Cairox S-TOUCH User manual

user manual

2 3
CAIROX
Name Description
Power supply 24 VDC
Way of control touch screen
Temperature adjustment range
+5 ÷ +45°C
Operating temperature range -10 ÷ +60°C
Temperature sensor built-in
Protection degree IP20
Installation on the wall
Casing ABS plastic, RAL 9003
Max. number of connected
units 31
Dimensions (HxWxD) 130 x 115 x 35 mm
S-TOUCH intelligent controller with touch screen enables
control all air curtains SOLANO.
Each unit must have its own individual address in S-ECM
control module.
Table of contents Technical data
General information
Technical data................................................................................................2
General information .................................................................................2
Installation........................................................................................................3
Navigation........................................................................................................3
First run...............................................................................................................4
Main screen .....................................................................................................6
Main menu ................................................................................................ 6
Time...............................................................................................................7
Date................................................................................................................7
Calendar......................................................................................................7
Language.................................................................................................10
Integrated units...................................................................................11
Reset...........................................................................................................11
Leading sensor.....................................................................................12
Control lock............................................................................................12
System information........................................................................... 13
BMS..............................................................................................................13
SOLANO air curtains ............................................................................14
SOLANO COMBI air curtain-fan heater combo units...16
Alarms...............................................................................................................20
SW
1
0
1 2 4 8 16 Y1

3
CAIROX
General information
S-TOUCH controller has a built-in sensor for measuring
air temperature in the room. To ensure proper measure-
ments, the controller should be installed at a height of
approx. 1.5 m above the ground in a place with good air
circulation. Do not place it near heat sources, lighting, air
inlets, windows and door openings, etc.
If temperature sensor was chosen in a S-TOUCH menu
as„installed in unit” (p.32), S-TOUCH controller can be
mounted out of area i.e. technical room.
BMS
GND
B A
SW1
RESET
SW1
T120
T-box
GND
B A VCC
max. 50 m
VCC
GND
A
T- box
B
DRV
min. LICY 4x0,5 mm2 screenedy
A and B braided wire pair
In the case, when S-TOUCH in BMS network is the last
device, SW1 switch should be set in T120 position.
return to previous screen with
save of changes
change of parameter value
change of unit group
return to previous screen without
save of changes
menu navigation
Installation
Navigation
1
3
2

4 5
CAIROX
First run
active language
Searching of connected units
Selection of language Setting of date
Setting of time
DevicesTime
DataLanguage
13PM
August
FR

5
CAIROX
Verify if all units have been
found. If not, check:
• correct connection of communication signal A-A, B-B,
• power supply of the unit,
• correct setting of addresses, each unit must have
dierent address,
• if in the last unit dip-switch SW2 is set in T120 position.
Setting of desired temperature.
12:55PM
Devices
SOLAN
Set individual addrress in S-ECM module for each unit.
DRV address
1
2
3
...
31
1 2 4 8 16 Y1

6 7
CAIROX
Main screen Main menu
long press turn on/off of the controller
long press main menu
short press units menu
alarms
setting of desired temperature
time
setting
date
setting
selection of
leading sensor
calendar
controller lock
language selection
integrated units
hardware
version
restore factory settings
BMS settings
desired temperature
measured temperature
date, time
settings lock active
BMS mode active
calendar active
calendar active – settings forced
Enter to the menu after entering the
password: 2014
long
press
4:05PM
12:55PM General settings
FR

7
CAIROX
Time Calendar
Date
Setting of time
Setting of date
• For each day you can set up to 20 on/o events,
• Start time of new event is also the end time of previous
event,
• For each event you can set any temperature for units, in
the range of 5 – 45oC,
• Events for each day can be set individually or can be
copied from day, which was already set.
Activation of calendar is signalized on main screen via
following icons:
There were ad hoc set other parameters than
the settings programmed in the calendar:
• desired temperature,
• system were OFF and was turned on (to turn
on the system press and hold for 2 s the
calendar icon on main screen),
• system were ON and was turned o (to turn
o the system press and hold for 2 s the
calendar icon on main screen).
Ad hoc settings stays as long as time of current
event in calendar. With start of next event,
units will operate according to programmed
settings.
calendar active – SYSTEM ON
calendar active – SYSTEM OFF
calendar active – settings forced.
Date
Time
13PM
August

8 9
CAIROX
Calendar – Adding the ON event
In given example SYSTEM will be turned on at 6:15 and
the units will maintain temp. 12oC.
SYSTEM WILL OPERATE USING CURRENT SETTINGS UNTIL
NEW EVENT WILL BE SET.
activation / deactivation of calendar
moving to the next day
adding the event
event – system ON
copying events on the following days
event – system OFF
removing the events
Calendar
Weekly programer
New task
Weekly programer
Monday
4:15AM
7:00AM
11:30PM
4:00PM 6:00PM Tue
7:00AM
9:00AM

9
CAIROX
Calendar – Copying events
day from which events will be copied
day selected for copying events from PN day
day with already programmed operation
schedule – you can also copy here the events
from PN day
day without programmed operation schedule
Calendar – Adding the OFF event
In given example units will be turned o at 16:00.
SYSTEM WILL BE TURNED OFF UNTIL THE NEXT EVENT,
ACCORDING TO CALENDAR SETTINGS.
Weekly programer
Copy
Weekly programer
New task
Mon ThuTue
SatFr
4:00PM Wed
Sun

