Canalta Combustex BMS-2000 User manual

The Combustex BMS-2000
OPERATIONS MANUAL
OPERATION CONFIGURATION CALIBRATION INSTALLATION
B149.3 Compliant Burner Mangagement System
BMS Software Version 5.03

Phone: 403.342.4494 |Web: www.combustex.com
For operational, technical or installation assistance, please contact us.
QUALITY, RELIABILITY, PERFORMANCE
With Control Comes Safety
The BMS-2000 Burner Management System gives you the automated control to safely start,
monitor and manage a single or dual burner gas-red industrial heater.
• Calibrate, tune and congure more than 60 parameters and variables via the front keypad.
• Maintain system security through password protection.
• Access a wide selection of sequencing, monitoring and control information through easy page scrolling
on the heated, back-lit display.
• Gain exibility with remote and local start / shutdown / set point capabilities.
• Take control of shutdowns with rst out annunciation and a direct readout of shutdown conditions.
With the BMS-2000, You Have Exceptional Control
Call Us Toll Free: 1-855-226-2582
ANSI Z21.20 - 2007
CSA C22.2 No. 199 - B149.3 Compliant
CSA 22.2 No. 213 - M1987
UL 1998
UL 372
Class 1, Div. 2 Groups B, C and D Haz. Loc.
Temp. Code T4
NEMA Type 4x
Standards & Certications
4003497

The Combustex BMS-2000
Burner Management System
OPERATIONS MANUAL
Controller Version 5.03
Phone: 403.342.4494 |Web: www.canaltaow.com
For operational, technical or installation assistance, please contact us.
WARNINGS
Combustex recommends that this manual be read thoroughly before
attempting installation or operation of the BMS-2000. SAFETY FIRST.
Call Us Toll Free: 1-855-226-2582
-- WARNING --
THIS EQUIPMENT IS SUITABLE FOR USE IN CLASS 1, DIVISION 2 GROUPS B, C, D OR
NON-HAZARDOUS LOCATIONS ONLY.
-- WARNING --
EXPLOSION HAZARD - DO NOT DISCONECT EQUIPMENT WHILE CIRCUIT IS LIVE
UNLESS AREA IS KNOWN TO BE NON-HAZARDOUS
-- WARNING --
EXPLOSION HAZARD - SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY
FOR CLASS 1, DIVISION 2 LOCATIONS.
-- AVERTISSEMENT --
RISQUE D’EXPLOSION - LA SUBSTITUTION DE COMPOSANTS PEUT RENDRE CE
MATERIEL INACCEPTABLE POUR LES EMPLACEMENTS DE CLASSE 1, DIVISION 2.
-- ADVERTENCIA --
PELIGRO DE EXPLOSION - LA SUSTITUCION DE LOS COMPONENTES PUEDE
AFECTAR LA COMPATIBILIDAD PARA CLASE 1, LOCALIZACION DE DIVISION 2

2of 42
Combustex BMS-2000 [5.03] Operations Manual
Phone: 403.342.4494 |Web: www.canaltaow.com
For operational, technical or installation assistance, please contact us.
Call Us Toll Free: 1-855-226-2582
CONTENTS
1. INTRODUCTION
1.1 Overview
1.2 Burner Sequencing
1.3 ESD (Emergency Shutdown) Capabilities
1.4 Temperature Control
1.5 Features
1.6 Communications
1.7 Denitions of Common Terms and Abbreviations
1.8 Technical Specications
2. OPERATION
2.1 Overview
2.2 Passwords - Gaining Entry
2.3 Sequence Status & Shutdown Annunciation
2.4 Temperature Control
2.5 Output Status
2.6 Auxiliary Analog Inputs and Shutdowns
2.7 PID & Control Parameters
3. CONFIGURATION OF THE BMS-2000
3.1 Overview
3.2 Conguration Menu Options
4. CALIBRATION OF THE BMS-2000
4.1 Overview
4.2 Calibration Menu Items
4.3 Thermocouple / mV Reference Chart
5. INSTALLATION
5.1 Overview
5.2 Analog Input Connections
5.3 Digital Input Connections
5.4 Analog Output Connections
5.5 Digital Output Connections
5.6 Modbus Connections
5.7 Sample P&ID Drawings & Wiring Diagrams
6. TROUBLESHOOTING SHUTDOWN CONDITIONS
6.1 Error Messages and Shutdown Conditions
3
4
4
5
5
6
6
6
7
9
10
12
13
13
14
15
16
25
26
27
28
29
29
30
30
30
31
37

