Calorex DH150 Quick start guide

DH150/DH300/DH600
Owner installation manual (SD208050 issue 44)

2 SD208050 ISSUE 44
DH150/300/600 OWNER INSTALLATION MANUAL

Contents
HEATH AND SAFETY WARNING ..............................................4
1.0 WHAT ARE THE CALOREX
DEHUMIDIFIERS DESIGNED TO DO ?.....................................5
2.0 ORDERING PROCEDURE (MODEL DESIGNATION)........6
3.0 INSTALLATION .....................................................................6
3.1 SITING....................................................................................6
3.2 DUCTING...............................................................................7
3.4 ELECTRICAL (MACHINE WIRING AND SUPPLY).......... 10
4.0 CONTROLS AND INDICATION LAMPS........................... 12
5.0 DEHUMIDIFIER MALFUNCTION ..................................... 13
6.0 DEHUMIDIFIER TECHNICAL DATA SHEET .................... 14
7.0 INSTALLATION DRAWINGS............................................. 15
8.0 LOW PRESSURE HOT WATER (LPHW)
HEATER BATTERY OPTION.................................................... 18
9.0 DH150 WITH TOP DISCHARGE BOX OPTION .............. 19
10.0 DH600 WITH TOP DISCHARGE BOX OPTION............ 20
11.0 ELECTRICAL CIRCUIT DIAGRAMS............................... 21
12.0 WARRANTY CONDITIONS............................................. 29
13.0 MACHINE RECORD LOG................................................ 30
HEALTH AND SAFETY WARNING
As e dehumidifier embodies electrical and rotational equipment, ONLY competent persons
should carry out any work on is type of machine.
(SEE GUARANTEE)
3
SD208050 ISSUE 44

HEALTH AND SAFETY WARNING
This appliance can be used by children from eight years and above and persons wi reduced
physical, sensory or mental capabilities or lack of experience and knowledge if ey have been
given supervision or instruction concerning e use of e appliance in a safe way and understand
e hazards involved. Children should not play wi e appliance. Cleaning and maintenance shall
not be made by children wiout supervision.
Disconnect from e mains supply and wait ree minutes before removing panels and
commencing work on is machine.
HEATH AND SAFETY WARNING
4 SD208050 ISSUE 44
DH150/300/600 OWNER INSTALLATION MANUAL

Models DH150, DH300 & DH600 are designed to remove moisture from e
air and reject e latent heat of e dehumidification process back into e air.
Warm, humid air is drawn in rough e evaporator which extracts e latent
heat and at e same time dehumidifies e air by cooling it below its dew
point temperature. The condensed moisture forms on e evaporator coil and is
en drained to waste. The extracted heat is en upgraded to a much higher
temperature by e compressor and passes into e condenser coil. The cool,
drier air en passes over e condenser, collects e heat and passes back into
e room as warm, dry air.
Fig. 1.
1.0 WHAT ARE THE CALOREX DEHUMIDIFIERS DESIGNED TO DO?
5
SD208050 ISSUE 44

Great care should be exercised in following e installation procedure to ensure
at your Calorex dehumidifier performs as it was designed.
3.1 SITING
a. Ensure dehumidifier on site is as ordered, i.e. model, electrical supply and
factory fitted options.
b. Inspect unit for damage, in particular inspect e evaporator (finned side)
to ensure at it is undamaged. (Minor indentations in e fins do not affect
performance). If severely damaged, endorse delivery note in presence of e
driver and send a recorded delivery letter to transport company giving details.
c. Protect unit if installation is delayed.
d. Provide a firm level base capable of supporting operational weight of unit;
spread load if on timber floor.
e. Ensure water cannot collect under unit, recommend units are installed on
plins 100mm above finished floor level and to also aid condensate drainage.
f. Allow adequate clearance to service panels on unit; recommend 500mm
minimum (see installation drawings).
g. All Calorex dehumidifiers are by design as quiet as is practicable, however,
due consideration should be given to siting in order to fully exploit is feature,
i.e. orientate inlet/outlet parallel to occupied premises.
h. Ensure loose debris will not block air inlet filters or grilles.
2.0 ORDERING PROCEDURE (MODEL DESIGNATION)
High output fan to combat extended duct work. (DH300/DH600 only)
Remote control facilities.
S’ signifies so start kit fitted. To be used ONLY where local electricity boards demand lower
instantaneous starting amps and not to overcome a suspect supply line, ie low voltage.
X’ models ambient air temperatures down to 0ºC (DH150 only).
Y’ models ambient air temperatures down to -15ºC (DH300/600 only).
A = 230V ~1phN 50Hz (model 150 only).
B = 400V ~3phN 50Hz.
D = 208-230V ~1ph 60Hz (model 150 only).
E = 200-230V ~3ph 60Hz.
00 = R407c models design limitations are:
Max air on temperature = 35ºC.
DH = Dehumidifier wi heat reclaim to air.
3.0 INSTALLATION
EXAMPLE: DH 600 B Y S R F
6 SD208050 ISSUE 44
DH150/300/600 OWNER INSTALLATION MANUAL

