Buderus HS 2102 User manual

Service Manual
Ecomatic HS 2102
Save These Instructions !
5645 469 8/97

TABLE OF CONTENTS
1Mounting Instructions 4
2Program Overview 6
3Key Code 7
4Installation Entries 8-18
5Relay Test 19
6Testing the Manual Reset High Limit (STB) 20
7LCD Test 21
8Heating Curve Display 22
9Version Number 23
10 Troubleshooting Procedures 24
11 Reset 25
12 Sensor Curves 26-27
13 Wiring Diagrams 28-29
3
SYSTEMOVERVIEW
The Ecomatic HS2102 is a weather responsive control that is designed for residential
heating systems with a single type of radiation, such as fin tube baseboard, panel radiators,
or cast iron radiators. It can also be used to control and prioritize an indirect fired domestic
hot water tank.
The control provides the following features:
•Boiler water temperature modulation based on outdoor temperature.
• Domestic hot water priority.
• 7-day programmable clock.
• Daytime and nighttime temperatures.
• Room temperature compensation with optional BFC room sensor.
• Manual override switches for emergency operation.
• Freeze protection for heating system; constant circulation in nighttime below freeze
temperature.
• Freeze protection for indirect hot water tanks; maintenance tank at a minimum of
50°F (10°C) in night mode.
• Malfunction display for system troubleshooting.
• Standard non-adjustable 100°F/104°F pump logic for condensate protection of the boiler.
• Pump kick during vacation and summer operation; the control will operate pumps for
1 minute at 12:00PM every Wednesday to prevent pump seizure.
The “Service Manual - Ecomatic HS 2102” will include all information necessary to mount, wire, and
place the Ecomatic control into operation. The settings described in this manual are intended for use by the
heating contractor.
To change settings such as the time, date and heating program, please refer to the “Operating Instructions -
Control panel HS 2102” .This manual will allow the homeowner to customize the control to their needs.
2
NOTE: This manual is for reference only.The manual does NOT purport to address all design,
installation and safety considerations. It is the responsibility of the user of this manual to
determine the applicability and safety of each individual application and ensure its
compliance with local building codes.
It is expected that the user/installer is a licensed heating contractor with knowledge of
accepted industry practices for the installation and maintenance of the equipment and
various applications of the equipment involved.

TABLE OF CONTENTS
1Mounting Instructions 4
2Program Overview 6
3Key Code 7
4Installation Entries 8-18
5Relay Test 19
6Testing the Manual Reset High Limit (STB) 20
7LCD Test 21
8Heating Curve Display 22
9Version Number 23
10 Troubleshooting Procedures 24
11 Reset 25
12 Sensor Curves 26-27
13 Wiring Diagrams 28-29
3
SYSTEMOVERVIEW
The Ecomatic HS2102 is a weather responsive control that is designed for residential
heating systems with a single type of radiation, such as fin tube baseboard, panel radiators,
or cast iron radiators. It can also be used to control and prioritize an indirect fired domestic
hot water tank.
The control provides the following features:
•Boiler water temperature modulation based on outdoor temperature.
• Domestic hot water priority.
• 7-day programmable clock.
• Daytime and nighttime temperatures.
• Room temperature compensation with optional BFC room sensor.
• Manual override switches for emergency operation.
• Freeze protection for heating system; constant circulation in nighttime below freeze
temperature.
• Freeze protection for indirect hot water tanks; maintenance tank at a minimum of
50°F (10°C) in night mode.
• Malfunction display for system troubleshooting.
• Standard non-adjustable 100°F/104°F pump logic for condensate protection of the boiler.
• Pump kick during vacation and summer operation; the control will operate pumps for
1 minute at 12:00PM every Wednesday to prevent pump seizure.
The “Service Manual - Ecomatic HS 2102” will include all information necessary to mount, wire, and
place the Ecomatic control into operation. The settings described in this manual are intended for use by the
heating contractor.
To change settings such as the time, date and heating program, please refer to the “Operating Instructions -
Control panel HS 2102” .This manual will allow the homeowner to customize the control to their needs.
2
NOTE: This manual is for reference only.The manual does NOT purport to address all design,
installation and safety considerations. It is the responsibility of the user of this manual to
determine the applicability and safety of each individual application and ensure its
compliance with local building codes.
It is expected that the user/installer is a licensed heating contractor with knowledge of
accepted industry practices for the installation and maintenance of the equipment and
various applications of the equipment involved.