3of 42
Combustex BMS-2000 [5.03] Operations Manual - 1. INTRODUCTION
Phone: 403.342.4494 |Web: www.canaltaow.com
For operational, technical or installation assistance, please contact us.
Call Us Toll Free: 1-855-226-2582
INTRODUCTION
1.1 OVERVIEW
The Combustex BMS-2000 Burner Management System has been designed to be compatible with a wide
variety of industrial and oileld burner vessels. A common vessel will have a main burner ring into a re
tube which, in turn, heats a uid (often glycol). This uid is referred to as the “Bath”. Another uid (oil or
gas) is routed through the bath to be heated. This is referred to as the“Process”.
The BMS will control up to two pilots and two main burners, handle temperature control of the bath, and
provide ame status outputs and a variety of ESD (emergency shutdown) inputs.
The BMS-2000 is typically installed together with a Pilot Pro™ Series Ignition Assembly. These igniters
are designed and built around the features of the BMS, allowing the BMS to light and maintain a pilot
ame using the sensor that is incorporated into the pilot ignition module, providing ame verication.
The Combustex BMS-2000 is suitable for both new installations and retrotting older vessels, and is not
limited to Pilot Pro™ igniters.

4of 42
Combustex BMS-2000 [5.03] Operations Manual - 1. INTRODUCTION
Phone: 403.342.4494 |Web: www.canaltaow.com
For operational, technical or installation assistance, please contact us.
Call Us Toll Free: 1-855-226-2582
1.3 EMERGENCY SHUTDOWN CAPABILITIES
The BMS-2000 can be congured to shut down when an unsafe or out-of-control condition exists.
1. Programmable HTSD limits on:
• Bath Thermocouple Input
• Process Thermocouple Input
• Stack Thermocouple Input
2. Standard dedicated discrete eld device inputs preset at the factory:
• Remote Stop
• Remote Start
• Low Voltage
• Burner #1 Flame Sensor Failure
• Burner #1 Flame Failure to Relight
• Burner #1 Fuel Gas Low Pressure
• Burner #1 Fuel Gas High Pressure
• Aux. High Bath Temp. (Contact)
• Low Bath Level
• Burner #1 Main Valve Proof of Closure
3. Additional inputs for Dual Burner Systems:
• Burner #2 Flame Sensor Failure
• Burner #2 Flame Failure to Relight
• Burner #2 Fuel Gas Low Pressure
• Burner #2 Fuel Gas High Pressure
• Burner #2 Main Valve Proof of Closure
1.2 BURNER SEQUENCING
When initiating a start sequence, the BMS will open the pilot and energize the igniter for the trial for
ignition period and wait for the ame sensor to conrm a ame. Upon ame verication, the unit will
then go into “Normal Operation”. At this point, the BMS will energize the main burner and the ame
status output(s). The temperature control option will also become enabled (if congured).
Set points and the associated password protected timers are congurable in the BMS menu. Other
congurable options:
• Purge and Pre-purge
• Auto Relight on Flame Fail
• Auto Relight on Power Fail (unit will relight when power is restored)

