7/7 User Instructions CAIROX CK AC / EC rev1 - 21/07/2022
4OPERATION
For technical data please see the product label. Before starting, make sure that:
•the current does not exceed more than +5% of what is stated on the label.
•the supplied voltage is within +6% to –10% of the rated voltage.
•no noise appears when starting the fan.
5MAINTENANCE
•Before service, maintenance, or repair, disconnect power and wait until the impeller has stopped.
•Attention, look out for sharp edges and corners.
•Consider the weight of the fan when removing or opening larger fans to avoid injury and damage.
•Attention! Temperatures up to 85°C can be present on the controller housing (only for EC motor).
•Waiting period of at least 3 minutes! (Only for EC motor) Because of internal capacitors, danger of death
exists even after switching off the device through directly touching the energized parts or due to parts
that have become energized due to faults. The controller housing may only be removed or opened when
the power line has been switched off and a period of three minutes has elapsed since switching it off.
•When cleaning and maintaining, the fan always must be secured when open, so it can’t fall down and
cause injury.
•The fan must be cleaned regularly, at least once a year to maintain the capacity and to avoid unbalance
which may cause unnecessary damage of the bearings.
•When cleaning the fan, high-pressure cleaning or strong dissolvent must not be used. Cleaning should be
done without displacing or damaging the impeller.
•The fan bearings are maintenance-free and should be replaced only when necessary.
•Notice the weight of the fan when closing after inspection/cleaning.
•Mount back all details in reverse order. Check that the fan is closed and locked before starting.
•Make sure that there is no noise from the fan.
6FAULT DETECTION
1. Make sure that the power is connected to the fan.
2. Disconnect the power and verify that the impeller is not blocked.
3. Check the thermal contact (for AC). If it is triggered the cause of overheating must be investigated and
taken care of. To restore the manual thermoprotector the power must be disconnected for a couple of
minutes. In case of automatic thermoprotector the resetting will be done automatically when the motor
has cooled down.
4. Make sure that the capacitor is connected according to the wiring diagram (for AC).
5. If the fan still does not work, the first thing to do is to replace the capacitor (for AC).
6. If the previous steps don’t solve the problem, contact your fan supplier.
7. If the fan is returned to the supplier, it must be cleaned, the motor cable must be undamaged, and a
detailed fault description must be enclosed.
7WARRANTY
The warranty is only valid under condition that the fan is used according to this “Directions for use” and a regular
maintenance has been made and record. The warrantor is responsible only for the operation if approved
accessories are used. The warranty does not cover product failures caused by accessories/equipment from other
manufacturers