Mounting Instructions 1
5
Electrical connections must be made according to
the wiring diagram (See pages 28-31).
All the wires should be routed through the cable
raceway at the rear of the boiler. Rear panel jacket
may be modified per local code.
Use the white strain reliefs provided to lock all cables
into place on the back of the control.
Replace the top housing of the control and fasten
the two screws. The control is ready to be placed
into operation.
Tilt the display to the desired position.
1 Mounting Instructions
4
Remove the front panel of the boiler.
• Only necessary with G124X and G224
Remove the two screws and housing from the top of
the Ecomatic.
Insert the two front feet of the control
into the holes provided on the top of the
boiler. Then, firmly push down on the
rear of the control until it snaps into place.
The sensor bundle consists of one thermistor (FK), two
capillaries and a spacer. Mount the sensors per the following
boiler specific instructions.
G115, G205, G305: Replace brass well with chrome
Ecomatic well. The sensor bundle should be inserted
into the Ecomatic well.
G124X: Unwrap the sensor bundle. Remove spacers from
the chrome well on the boiler.The high limit (STB) capillary
and temperature sensor (FK) should be inserted into the
chrome well with existing Honeywell Aquastat. The
remaining capillary should be mounted to the supply
manifold and thoroughly insulated.
G224: The tridicator assembly should be moved to the
supply piping and replaced with the chrome plated Ecomatic
well. The sensor bundle should be inserted into this well.
Fasten the control to the boiler jacket
using the two screws as shown.

Mounting Instructions 1
5
Electrical connections must be made according to
the wiring diagram (See pages 28-31).
All the wires should be routed through the cable
raceway at the rear of the boiler. Rear panel jacket
may be modified per local code.
Use the white strain reliefs provided to lock all cables
into place on the back of the control.
Replace the top housing of the control and fasten
the two screws. The control is ready to be placed
into operation.
Tilt the display to the desired position.
1 Mounting Instructions
4
Remove the front panel of the boiler.
• Only necessary with G124X and G224
Remove the two screws and housing from the top of
the Ecomatic.
Insert the two front feet of the control
into the holes provided on the top of the
boiler. Then, firmly push down on the
rear of the control until it snaps into place.
The sensor bundle consists of one thermistor (FK), two
capillaries and a spacer. Mount the sensors per the following
boiler specific instructions.
G115, G205, G305: Replace brass well with chrome
Ecomatic well. The sensor bundle should be inserted
into the Ecomatic well.
G124X: Unwrap the sensor bundle. Remove spacers from
the chrome well on the boiler.The high limit (STB) capillary
and temperature sensor (FK) should be inserted into the
chrome well with existing Honeywell Aquastat. The
remaining capillary should be mounted to the supply
manifold and thoroughly insulated.
G224: The tridicator assembly should be moved to the
supply piping and replaced with the chrome plated Ecomatic
well. The sensor bundle should be inserted into this well.
Fasten the control to the boiler jacket
using the two screws as shown.

Key Code
The access to the installation level is protected against
unauthorized use by a key code. This will enable you
to change settings described in this manual.
This operating level should only be accessed by a
heating contractor or a trained operator.
Accessing the installation level.
Key Code 3
7
Key Code
• Press and release the “AUT” button. Button
is located adjacent to cover flap.
• Press and hold down the “INS”
button.
• Insert a pointed object into the hole
to the right of the “INS” button. Release
the “INS” button and remove the pointed
object from the hole.
• The control automatically
reverts back to previous operation if no
entries are made within 20 seconds.
• Different settings become accessible
by repeatedly pressing the “INS” button.
The display will indicate the current
setting. The value of each setting is
changed by turning the dial.
AMERICAN
INS O
SETTING THE LANGUAGE TO AMERICAN
• Enter the key code
• Turn dial until “American” appears.
• Automatic operation is resumed after
20 seconds.
2 Program Overview
6
Possible settings for the installation level.
The following settings allow the heating contractor to
customize the Ecomatic HS 2102 control for the
particular application.
1. Language:
Factory Setting: American
Other Languages: Deutsch, English,
Español, Italiano, etc.
2. Temperature Scale:
Factory Setting: Fahrenheit
Optional Selection: Celsius
3. Heating curve-REF TEMP:
Factory Setting: 167°F (75˚ C)
Range: 122°F to 194°F (50°C to 90°C)
4. Freeze protection temperature-FREEZTEMP:
Factory Setting: 34°F (1°C)
Range: 14°F to 50°F (-10°C to 10°C)
5. Room Sensor - BFC:
Factory Setting: Off
Option: On
6. Compensation temperature-ROOM COMP:
(only with room sensor)
Factory Setting: 5°F (3°C)
Range: 0°F to 18°F (0°C to 10°C)
7. Setback modes:
Factory Setting: Outside Air Setback
Options: Setback
Room Setback
Boiler Off
8. Minimum boiler water temperature-MIN TEMP:
Factory Setting: 50°F (10°C)
Range: 50°F to 104°F (10°C to 40°C)
9. Maximum boiler water temperature-MAX TEMP:
Factory Setting: 185°F (85°C)
Range: 149°F to 194°F (65°C to 90°)
10. Flue Gas Sensor-FLUE GAS:
Factory Setting: Off
(Not available in the USA)
11. Clock recalibration-TIM ADJ:
Factory Setting: 0 Sec/Day
Range: -59 to 59 Sec/Day
12. Room temperature shift-OFFSET:
Factory Setting: 0
Range: -9°F to 9°F (-5°C to 5°C)
13. Diagnostic Test Features:
Relay Test
LCD Test
Heating curve display
Version number