5of 42
Combustex BMS-2000 [5.03] Operations Manual - 1. INTRODUCTION
Phone: 403.342.4494 |Web: www.canaltaow.com
For operational, technical or installation assistance, please contact us.
Call Us Toll Free: 1-855-226-2582
1.5 FEATURES
Automatic Sequencing Features
• LCD backlight, which can be set to ON, OFF, AUTO (with photocell) or TIMED.
• LCD heater, which automatically turns on at -10°C (14°F) to maintain display stability.
• Available computer interface via RS232 or RS485 Modbus protocol.
• Input ltering to help alleviate noisy signals and signal spikes.
• Capable of driving latching solenoids (separate latch and unlatch outputs).
• Single or dual burner control (selectable in series or parallel).
• Auto relight sequence can be de-selected or selected with up to three relight attempts after loss of
ame.
• Congurable pre- and post-purge times and auxiliary blower with conrmation.
• Congurable ame sensor options.
• Ignition output signal can be congured as steady or pulsed.
• Wide variety of congurable safety interlock devices (factory set to standard settings).
• Remote start / stop is congurable.
• Auto startup after power failure is congurable.
• Intermittent pilot or standing pilot is congurable.
• Remote indication of temperatures via 4-20 mA output.
• Remote set point of bath available via 4-20 mA input.
• Conguration is password protected and stored in non-volatile memory.
Shutdown Annunciation Features
• A rst out annunciation is built in with direct readout of the shutdown conditions. Each shutdown
condition is marked with its chronological incoming position. The operator must acknowledge
each shutdown condition and the condition must be cleared before startup can be initiated.
1.4 TEMPERATURE CONTROL
The BMS-2000 can be congured to perform bath temperature control by a Proportional or ON/OFF
Control output.
Proportional Control:
One 4-20mA output will be used. Set point and PID parameters are congurable via the BMS-2000
keypad.
ON/OFF Control:
The main #1 (and main #2, if applicable) burner will be cycled on and o to maintain set point. The
ON/OFF dead band and set point is adjustable via the BMS-2000 keypad.

6of 42
Combustex BMS-2000 [5.03] Operations Manual - 1. INTRODUCTION
Phone: 403.342.4494 |Web: www.canaltaow.com
For operational, technical or installation assistance, please contact us.
Call Us Toll Free: 1-855-226-2582
1.8 TECHNICAL SPECIFICATIONS
Rating CSA Class 1, Div. 2; Class 1, Div. 1 (pending); Intrinsically Safe; Nema 4x; B149.3 Compliant
Enclosure Dimensions 10.5” H, 8.5”W, 6” D
Enclosure Construction Molded Fiberglass Polyester with Quick Release Latches
Operating Temperature - 40°C to + 40°C (-40°F to +104°F)
Inputs (12) Digital Solid State; (2) Analog 4-20mA;
(5) Thermocouple Type K Underground Cold Junction Compensated
Outputs (16) 12-30 VDC Digital Solid State Optical Isolated (1.5A each)
(2) Analog 4-20mA 500 Ohm (max.)
Power Supply 12 to 30 VDC Clean Filtered
Current Draw
80 mA (min), 160 mA (typical), 300 mA (max) for Electronics + LCD Backlight + Display
Heater. Current draw of solenoids and other devices driven by BMS will have to be
added to above to calculate total. Total current draw not to exceed 3A.
Display Low Temp. Heated LCD
Mounting Wall Mount Bracket Standard; 2”Pipe Mount Optional
Communication Digital, Analog and Modbus
1.7 DEFINITIONS AND ABBREVIATIONS
Dead Band The allowed deviation from set point (while in ON/OFF Control)
DI Discrete Input
ESD Emergency Shutdown
HTSD High Temperature Shutdown
LCD Liquid Crystal Display
PID Proportional, Integral (Reset), Derivative (Rate)
PV Process Variable (Actual Temperature)
SD or S/D Shutdown
SP Set Point (Desired Temperature)
1.6 COMMUNICATIONS
The Combustex BMS-2000 includes both analog (9 total) and digital (28 total) connections for
communication between the BMS controller and various combustion system monitoring and control
devices. In addition, the BMS oers Modbus connectivity for fast, robust communication between the
BMS unit and remote controllers and readout devices. Modbus protocols RS232 and RS485 can be used
to remotely monitor and congure a select list of settings and status readouts. This functionality is
available in both single and dual-burner versions of the Combustex BMS-2000.

