Exhaust from Wet Area - Humid Air - Should be taken from as low as
practicable to inlet of dehumidifier unit. In many instances siting of dehumidifier
unit in hall or in adjacent rooms can eliminate use of ductwork to inlet.
Inlet/Return - Dry Air - Frequently requires overhead ducting wi suitable
grilles to give balance and direction of air flow.
The quantity of air flow handled by each dehumidifier unit is given on e data
sheet togeer wi e maximum pressure available from e fan to overcome
total ducting resistance to air flow, i.e. inlet, discharge ducting, grilles, filters and
where, installed air heater batteries.
Note:-
a. The humidity sensing tube situated by e air inlet is to be encompassed by
or extended to any inlet air ducting.
Refer to installation drawings.
b. All units have discharge ducting spigots as standard.
c. Inlet ducting spigots and or inlet air filters are available from stockists. Do not
drill into unit to fit spigots or filters.
d. Final connections to dehumidifier spigots must be made wi flexible ducting
(rubber or canvas) to eliminate transmission of vibration down any ducting
fitted.
e. Before any discharge ducting is attached remove e damper plate (if fitted)
from dehumidifier outlet or fan grille.
f. Aer completion of installation including all grilles, ductwork, etc., ensure at
e air flow rough e dehumidifier is as specified in e data sheet ± 10%.
If airflow is high, adjust e main system damper to obtain correct airflow. If
airflow is low or high, unit will not function correctly.
g. TABLE 1. Required Free Areas to provide air flow to and from dehumidifiers
when installed in an enclosed area or where required to pass air rough a wall,
etc.
Free area is e available area rough which air can pass, rough a
grille or louvres.
Model DH150 - minimum free area air inlet = 0·35 m².
Model DH300 - minimum free area air inlet = 0·57 m².
Model DH600 - minimum free area air inlet = 1·1 m².
Note: If multiple units are installed in an enclosed area en e inlet free areas
required for each unit can be added togeer to form one inlet aperture. BUT
discharge from each unit must be kept separate and must not be incorporated
into one common duct system, unless back dra flaps are installed in outlet
duct of each dehumidifier.
FIG. 4. CALOREX DEHUMIDIFIER
INSTALLED WITHIN SPACE TO BE
DEHUMIDIFIED, WITH TOP DISCHARGE
BOX OPTION AND FLEXIBLE DUCTING
FITTED.
8 SD208050 ISSUE 44
DH150/300/600 OWNER INSTALLATION MANUAL