Key Code
The access to the installation level is protected against
unauthorized use by a key code. This will enable you
to change settings described in this manual.
This operating level should only be accessed by a
heating contractor or a trained operator.
Accessing the installation level.
Key Code 3
7
Key Code
• Press and release the “AUT” button. Button
is located adjacent to cover flap.
• Press and hold down the “INS”
button.
• Insert a pointed object into the hole
to the right of the “INS” button. Release
the “INS” button and remove the pointed
object from the hole.
• The control automatically
reverts back to previous operation if no
entries are made within 20 seconds.
• Different settings become accessible
by repeatedly pressing the “INS” button.
The display will indicate the current
setting. The value of each setting is
changed by turning the dial.
AMERICAN
INS O
SETTING THE LANGUAGE TO AMERICAN
• Enter the key code
• Turn dial until “American” appears.
• Automatic operation is resumed after
20 seconds.
2 Program Overview
6
Possible settings for the installation level.
The following settings allow the heating contractor to
customize the Ecomatic HS 2102 control for the
particular application.
1. Language:
Factory Setting: American
Other Languages: Deutsch, English,
Español, Italiano, etc.
2. Temperature Scale:
Factory Setting: Fahrenheit
Optional Selection: Celsius
3. Heating curve-REF TEMP:
Factory Setting: 167°F (75˚ C)
Range: 122°F to 194°F (50°C to 90°C)
4. Freeze protection temperature-FREEZTEMP:
Factory Setting: 34°F (1°C)
Range: 14°F to 50°F (-10°C to 10°C)
5. Room Sensor - BFC:
Factory Setting: Off
Option: On
6. Compensation temperature-ROOM COMP:
(only with room sensor)
Factory Setting: 5°F (3°C)
Range: 0°F to 18°F (0°C to 10°C)
7. Setback modes:
Factory Setting: Outside Air Setback
Options: Setback
Room Setback
Boiler Off
8. Minimum boiler water temperature-MIN TEMP:
Factory Setting: 50°F (10°C)
Range: 50°F to 104°F (10°C to 40°C)
9. Maximum boiler water temperature-MAX TEMP:
Factory Setting: 185°F (85°C)
Range: 149°F to 194°F (65°C to 90°)
10. Flue Gas Sensor-FLUE GAS:
Factory Setting: Off
(Not available in the USA)
11. Clock recalibration-TIM ADJ:
Factory Setting: 0 Sec/Day
Range: -59 to 59 Sec/Day
12. Room temperature shift-OFFSET:
Factory Setting: 0
Range: -9°F to 9°F (-5°C to 5°C)
13. Diagnostic Test Features:
Relay Test
LCD Test
Heating curve display
Version number