7of 42
Combustex BMS-2000 [5.03] Operations Manual - 2. OPERATION
Phone: 403.342.4494 |Web: www.canaltaow.com
For operational, technical or installation assistance, please contact us.
Call Us Toll Free: 1-855-226-2582
Start Key
Stop Key
LCD Display
Configuration Key
Calibration Key
Auto Backlight Sensor
Acknowledge Key
Page Scroll Key
Up Key
Down Key
Select Item Key
2.1 OVERVIEW
The operator interface of the BMS-2000 consists of two components:
• Heated, Back-lit LCD Alphanumeric Display
• 9-Key Membrane Keypad
OPERATION
Keypad functions:
• START initiates the automatic ignition sequence of the pilot and BMS. Once the pilot ame is
proven, the BMS will continue into NORMAL OPERATION.
Note: the BMS display must read “CLEAR TO START” in order to initiate startup sequence.
• STOP cancels the ignition sequence and / or shutdown the operation of the BMS and pilot
by closing all fuel train valves and extinguishing the pilot ame. A shutdown reading
of “LOCAL MANUAL S/D” will be displayed on BMS display page 1, indicating the STOP
button has been pressed.
• ACK clears any active shutdowns displayed on BMS display page 1. This key also acknowledges
passwords and selects items in the calibration and conguration menus for adjustment.
Note: active shutdowns will only be cleared from the display if they have been cleared in the
eld and a safe condition exists. If the ACK button is pressed and a shutdown has not
been eld-cleared, a *symbol will appear beside the shutdown, indicating that it has
been acknowledged by the operator, but the error still exists in the eld.

8of 42
Combustex BMS-2000 [5.03] Operations Manual - 2. OPERATION
Phone: 403.342.4494 |Web: www.canaltaow.com
For operational, technical or installation assistance, please contact us.
Call Us Toll Free: 1-855-226-2582
Upon power-up, the introduction message and controller version will be displayed:
From the main display, the user can scroll through ve dierent pages.
To enable the scroll function:
1. Press the ‘PAGE SCROLL’ button. Notice that the >symbol appears beside the page number in the
top left-hand corner of the display.
2. Press the and buttons to go to the desired page.
Burner Management System V 5.03
REV 2.xx
1>
Low Input Voltage 1 of 3
• CONFIG allows the user access to the Conguration Menu.
Note: BMS must be shut down (not in NORMAL OPERATION) in order to access the
Conguration Menu.
Note: Conguration Menu is password protected.
• CALIB allows the user access to the Calibration Menu.
Note: BMS must be shut down (not in NORMAL OPERATION) in order to access the
Calibration Menu.
Note: Calibration Menu is password protected.
• PAGE SCROLL / EXIT displays a >symbol beside the page number in the top left corner of the
BMS display, indicating that the user may scroll through the pages by pressing the arrow keys.
PAGE SCROLL is also used to exit the Conguration and Calibration Menus.
• SELECT ITEM allows the user to scroll through any active shutdowns on BMS display page 1,
change the control parameters on page 2, and adjust settings on pages 4 and 5 (using the
arrow keys). SELECT ITEM also moves the cursor from right to left when inputting any
password or numerical value.
• The arrows are used to scroll through pages, scroll through the Conguration and
Calibration Menus, and adjust settings and numerical values.

