks can affect Smart Sensor operation.
7. Attach Evolution Smart Sensor to the mounting base by lin-
ing up the plastic guides and gently snapping assembly to-
gether.
ELECTRICAL OPERATION HAZARD
Failure to follow this caution may result in equipment damage
or improper operation.
Improper wiring or installation may damage the Smart Sensor.
Check to make sure wiring is correct before proceeding with
installation or turning on unit.
CAUTION
!
Step 3 — Setup and Checkout
NEW EVOLUTION SMART SENSOR SETUP
Upon initial power up, the Evolution Smart Sensor will need to be
properly addressed. “ZONE” will be displayed and default zone
number “2” will be shown in the temperature display. The word
“SETUP” will also appear in the lower left text area. Use the
TEMP (+/--) button to select the correct zone address number 1
through 8. If only one Damper Control Module exists, the zone
address selection will only be 1 through 4. Once the zone number
is selected, press the FAN button to store the zone address and exit
the setup menu. The Evolution Smart Sensor is ready to operate.
CHANGING ZONE ADDRESS
To change an existing zone address, enter the setup menu by
pressing the FAN button for 10 seconds until “ZONE” is
displayed. Use the TEMP (+/--) button to select the correct zone
address and then press the FAN button once to automatically save
and exit the setup menu. If no buttons are pressed for
approximately 3 minutes, the screen will automatically save and
exit back to a normal display.
To ensure that all changes are recognized by the main control,
perform the “Full Installation” function in the Installation &
Service Menu of the Evolution Connex Control. After zone
addresses are changed.
BACKLIGHTING
The LCD backlighting will energize whenever a button is pressed.
The backlighting will de--energize after 10 seconds of no push
button or activity. To enable constant backlighting, press the FAN

3
button for 10 seconds to enter setup menu. Use the HOLD button
to toggle between “LIGHT OFF” and “LIGHT ON” which will
enable a fixed low intensity backlight. Press the FAN button to
save all settings and exit the setup menu. If no buttons are pressed
for approximately 3 minutes, the screen will automatically save and
exit back to a normal display.
FAN BUTTON
Pressing the FAN button momentarily will scroll through: AUTO,
LOW, MED, and HIGH speed continuous fan operation. The FAN
button is used to enter into the setup mode by holding the FAN
button for 10 seconds.
HUMIDITY/OAT BUTTON
Pressing the HUMIDITY/OAT button will toggle between the
Outside Temperature and Indoor Relative Humidity reading
(humidity reading at wall control). The LCD will revert back to the
outside temperature after 5 seconds.
COOL/HEAT BUTTON
Use the COOL/HEAT button to change between “COOL AT” and
“HEAT AT” setpoints.
TEMPERATURE UP/DOWN BUTTON
Use the TEMP (+/--) button to change a zone temperature setpoint.
Depending on the active heating/cooling mode, the “HEAT AT” or
the “COOL AT” setpoint will appear and will increment or
decrement accordingly. If not in a “HOLD” mode, changing the
setpoint, when used with an Evolution User Interface wall control,
will cause the Override timer to be displayed (i.e. 2--hours). If used
with an Evolution Connex Control wall control, changing the
setpoint will cause a HOLD UNTIL with a default time of
approximately 3 hours from the current time to be displayed. Either
the Override timer or default time can be increased or decreased by
using the TIME (+/--) button.
TIME UP/DOWN BUTTON
When used with Evolution User Interface wall control and the
TIME (+/--) button is pressed during a normal operation,
“OVERRIDE” is displayed and the Override timer is shown
(default is 2--hours). When used with an Evolution Connex
Control wall control and the TIME (+/--) button is pressed during a
normal operation, pressing the setpoint will cause a HOLD UNTIL
with a default time of approximately 3 hours from the current time
to be displayed. When used with either wall control, the Override
timer or default time can be increased or decreased by using the
TIME (+/--) button. While the timer or default time is shown, the
TIME buttons can be used to raise or lower the Override timer or
the default time in 15--minute increments up to a maximum of 24
hours. If the time is decreased to zero, the “OVERRIDE” text
disappears along with the timer or the default time will be replaced
with “SCHEDULED,” depending on the type of wall control, and
the program resumes regular operation.
NOTE: If the wall control is configured for non--programmable
operation, the Evolution Smart Sensor will ignore HOLD and
Override functions at the Smart Sensor.
HOLD BUTTON
Pressing the HOLD button momentarily will cause “HOLD” to be
displayed. The system will continue using the active (displayed)
temperature setpoints indefinitely. Pressing the HOLD button again
removes the “HOLD” text and the system resumes normal
programming schedules. When used with an Evolution User
Interface wall control, pressing the HOLD button for
approximately 3 seconds will cause “UNOCCUPIED” to be
displayed in the lower left area of the LCD and the unoccupied
temperature settings will be displayed. Pressing the HOLD button
again cancels the “UNOCCUPIED” mode and the system resumes
normal programming schedules.
NOTE: The Evolution Connex Control System does not include
an “unoccupied” mode.
SYSTEM OFF
When the OFF mode is selected on the Evolution Connex Control/
Evolution User Interface wall control, the Evolution Smart Sensor
will show “SYSTEM OFF” in the lower left text area of the display
screen. The end user will be unable to operate the system from the
Smart Sensor.
KEYPAD LOCK
The Evolution Smart Sensor can be locked if the FAN and
HUMIDITY/OAT buttons are pressed simultaneously for
approximately 3 seconds. A padlock icon will appear and all push
button functions will be ignored. Pressing the FAN and
HUMIDITY/OAT buttons again for 3 seconds will unlock the
Evolution Smart Sensor.
VACATION
When the VACATION mode is activated from Evolution Control/
Evolution User Interface wall control, the Evolution Smart Sensor
will display the “VACATION” in the lower left area of the LCD.
The padlock icon will appear, flash and ignore all push button
functions for 15 minutes.
ERROR DISPLAY
COM ERROR (Communication Error) will be displayed If the
Evolution Smart Sensor cannot send or receive communication
data with the Evolution Connex Control/ Evolution User Interface
wall control. Check ABCD wiring and Zone address.
SYST ERROR (System Error or Malfunction) will be displayed if
a system critical error is active at the Evolution Connex
Control/Evolution User Interface wall control. Check fault history
at the wall control.