Installation Entries 4
9
REF TEMP 167
˚F
Setting the REF TEMP.
The heating curve is adjusted when the reference
temperature is changed.
The factory setting is 167˚ F; range is 122°F to 194°F.
Procedure
1. Enter the key code.
2. Press the “INS” button repeatedly until “REF TEMP”
appears in the display.
3. Turn the knob until the desired “REF TEMP” appears.
Automatic operation is resumed after 20 seconds.
Reference Temperature - Heating Cur ve Selection
The heating curve establishes the relationship between
the outside air and boiler water temperatures. The boiler
water temperature is lowered at warmer outside air
temperatures and the boiler water temperature is raised at
colder outside air temperatures.
The correct heating curve is determined by the
characteristics of the house, (ie. type of radiation,
construction, degree of insulation, etc.). Baseboard
systems are generally operated at 194°F at the outside
design temperature. Several curves are shown for
different design temperatures. Follow the curve to the
14°F outside temperature. Read the corresponding
boiler water temperature on the vertical scale. This is
your REF TEMP setting.
The control automatically creates a curve for all outside
temperatures. The factory setting for REF TEMP is 167°F.
To adjust the heating curve, raise or lower the REF TEMP
value on the control.
This setting is an approximation based on design
conditions and may need adjustment after the system
has been operating for some time.
Heating curve adjustments:
The REF TEMP fine adjustment should be done based on cold
weather performance. Increase the REF TEMP value if the room
temperature is too low during the cold days. Decrease the REF
TEMP if overheating tends to occur at low outside temperatures.
Make only minor adjustments and allow ample time for system
to respond. For fine adjustment of the curve during mild
weather, please consult page 18.
Example: REF TEMP Selection
Assume the maximum design water temperature for a
panel radiator system is 176°F. The curve shown is based
on a -20°F design temperature. To select this curve, set
the REF TEMP value to 140°F. The control then creates
this heating curve automatically.
4 Installation Entries
8
REF TEMP ˚F
167
68 52 36
OUTSIDE TEMPERATURE (°F)
68
194
176
158
140
122
104
86
20 4 -12 -28 -44
14 -20
68 59 50
OUTSIDE TEMPERATURE (°F)
41 32 23 14 5
0 -10 -20 -30 -40
-4 -13 -22 -31 -40
167
158
140
122
104
86
68
194
176
BOILER
WATER
TEMPERATURE (°F)

Installation Entries 4
9
REF TEMP 167
˚F
Setting the REF TEMP.
The heating curve is adjusted when the reference
temperature is changed.
The factory setting is 167˚ F; range is 122°F to 194°F.
Procedure
1. Enter the key code.
2. Press the “INS” button repeatedly until “REF TEMP”
appears in the display.
3. Turn the knob until the desired “REF TEMP” appears.
Automatic operation is resumed after 20 seconds.
Reference Temperature - Heating Cur ve Selection
The heating curve establishes the relationship between
the outside air and boiler water temperatures. The boiler
water temperature is lowered at warmer outside air
temperatures and the boiler water temperature is raised at
colder outside air temperatures.
The correct heating curve is determined by the
characteristics of the house, (ie. type of radiation,
construction, degree of insulation, etc.). Baseboard
systems are generally operated at 194°F at the outside
design temperature. Several curves are shown for
different design temperatures. Follow the curve to the
14°F outside temperature. Read the corresponding
boiler water temperature on the vertical scale. This is
your REF TEMP setting.
The control automatically creates a curve for all outside
temperatures. The factory setting for REF TEMP is 167°F.
To adjust the heating curve, raise or lower the REF TEMP
value on the control.
This setting is an approximation based on design
conditions and may need adjustment after the system
has been operating for some time.
Heating curve adjustments:
The REF TEMP fine adjustment should be done based on cold
weather performance. Increase the REF TEMP value if the room
temperature is too low during the cold days. Decrease the REF
TEMP if overheating tends to occur at low outside temperatures.
Make only minor adjustments and allow ample time for system
to respond. For fine adjustment of the curve during mild
weather, please consult page 18.
Example: REF TEMP Selection
Assume the maximum design water temperature for a
panel radiator system is 176°F. The curve shown is based
on a -20°F design temperature. To select this curve, set
the REF TEMP value to 140°F. The control then creates
this heating curve automatically.
4 Installation Entries
8
REF TEMP ˚F
167
68 52 36
OUTSIDE TEMPERATURE (°F)
68
194
176
158
140
122
104
86
20 4 -12 -28 -44
14 -20
68 59 50
OUTSIDE TEMPERATURE (°F)
41 32 23 14 5
0 -10 -20 -30 -40
-4 -13 -22 -31 -40
167
158
140
122
104
86
68
194
176
BOILER
WATER
TEMPERATURE (°F)