9of 42
Combustex BMS-2000 [5.03] Operations Manual - 2. OPERATION
Phone: 403.342.4494 |Web: www.canaltaow.com
For operational, technical or installation assistance, please contact us.
Call Us Toll Free: 1-855-226-2582
2.2 PASSWORDS - GAINING ENTRY
The controller will be precongured at time of order, making changes to the unit’s conguration and
calibration unnecessary.
The BMS-2000 has a congurable 4-digit password which can be used to prevent unauthorized personnel
from altering conguration, calibration or temperature control parameters. Once in the conguration
menu, the ‘USER’ password can be changed to a dened value.
Whenever the BMS asks for the password, use the ‘SELECT ITEM’ and and buttons to change the
password, then press the ‘ACK’ key.
If the ‘USER’ password has been congured, use that value. If the ‘USER’ password has not been
congured, use the ‘MASTER’ password.
Factory presets are as follows:
MASTER - Password is 1313 and can be used if ‘USER’ password is forgotten.
USER - Same entry level as‘MASTER’ but user-dened (see section 3.2 item 39).
CONFIG - Manufacturer and authorized personnel (password = 0065).
CALIB - Manufacturer and authorized personnel (password = 0067).
Feature access is as follows:
ACCESS TYPE MASTER USER CONFIG CALIB
View CONFIG Menu Items YES YES YES YES
Change Enabled CONFIG Menu Items YES YES YES YES
Change Locked CONFIG Items NO NO YES NO
View CALIB Menu Items YES YES YES YES
Change CALIB Menu Items NO NO NO YES
View PAGE 5 (PID, ON/OFF Parameters) YES YES YES YES
Change PID / ON/OFF Control Parameters YES YES YES YES
Pages are displayed in the following order:
Page 1 - Sequence Status & Shutdown
Page 2 - Temperature Control / Set Point
Page 3 - Output Status
Page 4 - Auxiliary Analog Input
Page 5 - PID & Temperature Control Parameter

10 of 42
Combustex BMS-2000 [5.03] Operations Manual - 2. OPERATION
Phone: 403.342.4494 |Web: www.canaltaow.com
For operational, technical or installation assistance, please contact us.
Call Us Toll Free: 1-855-226-2582
2.3 SEQUENCE STATUS & SHUTDOWN ANNUNCIATION
Page one on the controller display is the Sequence / Status page which displays:
• The current status of the controller
• Shutdown conditions
All shutdowns are recorded in chronological order and can be scrolled through.
1. Press the ‘SELECT ITEM’ key
2. Press the and buttons
In the example below, three shutdowns are active, the rst of which is due to low voltage.
All shutdowns must be cleared before being permitted to proceed. To clear them:
1. Satisfy the shutdown condition(s)
2. Depress the ‘ACK’ key for each condition (shutdown message will scroll in sequence)
Note:
• Any shutdown which has been acknowledged will have an asterisk (*) preceding the text.
• Any condition that has been satised will be cleared from the screen, providing it has been
acknowledged. Note: See section 6 for troubleshooting shutdown conditions (pp. 37 - 41).
After all shutdowns have been cleared and acknowledged, the following will be displayed:
1.
Low Input Voltage 1 of 3
1.
*Remote Shutdown 2 of 3
1.
Clear to Start

11 of 42
Combustex BMS-2000 [5.03] Operations Manual - 2. OPERATION
Phone: 403.342.4494 |Web: www.canaltaow.com
For operational, technical or installation assistance, please contact us.
Call Us Toll Free: 1-855-226-2582
The BMS-2000 is now ready to relight the burner. The following message appears after depressing the
‘START’ button (ignitor is on Preset Trial for Ignition Period):
The following message is displayed once the system has veried the pilot ame:
If, after reaching “Normal Mode”, the pilot ame goes out, the following message will be displayed
(provided relight attempts have been enabled):
After the preset purge time, the relight ignition sequence is initiated.
1.
Ignition ON
1.
#1 Burner
Normal Mode
1.
Relight Attempt #1
Purge On
1.
Relight Attempt #1
Ignition On