4
* ABCD Connections are in Parallel with each other.
Smart Sensors and Equipment may be connected in any combination.
For easier troubleshooting, the installer may elect to use one terminal block
for wall control and smart sensor connections, and the other for equipment connections.
NOTE:
DAMPER CONTROL MODULE
ZONES 1-4
ABCD
RED
GREEN
YELLOW
WHITE
SMART SENSOR(S)
TO WALL CONTROL, AND/OR
DAISY CHAIN
OPTION
TO OTHER
SMART SENSORS
IF AVAILABLE
TO EQUIPMENT OR
ACCESSORY CONNECTIONS
A
B
C
DRED
COMMUNICATION
BUS
*
GREEN
YELLOW
WHITE
A
B
C
DRED
GREEN
YELLOW
WHITE
ABCD
RED
GREEN
YELLOW
WHITE
ABCD
RED
GREEN
YELLOW
WHITE
ABCD
RED
GREEN
YELLOW
WHITE
TO EQUIPMENT, AND/OR
DAMPER CONTROL MODULE
(ZONES 5-8)
A04135
Fig. 3 -- Typical Smart Sensor Wiring diagram

5
Outside Temp /
Indoor Humidity
Hold/Unoccupied
Time (+/-) Temp (+/-)
COOL / HEAT
Setpoint
Room Temperature
Fan Control
Fan Status
Humidity/OAT
HOLD
A04136
Fig. 4 -- Smart Sensor Operation
SMART SENSOR OPERATION
The Infinity Smart Sensor allows control and changing of zone
temperature setpoints. Continuous FAN selection is available;
AUTO, LOW, MED, HIGH. Other features include viewing
Outdoor Temperature and Indoor Relative Humidity. Evolution
Smart Sensor Functions also include; HOLD and UNOCCUPIED
settings.
A. Changing Desired Temperature
SThe current zone temperature will be displayed in the LCD.
SPress COOL/HEAT button to change between “COOL AT” and
“HEAT AT” setpoints.
A04141
SPress Temp (+/--) button to raise or lower setpoints.
SThe default time for temporarily overriding the temperature
schedule is 2:00 HRS as indicated by the text in the lower left
screen.
OVERRIDE
2:00 HRS
A04142
STemporary override time can be changed in 15--minute
increments by pressing the TIME (+/--) button to increase or
decrease the override timer.
NOTE: Override will not appear if programming has been turned
off.
B. HOLD/UNOCCUPIED
SPressing HOLD / UNOCCUPIED button will display HOLD
allowing setpoints to remain permanent and override any existing
program schedules. Pressing HOLD/UNOCCUPIED button
again will release HOLD and return to previous program
schedules.
SPressing HOLD/UNOCCUPIED button for approximately 3
seconds will display UNOCCUPIED status on lower left screen.
Pressing button again for approximately 3 seconds will release
UNOCCUPIED status and return to previous mode.
UNOCCUPIEDHOLD
A04143
C. Continuous Fan Adjustment
SPressing the FAN button will scroll through the following:
AUTO, LOW, MED, HIGH.
SWhen AUTO is selected, zone airflow is available only when a
heating or cooling demand exists within the zone.
SWhen LOW, MED, or HIGH is selected, zone airflow will be
continuous without a heating or cooling demand.
A04141
D. Outdoor Temperature and Indoor Relative Humidity
SThe current outside temperature is displayed in upper left corner
of the LCD.
SPress and release the HUMIDITY/OAT button to view % Indoor
Relative Humidity, value is measured at Zone Control (User
Interface).
SOutdoor temperature will return after five seconds or after the
button is pressed again.
%RH INSIDE 50
A04144

6
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
E2014 Bryant Heating & Cooling Systems D7310 W. Morris St. DIndianapolis, IN 46231 Edition Date: 03/14 U.S. Export Classification: EAR99.
R e p l a c e s: I I Z O N E S M S --- 0 3
C a t a l o g N o . I I --- Z O N E S M S --- 0 4
Table of contents
Other Bryant Accessories manuals
Popular Accessories manuals by other brands

1 BY ONE
1 BY ONE O00QH-0499 instruction manual

SM Pro Audio
SM Pro Audio ADDA 192-S operating manual

CARDIOSTRONG
CARDIOSTRONG CST-FT-125 Assembly and operating instructions

Delta-T Devices
Delta-T Devices SM200 quick start guide

Contro l4
Contro l4 ZCA-IDP10A installation guide

Silvercrest
Silvercrest SSA01B Operation and safety notes

PCB
PCB TORKDISC 5302D-01A Installation and operating manual

Rocket Fish
Rocket Fish RF-GPS31201 Guide d'installation rapide

Baicells
Baicells Nova-243 installation guide

German pool
German pool UTS-001 user manual

Concept2
Concept2 DV7320 manual

Turboair
Turboair TMKC-34S-N-SS Installation and operation manual