11
BFC ON
BFC Room Sensor:
The BFC room sensor is an optional room thermostat
that allows you to set and adjust day and night time
temperatures at the BFC. The BFC allows the control to
fine tune the boiler water temperature based on the desired
room temperature and the current room temperature. For
each degree of room temperature deviation from the BFC
setting, the BFC and the control adjust the boiler water
temperature by 3°. The BFC allows you to manually override
your heating program. If a BFC is not used, the control
operates using only outside temperature as a reference.
The BFC room sensor selection must be activated if the
system is equipped with a BFC.
To activate the BFC
1. Enter the key code.
2. Press the “INS” button repeatedly until “BFC” appears
in the display.
3. Turn the knob until “ON” appears in the display.
Automatic operation is resumed after 20 seconds.
Once the BFC room sensor has been activated, it is
no longer possible to adjust the day and night time
temperatures on the control panel; they can only be
adjusted at the BFC room sensor.
Installation Entries 4
10
Setting the FREEZTEMP.
To prevent the heating system from freezing in the setback
heating mode, the control will automatically run the heating
circulator when the outdoor temperature drops below the
set value.
The factory setting is 34˚ F; range is 14°F to 50°F.
To change the FREEZTEMP:
1. Enter the key code.
2. Press the “INS” button repeatedly
until “FREEZTEMP” appears in the display.
3. Turn the knob until the desired “FREEZTEMP” appears
in the display.
Automatic operation is resumed after 20 seconds.
FREEZTEMP ˚F
34
4 Installation Entries

11
BFC ON
BFC Room Sensor:
The BFC room sensor is an optional room thermostat
that allows you to set and adjust day and night time
temperatures at the BFC. The BFC allows the control to
fine tune the boiler water temperature based on the desired
room temperature and the current room temperature. For
each degree of room temperature deviation from the BFC
setting, the BFC and the control adjust the boiler water
temperature by 3°. The BFC allows you to manually override
your heating program. If a BFC is not used, the control
operates using only outside temperature as a reference.
The BFC room sensor selection must be activated if the
system is equipped with a BFC.
To activate the BFC
1. Enter the key code.
2. Press the “INS” button repeatedly until “BFC” appears
in the display.
3. Turn the knob until “ON” appears in the display.
Automatic operation is resumed after 20 seconds.
Once the BFC room sensor has been activated, it is
no longer possible to adjust the day and night time
temperatures on the control panel; they can only be
adjusted at the BFC room sensor.
Installation Entries 4
10
Setting the FREEZTEMP.
To prevent the heating system from freezing in the setback
heating mode, the control will automatically run the heating
circulator when the outdoor temperature drops below the
set value.
The factory setting is 34˚ F; range is 14°F to 50°F.
To change the FREEZTEMP:
1. Enter the key code.
2. Press the “INS” button repeatedly
until “FREEZTEMP” appears in the display.
3. Turn the knob until the desired “FREEZTEMP” appears
in the display.
Automatic operation is resumed after 20 seconds.
FREEZTEMP ˚F
34
4 Installation Entries

Installation Entries 4
Setback Mode
The control allows you to choose a lower nighttime, setback temperature.
You can choose from one of the following four modes
for night setback.
1. Outside Air Setback - OASETBACK (Factory Setting)
2. Setback - SETBACK
3. Boiler Off - BLR OFF
4. Room Setback - RMSETBACK
Selecting the setback mode
OASETBACK: If the outside temperature is below the FREEZTEMP,
(FREEZTEMP was set on page 10), boiler runs on a
setback curve.
If the outside temperature is above the FREEZTEMP,
heating system is off.
SETBACK: The boiler is set to the lower nighttime temperature. Set
directly with temperature button on control panel. This
mode is only to be used when no BFC is connected. The
pump runs continuously based on the nighttime room
temperature.
BLR OFF: The heating circuit is completely switched off during
setback times, except when the outside temperature is
below the FREEZTEMP, then the system runs on a
setback curve.
RMSETBACK: The nighttime room temperature is set with the slide
switch on the BFC room sensor. This mode requires
the use of the BFC.
Recommended Settings:
Heating system with BFC
room sensor: RMSETBACK
Heating system without
BFC room sensor: SETBACK
Commercial buildings without
BFC room sensor: SETBACK
Non-occupied in night mode: OASETBACK
Heating zone completely switched off,
except for freeze protection: BLR OFF
To change the setback mode:
1. Enter the key code.
2. Press the “INS” button repeatedly until ‘OASETBACK’ appears in the
display.
3. Turn the knob until the desired setback mode appears.
Automatic operation is resumed after 20 seconds.
OASETBACK
SETBACK
BLR OFF
RMSETBACK
13
12
Changing the ROOM COMP:
(Room temperature compensation)
The BFC room sensor compensates for swings in room temperature,
(ie: solar gain, open windows, etc.). The amount of compensation
can be adjusted according to individual preference.
The room temperature compensation range can only be changed if
a BFC room sensor has been activated.
Example: With the ‘ROOM COMP” at OFF, the BFC room
sensor will have no effect on the boiler water
temperature.
The amount of room temperature change that the
control compensates for is adjustable. With the
“ROOM COMP” at 15˚ F, the BFC will be able to
adjust to a 15˚ F (+10/-5) swing in room
temperature by adjusting boiler water temperature
accordingly.
The factory setting is 5˚ F; range is 0°F to 18°F.
To change the “ROOM COMP”:
1. Enter the key code.
2. Press the “INS” button repeatedly until “ROOM COMP”
appears in the display.
3. Turn the knob until “OFF”, or the desired temperature
appears in the display.
Automatic operation is resumed after 20 seconds.
4 Installation Entries
ROOM COMP ˚F
5