12 of 42
Combustex BMS-2000 [5.03] Operations Manual - 2. OPERATION
Phone: 403.342.4494 |Web: www.canaltaow.com
For operational, technical or installation assistance, please contact us.
Call Us Toll Free: 1-855-226-2582
2.4 TEMPERATURE CONTROL
Temperature control is accessed on page two of the BMS-2000 controller display. This page displays:
• Bath and/or Process Temperature
• Bath and/or Process Set Point
• Temperature Control Output Status
• HTSD Set Point (as set in the conguration menu)
* Note: Displayed temperature units are specied at time of order.
While viewing this page, the operator can:
• Adjust the Local Set Point
• Switch between Local, Remote or Serial Set Point Control
• Adjust ‘Manual’ Control’s Output Value
To make these changes:
1. Depress the ‘SELECT ITEM’key repeatedly until the ashing cursor is in front of the parameter to be
changed.
2. Use the and buttons to scroll through the options or to change the value.
NOTES:
• When congured for proportional control, the output will be displayed in‘%’.
• When congured for ON/OFF control, the output will be displayed as ‘ON’or ‘OFF’.
• Set point input oers three options:
• Loc. = Local (from BMS keypad)
• Rem. = Remote (via 4-20mA signal) - ‘REMOTE SP I/P’ must be enabled in conguration
• Ser. = Serial (computer interface, RS 232/485)
2. Bath: +21C
SP : +70C Loc.
OUT.: 90% Auto
HTSD: +95C

13 of 42
Combustex BMS-2000 [5.03] Operations Manual - 2. OPERATION
Phone: 403.342.4494 |Web: www.canaltaow.com
For operational, technical or installation assistance, please contact us.
Call Us Toll Free: 1-855-226-2582
2.5 OUTPUT STATUS PAGE
Page three of the BMS-2000 controller displays the status of the following:
• Pilot Solenoid Valve
• Main Solenoid Valve
• Ignition Output
• Purge Blower Output
NOTE: This page is non-adjustable and is for indication only.
2.6 AUX. ANALOG INPUTS AND SHUTDOWNS
Page four of the BMS-2000 controller displays two monitored values:
• Spare Thermocouple Input #1 (if selected)
• This value can be labeled as‘ #1 Stack’, ‘Bath’ or ‘Process’
• Input can be used for indication only, or as a HTSD
• When used as a HTSD, this value appears in brackets beside the actual temperature
• Supply Voltage
* Note: Displayed temperature units are specied at time of order.
NOTE: This page is non-adjustable and is for indication only. Shutdown limits, which appear in brackets,
are denable in the conguration menu (see section 3.2).
3. #1 Pilot : Open
#1 Main : Open
#1 Ign. : Off
Purge Blower: Off
4. #1 Stack : +315C [+700]
Supply Voltage : +24V [+20]

14 of 42
Combustex BMS-2000 [5.03] Operations Manual - 2. OPERATION
Phone: 403.342.4494 |Web: www.canaltaow.com
For operational, technical or installation assistance, please contact us.
Call Us Toll Free: 1-855-226-2582
2.7 PID & CONTROL PARAMETER PAGE
NOTE: This page is password protected. See section 2.2.
Page ve of the BMS-2000 controller display allows the adjustment of four parameters relating to
temperature control:
• Proportional, for PID control only
• Integral (Reset), for PID control only
• Derivative (Rate), for PID control only
• Dead Band, for ON/OFF control only
To make these adjustments:
1. Depress the ‘SELECT ITEM’key repeatedly until the ashing cursor is in front of the parameter to be
changed.
2. Use the and buttons to change the value.
* Note: Displayed temperature units are specied at time of order.
NOTES:
• If the Rate or Reset values are equal to zero, they are disabled.
• All of the above parameters can be changed during startup or normal operation.
5. Prop. Band (%) Bath: 50
Reset (Min/Rpt) Bath: 0.00
Rate (Min) Bath: 0.00
D.Band (Deg C) Bath: 2