IMPORTANT:
As dehumidifier units are handling air at dehumidified space
temperatures, ey must be sited in a similar environment, or insulated
plenum. They must not be sited in colder areas, i.e. subject to ambient
air.
3.2 DUCTING
(SEE FIGS 3, 4, 5 AND 6)
In order at moisture can be removed and humidity control can be effected
wiin e required area, it is essential at correct air movement and
distribution is achieved. The Calorex unit must extract e humid air generated
and discharge e drier air to areas which are subject to condensation problems
(windows, etc.) and or comfort zones, etc.
This can oen be achieved by use of ducting and correct application of grilles/
louvres to effect air distribution and movement to ese areas.
NOTE:- dehumidifier unit and ducting will be at higher temperature and will
require insulation if exposed to lower air temperatures, for instance, if e
ducting were to pass rough an un-heated lo space.
SITING CONT’
Fig. 2. Calorex Dehumidifier installed wiin
space to be dehumidified, wi top discharge
box option fitted.
Fig. 3. Calorex Dehumidifier installed wiin
space to be dehumidified, wi discharge ducting
fitted.
7
SD208050 ISSUE 44

Exhaust from Wet Area - Humid Air - Should be taken from as low as
practicable to inlet of dehumidifier unit. In many instances siting of dehumidifier
unit in hall or in adjacent rooms can eliminate use of ductwork to inlet.
Inlet/Return - Dry Air - Frequently requires overhead ducting wi suitable
grilles to give balance and direction of air flow.
The quantity of air flow handled by each dehumidifier unit is given on e data
sheet togeer wi e maximum pressure available from e fan to overcome
total ducting resistance to air flow, i.e. inlet, discharge ducting, grilles, filters and
where, installed air heater batteries.
Note:-
a. The humidity sensing tube situated by e air inlet is to be encompassed by
or extended to any inlet air ducting.
Refer to installation drawings.
b. All units have discharge ducting spigots as standard.
c. Inlet ducting spigots and or inlet air filters are available from stockists. Do not
drill into unit to fit spigots or filters.
d. Final connections to dehumidifier spigots must be made wi flexible ducting
(rubber or canvas) to eliminate transmission of vibration down any ducting
fitted.
e. Before any discharge ducting is attached remove e damper plate (if fitted)
from dehumidifier outlet or fan grille.
f. Aer completion of installation including all grilles, ductwork, etc., ensure at
e air flow rough e dehumidifier is as specified in e data sheet ± 10%.
If airflow is high, adjust e main system damper to obtain correct airflow. If
airflow is low or high, unit will not function correctly.
g. TABLE 1. Required Free Areas to provide air flow to and from dehumidifiers
when installed in an enclosed area or where required to pass air rough a wall,
etc.
Free area is e available area rough which air can pass, rough a
grille or louvres.
Model DH150 - minimum free area air inlet = 0·35 m².
Model DH300 - minimum free area air inlet = 0·57 m².
Model DH600 - minimum free area air inlet = 1·1 m².
Note: If multiple units are installed in an enclosed area en e inlet free areas
required for each unit can be added togeer to form one inlet aperture. BUT
discharge from each unit must be kept separate and must not be incorporated
into one common duct system, unless back dra flaps are installed in outlet
duct of each dehumidifier.
FIG. 4. CALOREX DEHUMIDIFIER
INSTALLED WITHIN SPACE TO BE
DEHUMIDIFIED, WITH TOP DISCHARGE
BOX OPTION AND FLEXIBLE DUCTING
FITTED.
8 SD208050 ISSUE 44
DH150/300/600 OWNER INSTALLATION MANUAL