Installation Entries 4
Setback Mode
The control allows you to choose a lower nighttime, setback temperature.
You can choose from one of the following four modes
for night setback.
1. Outside Air Setback - OASETBACK (Factory Setting)
2. Setback - SETBACK
3. Boiler Off - BLR OFF
4. Room Setback - RMSETBACK
Selecting the setback mode
OASETBACK: If the outside temperature is below the FREEZTEMP,
(FREEZTEMP was set on page 10), boiler runs on a
setback curve.
If the outside temperature is above the FREEZTEMP,
heating system is off.
SETBACK: The boiler is set to the lower nighttime temperature. Set
directly with temperature button on control panel. This
mode is only to be used when no BFC is connected. The
pump runs continuously based on the nighttime room
temperature.
BLR OFF: The heating circuit is completely switched off during
setback times, except when the outside temperature is
below the FREEZTEMP, then the system runs on a
setback curve.
RMSETBACK: The nighttime room temperature is set with the slide
switch on the BFC room sensor. This mode requires
the use of the BFC.
Recommended Settings:
Heating system with BFC
room sensor: RMSETBACK
Heating system without
BFC room sensor: SETBACK
Commercial buildings without
BFC room sensor: SETBACK
Non-occupied in night mode: OASETBACK
Heating zone completely switched off,
except for freeze protection: BLR OFF
To change the setback mode:
1. Enter the key code.
2. Press the “INS” button repeatedly until ‘OASETBACK’ appears in the
display.
3. Turn the knob until the desired setback mode appears.
Automatic operation is resumed after 20 seconds.
OASETBACK
SETBACK
BLR OFF
RMSETBACK
13
12
Changing the ROOM COMP:
(Room temperature compensation)
The BFC room sensor compensates for swings in room temperature,
(ie: solar gain, open windows, etc.). The amount of compensation
can be adjusted according to individual preference.
The room temperature compensation range can only be changed if
a BFC room sensor has been activated.
Example: With the ‘ROOM COMP” at OFF, the BFC room
sensor will have no effect on the boiler water
temperature.
The amount of room temperature change that the
control compensates for is adjustable. With the
“ROOM COMP” at 15˚ F, the BFC will be able to
adjust to a 15˚ F (+10/-5) swing in room
temperature by adjusting boiler water temperature
accordingly.
The factory setting is 5˚ F; range is 0°F to 18°F.
To change the “ROOM COMP”:
1. Enter the key code.
2. Press the “INS” button repeatedly until “ROOM COMP”
appears in the display.
3. Turn the knob until “OFF”, or the desired temperature
appears in the display.
Automatic operation is resumed after 20 seconds.
4 Installation Entries
ROOM COMP ˚F
5

Installation Entries 4
15
MAX TEMP:
The control can be set not to exceed a maximum boiler
water temperature.
The boiler water will not exceed the “MAX TEMP”.
The factory setting is 185˚ F; range is 167°F to 194°F.
To change the ‘MAX TEMP’:
1. Enter the key code.
2. Press the “INS” button repeatedly until “MAX TEMP”
appears in the display.
3. Turn the knob until the desired maximum
temperature appears in the display. The control will
never exceed this maximum value except during
the burner relay test as described in the Manual
Reset High Limit Test.
Automatic operation is resumed after 20 seconds.
MAX TEMP 185
˚F
4 Installation Entries
14
MIN TEMP ˚F
50
MIN TEMP:
The control can be set to maintain a minimum boiler water
temperature during the heating mode. This is the ‘MIN TEMP”.
The boiler will not fall below the “MIN TEMP” during the
heating mode.
The factory setting is 50˚ F; range is 50°F to 104*F.
To change the “MIN TEMP”:
1. Enter the key code.
2. Press the “INS” button repeatedly until “MIN TEMP”
appears in the display.
3. Turn the knob until the desired minimum boiler
temperature appears.
Automatic operation is resumed after 20 seconds.
Every time the burner fires, the boiler water will reach
at least 113˚ F to ensure that the flue way passages remain
dry. This value cannot be changed.

