4. Installation
lThe SDM-CD16AC must be installed in an enclosure that provides a pollution degree 2
environment (normally, only nonconductive pollution; however, a temporary conductivity
caused by condensation may be expected). All Campbell Scientific enclosures meet this
requirement.
lUse copper conductors only.
lWire Range: 30 – 14 AWG
lTightening Torque: 5 – 7 in/lb
lUse minimum 60/75 °C wire.
lInput power must be connected to a class 2 supply only. All Campbell Scientific power
supplies meet the class 2 supply requirements.
CAUTION:
Cables connecting the data logger and SDM device should be kept as short as possible to
minimize the risk of corruption of the signals and damage from induced surges. Where long
cable runs (>3m) are unavoidable and the cables run outside, some extra protection may be
required for the SDM control ports. Please contact Campbell Scientific for further advice.
When connecting wires to the SDM signal ports, please ensure they are at ground potential
before making the connection by touching them to the earth terminal.
For data logger connections, see Table 4-1 (p. 5).
Multiple SDM-CD16ACs may be wired in parallel by connecting the data logger side of one
SDM-CD16AC to the next. The CABLE5CBL-L or an equivalent cable is used to connect the
module to the data logger. A 0.3m (1ft) cable length should be sufficient when both data logger
and SDM-CD16AC are housed within an ENC12/14; a 0.6m (2ft) length may be required if the
data logger and SDM-CD16AC are housed at opposite ends of an EN16/18 enclosure.
CRBasic data loggers should use the SDMSpeed() instruction if the cable length is longer than
6m (20ft).
NOTE:
SDM cables in noisy environments need to be suitably shielded.
SDM-CD16AC 16 Channel AC/DC Controller 4