a. The condensate drain at e base of e unit collects e condensation
from e evaporator fins. It is erefore necessary to ensure at e
Calorex dehumidifier is placed on a level plin so at e condensate
water can run away and not overflow e edges of e drip tray inside e
dehumidifier.
Calorex dehumidifiers have condensate water outlet connections as follows:
DH150 = 22mm push fit domestic waste system.
DH300 = ¾” BSPM stub.
DH600 = 1½” BSPM stub.
FIG. 5. CALOREX DEHUMIDIFIER INSTALLED IN PLENUM
CHAMBER, WITH TOP DISCHARGE DUCTING FITTED.
Moist Air
Dry Air
MAXIMUM LIFT 8m
DH150
MAXIMUM LIFT 3m
DH300/600
3.3 PLUMBING
Fig. 6. Calorex Dehumidifier wi Condensate Pump Option fitted.
For applications where e condensate cannot be run to waste due to e
dehumidifier being lower an e waste pipe outlet, a condensate pump
option can be supplied. (Located internally on e DH150, DH300 and DH600
models).
9
SD208050 ISSUE 44

a. To be in accordance wi I.E.E. standards, latest issue, or local codes of
practice as applicable.
b. Protected supply to incorporate fuses or motor rated circuit breakers to
specified rating, (see Data Sheet). H.R.C. fuses are recommended. An isolator
which disconnects all poles must be fitted adjacent to e dehumidifier.
c. All units must be correctly eared/grounded. An ear leakage trip of e
current operating type is recommended to be fitted to all electrics. (If a heater
box is fitted, e same R.C.D. (residual current device) must feed bo supplies.
d. IMPORTANT:- Inconsistent Electrical Supply.
The following Iimits of operation list not be exceeded if Calorex dehumidifiers
are to be guaranteed eier in performance or warranty terms:
N.B. This voltage must be available at e dehumidifier whilst it is running under
full load.
The dehumidifier should be installed in accordance wi EMC2004/108/EC.
Note: DH300 & DH600 dehumidifiers are fitted wi a phase protection
relay and will not run if e phases are not connected in correct order (phase
sequence) or if e supply voltage is 15% less an e nominal voltage. (415V
for 3~N 50Hz). The lamp on e phase rotation relay, situated in e electric
box, is illuminated when e phases are correctly connected and e voltage is
sucient.
FIG.7. DH150, LOCATION OF MACHINE SUPPLY TERMINAL BLOCKS
Access to heater box
terminals (When heater
kit fitted)
Remove
service panels
(six screws)
Top discharge box
(If fitted)
Mains in
terminal block
and earing point
Remove
service panels
(¼ turn
fasteners)
Mains supply in
3.4 ELECTRICAL (MACHINE WIRING AND SUPPLY)
Voltage Minimum Maximum
Single phase machines (A) 207V 353V
Three phase machines (B) 360V 440V
Frequency 47.5Hz 52.5Hz
10 SD208050 ISSUE 44
DH150/300/600 OWNER INSTALLATION MANUAL

FIG.8. DH300/600, LOCATION OF MACHINE SUPPLY TERMINAL BLOCKS
So
start
Pool pump
interlock or
flow switch
NL1 L2 L3
12 3 4 5 6 7 8 9
DH300/600
Mains Terminal Block
and Earing Point
Mains
supply in
Remove front
service panel
(¼ turn
fasteners)
11
SD208050 ISSUE 44