Installation Entries 4
15
MAX TEMP:
The control can be set not to exceed a maximum boiler
water temperature.
The boiler water will not exceed the “MAX TEMP”.
The factory setting is 185˚ F; range is 167°F to 194°F.
To change the ‘MAX TEMP’:
1. Enter the key code.
2. Press the “INS” button repeatedly until “MAX TEMP”
appears in the display.
3. Turn the knob until the desired maximum
temperature appears in the display. The control will
never exceed this maximum value except during
the burner relay test as described in the Manual
Reset High Limit Test.
Automatic operation is resumed after 20 seconds.
MAX TEMP 185
˚F
4 Installation Entries
14
MIN TEMP ˚F
50
MIN TEMP:
The control can be set to maintain a minimum boiler water
temperature during the heating mode. This is the ‘MIN TEMP”.
The boiler will not fall below the “MIN TEMP” during the
heating mode.
The factory setting is 50˚ F; range is 50°F to 104*F.
To change the “MIN TEMP”:
1. Enter the key code.
2. Press the “INS” button repeatedly until “MIN TEMP”
appears in the display.
3. Turn the knob until the desired minimum boiler
temperature appears.
Automatic operation is resumed after 20 seconds.
Every time the burner fires, the boiler water will reach
at least 113˚ F to ensure that the flue way passages remain
dry. This value cannot be changed.

17
TIM ADJ 0
Clock
The time clock can be adjusted if the clock runs too fast
or too slow with the ‘TIM ADJ”.
For example: If the clock runs 10 seconds too fast per day,
set the TIME ADJ to -10.
Range is -59 to +59 sec/day.
To change the “TIM ADJ”:
1. Enter the key code.
2. Press the “INS” button repeatedly until ‘TIM ADJ”
appears in the display.
3. Turn the knob until the desired time
adjustment appears in the display.
Automatic operation is resumed after 20 seconds.
Installation Entries 4
4 Installation Entries
16
FLUE GAS OFF
Flue Gas
The flue gas temperature can only be measured with an
additional module, not available in the United States.
The factory setting is “OFF”. This must remain in the off
position or an error message will appear.

17
TIM ADJ 0
Clock
The time clock can be adjusted if the clock runs too fast
or too slow with the ‘TIM ADJ”.
For example: If the clock runs 10 seconds too fast per day,
set the TIME ADJ to -10.
Range is -59 to +59 sec/day.
To change the “TIM ADJ”:
1. Enter the key code.
2. Press the “INS” button repeatedly until ‘TIM ADJ”
appears in the display.
3. Turn the knob until the desired time
adjustment appears in the display.
Automatic operation is resumed after 20 seconds.
Installation Entries 4
4 Installation Entries
16
FLUE GAS OFF
Flue Gas
The flue gas temperature can only be measured with an
additional module, not available in the United States.
The factory setting is “OFF”. This must remain in the off
position or an error message will appear.

Relay Test 5
19
Relay Test
You can use the relay test to test the switch relays in
the control panel. The following relays can be tested.
• Burner
• Domestic hot water circulator
• Heating circulator
To test the relays:
1. Enter the key code.
2. Press the “INS” button repeatedly until “RELAY” appears in
the display. The actual system status is shown in the
display.
3. Turn the knob. The flame symbol for the burner appears
first. The burner will come on at this point.
4. Turn the knob further.The symbols for the domestic hot
water circulator and heating circulator will appear and
start up the respective circulators.
The test has no time limit. To stop the test, press the
“INS” or “AUT” button.
RELAY
RELAY
RELAY
18
OFFSET 0.0
˚F
OFFSET
The “OFFSET” can be used when the actual room
temperature differs from the room temperature setting.
The “OFFSET” will raise or lower the room temperature
the amount of degrees set. The “OFFSET” performs a
parallel vertical shift to the heating curve. A 1°adjustment
for the “OFFSET” will result in a 3° adjustment in boiler
water temperature.
Heating curve adjustments:
If the room temperature is too low/high for all outside
temperatures, increase/decrease the “OFFSET”.
If the room temperature is too lowonlyduring moderate outside
temperatures, increase the “OFFSET” and decrease the “REF
TEMP” slightly. Make only small adjustments and allow ample
time for the system to respond.
To change the “OFFSET”:
1. Enter the key code.
2. Press the “INS”button repeatedly until “OFFSET”
appears in the display.
3. Turn the knob until the desired offset appears in
the display.
Automatic operation is resumed after 20 seconds.
Example: Desired room temperature: 65˚ F
Actual room temperature: 63˚ F
The “OFFSET” should be 2.0˚ F
4 Installation Entries