15 of 42
Combustex BMS-2000 [5.03] Operations Manual - 3. CONFIGURATION
Phone: 403.342.4494 |Web: www.canaltaow.com
For operational, technical or installation assistance, please contact us.
Call Us Toll Free: 1-855-226-2582
CONFIGURATION
3.1 OVERVIEW
The BMS-2000 Burner Management System is congured by adjusting a series of password protected
menu items. This menu is accessed by depressing the ‘CONFIG’ key on the BMS keypad.
Initial Display
Parameter open for change (signied by >symbol)
To congure the BMS-2000:
1. Use the and buttons to navigate through the menu items.
2. Select an item for conguration by depressing the ‘ACK’ button. The >symbol will appear behind
the variable to be changed.
3. Use the and buttons to scroll through the list of options.
4. When a numerical value appears and the cursor is ashing, the value is open for adjustment. Use
the ‘SELECT ITEM’ key to move the cursor and the and buttons to change it.
5. If a numerical value appears in a list of options, depress the‘ACK’ key again to get the cursor to
ash.
6. Depress the ‘ACK’ key to conrm selection. Notice the >symbol disappear.
7. Resume scrolling through the menu items.
8. Depress the ‘PAGE SCROLL’button to exit from the CONFIG menu.
NOTES:
• The BMS-2000 is pre-congured at the factory, and the CONFIG menu is password protected. See
section 2.2.
• All shutdowns are factory set to YES by default. If a specic shutdown is not required, it must be
manually set to NO in the CONFIG menu. An active shutdown with no eld device will result in an er-
ror message and the controller will NOT be permitted to START.
• The CONFIG menu cannot be accessed while the BMS is in operation.
Burners
Parallel
Burners
>Parallel

16 of 42
Combustex BMS-2000 [5.03] Operations Manual - 3. CONFIGURATION
Phone: 403.342.4494 |Web: www.canaltaow.com
For operational, technical or installation assistance, please contact us.
Call Us Toll Free: 1-855-226-2582
3.2 CONFIGURATION MENU ITEMS
Below are the BMS-2000 Version 5.03 CONFIG menu items and their options. See pp. 17 - 23 for a
description of each.
Item # Sequencing Items Available Options Notes
1 Burners 1 / 2 / Dual Parallel / Dual Series
2 #1 T/C Flame 1st Level 0 - 800°C (32 - 1472°F)
Preset at 250°C (482°F)
N/A when “Flame Detection” cong-
ured to“Contact” (ame rod, UV)
3 #1 T/C Flame 2nd Level 0 - 800°C (32 - 1472°F)
Preset at 450°C (842°F)
N/A when “Flame Detection” cong-
ured to“Contact” (ame rod, UV)
4 #2 T/C Flame 1st Level 0 - 800°C (32 - 1472°F)
Preset at 250°C (482°F)
N/A when “Flame Detection” cong-
ured to“Contact” (ame rod, UV)
5 #2 T/C Flame 2nd Level 0 - 800°C (32 - 1472°F)
Preset at 450°C (842°F)
N/A when “Flame Detection” cong-
ured to“Contact” (ame rod, UV)
6 Trial for Ignition Timer
0 - 3.0 Minutes
Preset to .15 (9 sec) for“Contact”
Preset to 2 for“T/C”
Preset to 9 sec. when “Flame Detec-
tion” congured to“Contact” (ame
rod, UV)
7Flame T/C 2nd Level Timer 0 - 5.0 Minutes
Preset to 3 for“T/C”
N/A when “Flame Detection” cong-
ured to“Contact” (ame rod, UV)
8Purge Timer 0 - 10.0 Minutes
9 Pre-purge Yes / No
10 Ignition Steady / Pulsed
11 Relight Attempts 0 / 1 / 2 / 3
12 Flame Detection Contact / T/C / Aux Contact
13 Remote Start Yes / No
14 Remote Stop Yes / No
15 Power Failure Auto Relight Yes / No
Safety Interlocks
16 Proof of Closure #1 Yes / No
17 Proof of Closure #2 Yes / No
18 Pilot Continuous / Intermittent
19 Flame Status Independent / Common
20 Fuel Low Pressure #1 Yes / No
21 Fuel High Pressure #1 Yes / No