External Control Console.
a. MAINS LAMP - RED - Illuminates whenever e electrical supply to e
dehumidifier is on.
b. FAULT LAMP - AMBER - Illuminates if e internal limit switches detect a
problem, or if e external interlock facility is open circuit.
c. DEFROST - WHITE - Illuminates whenever e dehumidifier is in defrost
mode, is will happen at lower air temperatures and is not a fault condition,
e dehumidifier will revert to normal run automatically when e defrost cycle
is complete.
d. ON/OFF SWITCH - This will only be found on DH150 models and should
always be used if for some reason e dehumidifier is not required to be
running or prior to isolating e dehumidifier from e mains electrical supply.
e. STANDBY SWITCH - This will only be found on DH300/600 models and
must always be used if for some reason e dehumidifier is not required to be
running or prior to isolating e dehumidifier from e mains electrical supply.
IMPORTANT - On initial start up or if e mains electrical supply has been
interrupted for any leng of time (greater an 1 hour), en e standby
switch must be set to “standby” before e mains electrical supply is
reinstated, e dehumidifier must be le in is condition for 12 hours before
normal run is selected on e standby switch.
Internal Controls.
f. An adjustable internal humidistat effects control of humidity. Range 20/80%.
A normal setting is 60% for achieving comfortable conditions and minimising
condensation. (20% setting will remove more moisture from e dehumidified
space an a 80% setting).
g. An adjustable ermostat effects control of e air temperature and should be
set to e maximum desired air temperature for e dehumidified space.
h. Fan mode switch. This gives e user e option of having e fan cycle
under control of e humidistat (wi e compressor), or e fan can run
continuously which will promote better air circulation which again helps to
reduce condensation by preventing stagnant air pockets.
i. If e Turning Hood Top Box Heater assembly option is fitted, en e
adjustable air temperature ermostat control, located on e side of e Top
Box Heater assembly should be set to e desired minimum air temperature
required.
4.0 CONTROLS AND INDICATION LAMPS
12 SD208050 ISSUE 44
DH150/300/600 OWNER INSTALLATION MANUAL

5.0 DEHUMIDIFIER MALFUNCTION
WARNING : ISOLATE DEHUMIDIFIER ELECTRICALLY BEFORE
ENTERING OR REMOVING PANELS.
The user check list should be carried out by a competent electrician before
initiating a service call.
Do not attempt to interfere wi any internal control settings as ese have
been factory calibrated and sealed.
If in doubt or if advice is required contact e Danerm Group UK Service
Department : Phone +44(0)1621 857171 or +44(0)1621 856611. Fax
+44(0)1621 850871.
Any sign of abnormal operation, such as water dripping should be reported immediately to an installer or Danerm Ltd.
USER CHECK LIST
FAN AND COMPRESSOR BOTH OFF
LAMP TYPE LAMP COLOUR LAMP STATE ACTION
MAINS RED OFF Check at e electrical supply and supply fuse (or MCB) to
e dehumidifier are healy and switched on.
FAULT AMBER OFF
DEFROST WHITE OFF Check at e on/off rocker switch is "ON" (DH150 only).
ON/OFF RED OFF
MAINS RED ON Check control MCB is on (DH300/600 ree phase machines
only)
FAULT AMBER OFF
DEFROST WHITE OFF
ON/OFF RED OFF
FAN ON, COMPRESSOR OFF
LAMP TYPE LAMP COLOUR LAMP STATE ACTION
MAINS RED ON Check humidistat is calling for e dehumidifier to run and
at e air temperature ermostat is not exceeded.
FAULT AMBER OFF
DEFROST WHITE OFF Check internal fuses/overloads. Check "Standby" switch "ON"
(if fitted).
ON/OFF RED ON
LAMP TYPE LAMP COLOUR LAMP STATE ACTION
MAINS RED ON Check air flows are not restricted. Re-set HP switch on
DH300 & DH600.
FAULT AMBER ON Check ermal cut out on so start and heater hood if fitted.
DEFROST WHITE OFF Check fan for correct rotation (DH300/600).
ON/OFF RED ON
LAMP TYPE LAMP COLOUR. LAMP STATE. ACTION
MAINS RED ON Check at e air temperature is above 0ºC for DH150s, and
above -15ºC for DH300/600.
FAULT AMBER OFF
DEFROST WHITE ON Note :- It is acceptable for e dehumidifier to cycle on e
defrost light once per hour at low air temperatures.
ON/OFF RED ON
13
SD208050 ISSUE 44