10 11
CAIROX
Calendar – Removing events Language
events selected
to remove
conrmation of
events removal active language
Language
Weekly programer
Delete task
7:00AM
8:15PM
9:15AM9:00AM
10:00PM
4:00PM 4:15PM 7:00PM
FR

11
CAIROX
Integrated units Reset
searching for units integrated with system
active
unit
deactivated unit
– not operating
Restore default settings
Reset to default settings?
Yes No
Devices
long press displays the S-ECM software
SOLAN
System information
SOLANO01
CURTAIN MAIN
DRV-V 2.1
2.0.0-2d-G8B342117

12 13
CAIROX
The correction of sensor measurements is also possible.
Leading sensor
active temperature sensor
leading sensor is the sensor built
in S-TOUCH controller
leading sensor is the local sensor. When it is
selected, operation of each unit is regulated
locally
Temperature sensor
Controller lock
To activate the lock:
1. Set password
2. Conrm OK
Free 4-digit password can be set.
After returning to main screen and 30s of inactivity,
controller will be locked automatically.
Controller lock

13
CAIROX
System information
Information menu B M S – settings
Basic information about software and hardware version
ID – setting unit adress: from 1 to 247
BAUD – setting data transmission speed: from 9600 to
115200 bit/s
S-Touch 2.0.10
Compilation 2.0.15-2-gd25434f
14.10.2016

14 15
CAIROX
air ow setting – 3-steps
selection of operating mode
readings
setting of delay times
SOLANO air curtains
short
press
air curtain operates according to door sensor and
thermostat, whose priority is equivalent
heating – valve is opened when measured
temperature is lower than desired temperature
ventilation – valve is constantly closed, fan
operates continuously at selected step
air curtain operates according to door sensor and
thermostat. Door sensor has a priority. Without it’s
signal unit will not run
active operating mode
Operating modes
Operating mode
SOLANO
antifreeze
SOLANO
Settings
SOLAN

15
CAIROX
Fan switch o delay time – it can be set in the ran-
ge 0:00 - 10:00 minutes, every 0:30s. It is possible
to set ∞ value, then fan operates continuously.
Valve switch o delay time - it can be set in the
range 0:00 - 10:00 minutes, every 0:30s. It is possi-
ble to set ∞ value, then valve is constantly open.
Valve delay time must be shorter than fan delay
time.
Setting of delay time
Air ow setting
air ow setting
After the disappearance of signal from the door
sensor (or thermostat if K1 mode is activated), fan
of air curtain can operate on selected step for a
specied period of time or be turned o - select
OFF.
Delay time
Airow
SOLANO SOLANO

16 17
CAIROX
Readings
ON
To read temperatures near the unit, external temperature
sensors PT-1000 must be connected to S-ECM control
module.
air ow setting for air curtain part – 3-steps
air ow setting for fan heater part – 3-steps
selection of operating mode
readings
setting of delay times
SOLANO COMBI air curta-
in-fan heater combo units
short
press
Readings
SOLANO
ON/OFF valve
temperature in
the room
Antifreeze
Antifreeze protection of the heat exchanger. When tem-
perature in the room drops below desired temperature
fans stops and valve is open to 100%.
SOLANO
Antifreeze
SOLANO COMBI
Settings
antifreeze
COMBI

17
CAIROX
Fan heater operates always according to temperature set
on the controller, regardless K1/K2 mode.
air curtain operates according to door sensor and
thermostat, whose priority is equivalent
heating – valve is opened when measured
temperature is lower than desired temperature
ventilation – valve is constantly closed, fan
operates continuously at selected step
air curtain operates according to door sensor and
thermostat. Door sensor has a priority. Without
it’s signal unit will not run
active operating mode
Operating modes Air ow setting
air ow setting
After the disappearance of signal from the door
sensor (or thermostat if K1 mode is activated), fan
of air curtain can operate on selected step for a
specied period of time or be turned o – select
OFF.
AirowOperating mode
SOLANO COMBI SOLANO COMBI

18 19
CAIROX
air ow setting
After reaching desired temperature fan of the
heater can operate continously on selected step:
1, 2, 3 or be turned o – select OFF.
Fan switch o delay time can be set in the range
0:00–10:00 minutes, every 0:30s. Value ∞ – fan
operates continuously.
Valve switch o delay time can be set in the ran-
ge 0:00–10:00 minutes, every 0:30s. Value ∞
– valve is constantly open.
Setting of delay time
Delay timeAirow
SOLANO COMBI SOLANO COMBI

19
CAIROX
Readings
ON/OFF valve
temperature in the room
ON
To read temperatures near the unit, external temperature
sensors PT-1000 must be connected to S-ECM control
module.
Readings
SOLANO COMBI
Antifreeze
Antifreeze protection of the heat exchanger. When tem-
perature in the room drops below desired temperature
fans stops and valve is open to 100%.
SOLANO COMBI
Antifreeze

20 21
CAIROX
alarms
Alarms
• Real time clock error
set the S-TOUCH time again
• Internal temperature sensor errror
S-TOUCH built-in temperature sensor is
damagedx
• Temperature sensor T1/T2/T3/T4/T5
check temperature sensor
• Antifreeze water exchanger ON
antifreeze mode of water heat
exchanger is on
• S-ECM group error
Addressing failure. Check binary
address set in S-ECM and use search
button again
• Connect error
no communication between S-ECM
and S-TOUCH, check connection and
S-ECM power supply
List of alarms
• COMBI heater not connected
no communication between S-ECM
of fan heater part of SOLANO COMBI,
check connection between S-ECM
of air curtain part and S-ECM of fan
heater part
Alarms Alarms
SOLANO