17 of 42
Combustex BMS-2000 [5.03] Operations Manual - 3. CONFIGURATION
Phone: 403.342.4494 |Web: www.canaltaow.com
For operational, technical or installation assistance, please contact us.
Call Us Toll Free: 1-855-226-2582
Conguration Menu Items cont’d
Item # Sequencing Items Available Options Notes
22 Fuel Pressure #2 None / Hi Press / Hi & Low Press
23 Spare Temp. T/C #1 None / Indicate Only /
0 - 800°C (32 - 1472°F)
24 Spare Temp. #1 T/C Label Stack #1 / Bath / Process
25 Spare Temp. T/C #2 None / Indicate Only /
0 - 800°C (32 - 1472°F)
26 Spare Temp. #2 T/C Label Stack #2 / Bath / Process
27 Allow Auto / Manual Yes / No
28 Control Mode None, Proportional, On-O
29 Main Bath T/C High Temp. No / 0 - 600°C (32 - 1112°F)
30 Bath High Temp. (Contact) Yes / No
31 Bath Low Level Yes / No
32 Low Voltage 10 - 30 Volts
33 Spare Analog Input S/D None / Indicate Only / 0 - 100%
Temperature Control
34 Control Output Mode Steady / Latching Pulse
35 Remote Set Point I/P Yes / No
36 Remote Temp. Indicate O/P Yes / No
Operational
37 Backlight Steady On / O / Light Activated / Timed
38 Audio Yes / No
39 New Access Code 0 - 9999
40 R.F. Filter 0 - 1000
41 L.P. Filter (Pilot, Spare #1) 0 - 9999
42 L.P. Filter (Bath, Spare #2) 0 - 9999
43 Modbus Address 0 - 247

18 of 42
Combustex BMS-2000 [5.03] Operations Manual - 3. CONFIGURATION
Phone: 403.342.4494 |Web: www.canaltaow.com
For operational, technical or installation assistance, please contact us.
Call Us Toll Free: 1-855-226-2582
• Burner 1 operates only (see P&ID drawings pp. 31 - 15).
• Burner 2 operates only.
• Parallel - Dual Burner System. Both burners will run independently of each other
• Series - Dual Burner System. Both burners will shut down on any single ame fail.
This value represents the rst level of the ame proving sequence for burner #1 if“Flame Detection” is
congured to Thermocouple. Main burner #1 is allowed to open after crossing this set point. Preset at
250°C (482°F).
This value represents the nal level of ame verication for burner #1 if “Flame Detection” is congured
to Thermocouple. Burner #1 will go into Normal Operation upon crossing this set point. Preset at 450°C
(842°F).
This value represents the rst level of the ame proving sequence for burner #2 if“Flame Detection” is
congured to Thermocouple. Main burner #1 is allowed to open after crossing this set point. Preset at
250°C (482°F).
This value represents the nal level of ame verication for burner #1 if “Flame Detection” is congured
to Thermocouple. Burner #1 will go into Normal Operation upon crossing this set point. Preset at 450°C
(842°F).
This value sets the amount of time the BMS will allow for the Flame Sensor to verify a ame. If the ame
sensor does not send signal to BMS verifying a ame in the prescribed time, the ignition sequence is
halted. Preset for 10 seconds on contact input.
1 Burners 1 / 2 / Dual Parallel / Dual Series
2 #1 T/C Flame 1st Level 0 - 800°C (32 - 1472°F)
3 #1 T/C Flame 2nd Level 0 - 800°C (32 - 1472°F)
4 #2 T/C Flame 1st Level 0 - 800°C (32 - 1472°F)
5 #2 T/C Flame 2nd Level 0 - 800°C (32 - 1472°F)
6 Trial for Ignition 0 - 3.0 Minutes
Table of contents
Popular Control System manuals by other brands

Tektronix
Tektronix Keithley 7709 Instructions for use

Roger Technology
Roger Technology BAFS/05 instructions

ERS
ERS AK 6000 user manual

MacroAir Technologies
MacroAir Technologies Controller 4 Operation manual

WEIHONG
WEIHONG LS1500 manual

Liberty Pumps
Liberty Pumps OilTector OTC-115 Operation and maintenance manual