Relay Test 5
19
Relay Test
You can use the relay test to test the switch relays in
the control panel. The following relays can be tested.
• Burner
• Domestic hot water circulator
• Heating circulator
To test the relays:
1. Enter the key code.
2. Press the “INS” button repeatedly until “RELAY” appears in
the display. The actual system status is shown in the
display.
3. Turn the knob. The flame symbol for the burner appears
first. The burner will come on at this point.
4. Turn the knob further.The symbols for the domestic hot
water circulator and heating circulator will appear and
start up the respective circulators.
The test has no time limit. To stop the test, press the
“INS” or “AUT” button.
RELAY
RELAY
RELAY
18
OFFSET 0.0
˚F
OFFSET
The “OFFSET” can be used when the actual room
temperature differs from the room temperature setting.
The “OFFSET” will raise or lower the room temperature
the amount of degrees set. The “OFFSET” performs a
parallel vertical shift to the heating curve. A 1°adjustment
for the “OFFSET” will result in a 3° adjustment in boiler
water temperature.
Heating curve adjustments:
If the room temperature is too low/high for all outside
temperatures, increase/decrease the “OFFSET”.
If the room temperature is too lowonlyduring moderate outside
temperatures, increase the “OFFSET” and decrease the “REF
TEMP” slightly. Make only small adjustments and allow ample
time for the system to respond.
To change the “OFFSET”:
1. Enter the key code.
2. Press the “INS”button repeatedly until “OFFSET”
appears in the display.
3. Turn the knob until the desired offset appears in
the display.
Automatic operation is resumed after 20 seconds.
Example: Desired room temperature: 65˚ F
Actual room temperature: 63˚ F
The “OFFSET” should be 2.0˚ F
4 Installation Entries

LCD Test 7
21
LCD Test:
You can use the LCDTest to check whether all digits
and symbols are shown properly in their display.
1. Enter the key code.
2. Press the “INS” button repeatedly until
“LCD TEST” appears in the display.
3. Turn the knob. All digits and symbols must
appear correctly in the display. The display
is defective if it is not complete, and should
be replaced.
Automatic operation is resumed after
20 seconds.
1. Switch the control on
with the main power
switch (I Button).
2. Enter the key code
(See page 7)
3. Press the INS repeatedly until “RELAY”
appears in the display (See Fig. 1).
4. Turn the knob until the flame symbol
for the burner relay appears. The burner
will come on (See Fig. 2).
Heating pumps will not run during the
burner test. Allow the burner to run
until burner shuts off at the setpoint
on the aquastat dial.
5. Remove the black aquastat dial.
(See Fig. 3)
6. Push the green button in with a
screwdriver or similar instrument to
bypass the adjustable boiler aquastat.
Hold the green button until the STB,
manual reset high limit trips. This
happens at approximately 230°F
(See Fig. 4).
7. Run circulators to remove excess heat.
Then, to reset the STB, remove the
safety nut (See Fig. 5). Press in the reset
button underneath. This will return the
control back to normal operation.
To Resume Normal Operation:
Press the INS button or AUT button.
6 Testing the Manual Reset High Limit (STB)
20
RELAY
RELAY
Figure 1.
Figure 2.
Figure 3.
Figure 4.
Figure 5.
Aquastat Dial
Green Button
Safety Nut
180
C
C
Other manuals for HS 2102
2
Table of contents
Other Buderus Control System manuals
Popular Control System manuals by other brands

Radionics
Radionics D2212 installation manual

Lindsay
Lindsay Barrier Systems X-LITE installation manual

Rockford Fosgate
Rockford Fosgate SSC-500 installation manual

MacroAir Technologies
MacroAir Technologies Controller 4 Operation manual

WEIHONG
WEIHONG LS1500 manual

Politec
Politec ALES QUAD Series Installation and mounting guide

Techno CNC Systems
Techno CNC Systems BT1212 user manual

tbs electronics
tbs electronics H64 Installation instructions & user manual

Fröling
Fröling Lambdatronic SP 3200 Service manual

FoxAlien
FoxAlien Masuter Pro user manual

Crestron
Crestron 4 Series product manual

Bosch
Bosch rexroth IndraDrive Mi KMV03 instruction manual