6.0 DEHUMIDIFIER TECHNICAL DATA SHEET
MODEL NUMBER 1Ø DH150AX N/A N/A
3Ø DH150BX DH300BL(Y) DH600BY
PERFORMANCE DATA
Dehumidification Rate L/h 6·25 12·5 25
Output to Air Nett (DH model) kW 5·5 15·5 25
Total Electrical Input (STD fan) kW 2·3 6·7 10·0
Total Electrical Input ("F" Fan) kW N/A 7·3 10·4
ELECTRICAL DATA
Supply Details 1Ø 230V~1N 50Hz N/A N/A
Supply Details 3Ø |--------------------- 400V ~3N 50Hz ----------------------------|
Fan Option Type STD "F"
Maximum Supply Fuse 1Ø amps 32 N/A N/A N/A
Maximum Supply Fuse 3Ø amps 16 32 35 35
Maximum Running Amps 1Ø amps 23.3 N/A N/A N/A
Maximum Running Amps 3Ø amps 10.2 19.4 26 27
Starting Current Amps 1Ø STD amps 62 N/A N/A
Starting Current Amps 1Ø "S" amps 28 N/A N/A
Starting Current Amps 3Ø STD amps 30.5 66 135
Starting Current Amps 3Ø "S" amps 19 29 55
AIR HEATER OPTION
If Turning Hood wi Heater Fitted
Separate Supply for heaters
Maximum Power Output kW 9 N/A N/A
Maximum Full Load Amps 1Ø amps 36 N/A N/A
Maximum Full Load Amps 3Ø amps 12 N/A N/A
Maximum Supply Fuse 1Ø amps 50 N/A N/A
Maximum Supply Fuse 3Ø amps 16 N/A N/A
AIR FLOW DATA
Air Flow Nominal m³/h 2500 5000 9000
Ducting Design Static Pressure STD Pa N/A 60 80
*Ducting Max Static Pressure Pa 0-200 - -
Ducting Max' Static Pressure "F" M/C Pa N/A 140 160
If Turning Hood wi Heater fitted:
Ducting Design Static Pressure STD M/C Pa N/A N/A 0
* Ducting Max Static Pressure Pa 0-170 - -
Ducting Max Design Static Pressure "F" Pa N/A N/A 80
WATER FLOW DATA
Condensate Water Connection Size ¾"Domestic Waste 1½"BSPM 1½"BSPM
PHYSICAL DATA
Wid (unpacked) mm 660 980 1730
Dep (unpacked) mm 660 720 1250
Height (unpacked) mm 1313 1435 1600
Weight (unpacked) kg 130 220 497
MISC' DATA
Hermetic System
Refrigeration charge R407c (STD DH) kg 2·5 9.5 14
Refrigeration charge R407c (DH300BLY) kg 10
Sound Pressure at 3m db(A) 58 66 63
NOTES:-
1) Performance data based on air at 20ºC, 75%RH (Water at 26ºC).
2) Weight and dimensions nett.
3) Allow 500mm clearance to service panels.
4) Minimum air temperature 0ºC for "X" models and -15ºC for "Y" models.
5) Danerm Ltd. reserves e right to change or modify models wiout prior notice.
6) R407c Global Warming Potential (GWP) 1774
*DH150 features a Control Flow fan at 2500m3/h
14 SD208050 ISSUE 44
DH150/300/600 OWNER INSTALLATION MANUAL

7.0 INSTALLATION DRAWINGS
DH150 DEHUMIDIFIER.
NOTE:- Dimensions marked * refer to dimensions of inlet DUCT FLANGE KIT OPTION (50mm Deep).
100 510
557
50
1262
51
Mains
inlet
Front
service
panel
50
186
660
152 355
660
Air
outlet
Service panel
Front
service
panel
Top view
268
See note at foot of page
WATER IN
(DHW MODEL ONLY)
DISCHARGE
LIQUID
A/C RCU
MODELS
ONLY
139
190
524
129
156
197
645 50
WATER OUT
Drain
L H side
*
280
940 265
75* 720*
Optional
air
outlet
Rear view
Air inlet
Air
sampling
point
527
517
15
SD208050 ISSUE 44

DH150 DEHUMIDIFIER - WHEELS AND HANDLES OPTION (DH150BX ONLY)
660
934
1087
55
74 720
251
330
Drain
100 510
660
152 355
1252 50
Front
service
panel
Front view
Optional air
outlet
935 266
Air
inlet
Air
sampling
point
Rear
view
152 355
197 266
660
660
Air
outlet
Top view
NOTE:- Dimensions marked * refer to dimensions of inlet DUCT FLANGE KIT OPTION (50mm Deep).
16 SD208050 ISSUE 44
DH150/300/600 OWNER INSTALLATION MANUAL

DH600 DEHUMIDIFIER.
DH300 DEHUMIDIFIER.
680
613 475
256 547
980
AIR INLET
SERVICE PANEL
DISPLAY CONSOLE
*740
AIR OFF
SERVICE PANEL
SERVICE PANEL
238 423
20
369
980
640
1435
*775
NOTES :- Dimensions marked * refer to dimensions of INLET DUCT FLANGE KIT OPTION (50mm Deep).
‡ When e condensate pump is fitted service access may be necessary.
126‡ 110
AIR OFF
40
700
DRAIN
SERVICE
PANEL
1475
1020
1050
1240
100
700 *810
1730
842
SERVICE CONTROL
PANEL
*1380
1542
1600
295496
95
FRONT VIEW
AIR INLET
AIR
SAMPLING
POINT
REAR VIEW
576.5 570
732 496
OPTIONAL
AIR OUTLET
605
188
MAINS
INLET
100
AIR
OUTLET
SERVICE
PANEL
FRONT SERVICE PANEL
SERVICE
PANEL
OPTIONAL FRONT
ACCESS FILTER /DUCT
FLANGE KIT
DRAIN
NOTE: Dimensions marked * refer to dimensions of inlet DUCT FLANGE KIT OPTION (50mm DEEP)
Dimensions are e same for FRONT ACCESS FILTER KIT.
THE ALTERNATIVE SIDE ACCESS FILTER KIT IS 157mm DEEP.
TOP VIEW
OPTIONAL SIDE
ACCESS FILTER KIT
17
SD208050 ISSUE 44

8.0 LOW PRESSURE HOT WATER (LPHW) HEATER BATTERY OPTION
For use wi Calorex DH150 Dehumidifier only - available from your Danerm Ltd. Distributor.
MODEL LPHW580
Output (Water at 80ºC, Air at 30ºC) kW 18
Water Connections mm 22mm Stubs
Water Pressure Drop psig 0.5
Water Flow L/min 23
Water Volume litres 2.5
Air Pressure Drop mmWG 2.5
Air Off Temperature °C 50
Dimensions: "A" mm 650
"B" mm 620
"C" mm 250
"D" mm 50
"E" mm 500
"F" mm 540
"G" mm 60
1560
Front
DH150 wi LPHW 580
A B
C
D
F
E
GG
Water inWater out
Front
18 SD208050 ISSUE 44
DH150/300/600 OWNER INSTALLATION MANUAL

9.0 DH150 WITH TOP DISCHARGE BOX OPTION
WITH OR WITHOUT 9KW HEATER OPTION.
Adjustable deflector
grille on one or four
sides as required
Le hand side
110
Heater kit and
ermostat
(if fitted)
12", or 8", or 16"
spigots on one or four
sides as required
Rear view
Air inlet
DIA 8" or
12" or 16"
100 520 100
Front
service
panel
1262 605
Top view
Air
outlet Service panel
660
660
Service panel
70 520
50.00 520
Reset
button
19
SD208050 ISSUE 44

10.0 DH600 WITH TOP DISCHARGE BOX OPTION
1550.00
SERVICE CONTROL PANEL
965.00
FRONT VIEW
AIR INLET
L.H.SIDE
NOTE. 4 LOCKABLE
CASTORS AVAILABLE AS
OPTIONAL EXTRA
ADJUSTABLE DEFLECTOR
GRILLE ON ONE OR FOUR
SIDES AS REQUIRED
1060.00
TOP VIEW
AIR
OULTET
SERVICE
PANEL SERVICE
PANEL
1730.00
750.00128.00
490.00
FRONT SERVICE PANEL
REAR VIEW
12" OR
8" DIA
100.00 100.00
12" OR 8"
SPIGOTS ON ONE
OR FOUR SIDES
AS REQUIRED
750.00
20 SD208050 ISSUE 44