Cardinal 225 Manual instruction

8200-M564-O1 y225 Check Weigher Page 1
CHECK WEIGHER
For The 225 Weight Indicator
Installation, Setup and Operation Manual
8200-M564-O1 Rev A PO BOX 151 yWEBB CITY, MO 64870 Printed in USA
08/09 PH (417) 673-4631 yFAX (417) 673-5001
www.cardinalscale.com

8200-M564-O1 y225 Check Weigher Page 2

8200-M564-O1 y225 Check Weigher Page 1
INSTALLATION
Logic Level Output
Your Model 225 indicator has logic level outputs that can be used to control peripheral devices
used to signal when the weight is within preset limits. Note that these outputs (defined on the
next page) are at logic level and cannot drive external devices directly. Solid-state relays can
be used to accept the logic level output from the 225 and in turn, drive the external device.
Output Cable Installation
1. If the rear panel of the indicator has been removed, proceed to step 2. Otherwise,
remove the 14 acorn nuts securing the rear panel to main housing
2. Loosen a gland connector for the cable.
3. Slip the cable through the gland connector and into the enclosure.
4. Remove 2 inches of the cable outer insulation jacket
5. Next, remove 1/4 inch of insulation from each of the wires.
6. Connect each of the wires to the Remote Outputs terminal block (P15).
7. To terminate a wire, use a small flat blade screwdriver and press down on the release
bar for the terminal. Insert the wire into the terminal opening. Remove the screwdriver,
allowing the release bar to return to its original position, locking the wire in place.
8. Repeat procedure until all wires are in place.
AC Output Relay Board(s)
The AC Output Relay Boards are mounted in an external junction box for use with the 225
Indicator. The RB4-ACOUT contains one board and supports four outputs (jumper selectable).
The RB8-ACOUT contains two boards and supports eight outputs. The relay board used in
both is (Cardinal p/n 8539-C062-0A). Connect the devices to be controlled as shown in Figure
No. 1.
The individual relays can be configured to be on (closed) or off (open) at weights under the
preset weight then switch at the preset weight from on-to-off or off-to-on by setting the under
weight condition to on or off during setup and calibration or setup review.
OUTPUT (closed) 28-240VAC @ 3A maximum for each plug-in relay
CONTROL INPUT 5VDC @ 12mA from the 225 main pc board assembly P8
CONNECTION Removable plug-in screw terminals for up to 14 AWG wire
NOTE! All relays are the normally-open type that will open when power to indicator is lost.

8200-M564-O1 y225 Check Weigher Page 2
AC Output Relay Board(s), Cont.
Figure No. 1
Relay Box Cable Wire Number to Relay Number Table
The relay box cable wire numbers correspond to the 225 indicator P15 terminal connections.
CABLE WIRE
NUMBER RELAY NUMBER
(Set Proper Jumpers) CABLE WIRE
NUMBER RELAY NUMBER
(Set Proper Jumpers)
1 +SRC (For AC Input Relays) 6 5
2 1 7 6
3 2 8 7
4 3 9 8
5 4 10 GND
Relay Box Assembly RB4-ACOUT or RB8-ACOUT
225 Indicator – P15
CHECKWEIGHER
Relay Board
P15 3 Zone 5 Zone
2 Under Under
3 Accept Lo Under
4 Over Accept
5 Lo Over
6 Over
7
8
9

8200-M564-O1 y225 Check Weigher Page 3
OPTICALLY ISOLATED REMOTE INPUTS
The Model 225 has seven (7) programmable inputs that may be used to remotely (up to 100
feet) initiate various functions within the indicator. These inputs are accessed via a terminal
block (P17) on the back of the Main PC board. The 7 inputs are defined on the following page.
Remember that the input must be connected to GND to initiate the function.
Input Cable Installation
1. If the rear panel of the indicator has been removed, proceed to step 2. Otherwise,
remove the 14 acorn nuts securing the rear panel to main housing
2. Loosen a gland connector for the cable and slip the cable through the gland connector
and into the enclosure.
3. Remove 2 inches of the cable outer insulation jacket and then remove 1/4 inch of
insulation from each of the wires.
4. Connect each of the wires to the Remote Input terminal block (P17).
5. To terminate a wire, use a small flat blade screwdriver and press down on the release
bar for the terminal. Insert the wire into the terminal opening. Remove the screwdriver,
allowing the release bar to return to its original position, locking the wire in place.
6. Repeat procedure until all wires are in place.
AC Input Relay Board(s)
The AC Input Relay Board(s) are mounted in an external junction box for use with the 225
Indicator. The RB4-ACIN (115 VAC) or RB4-ACINV (230 VAC) contain one board and
supports 4 inputs (jumper selectable). The RB8-ACIN (115 VAC) or RB8-ACINV (230 VAC)
contain two boards and supports seven inputs that are jumper selectable. The relay board
used in the 115 VAC versions is Cardinal p/n 8200-C324-0A. The 230 VAC version uses relay
board Cardinal p/n 8200-C324-1A. Connect the devices as shown in Figure No. 2.
INPUT RELAY TYPE IAC-5 90 to 140 VAC @ 6mA maximum for each plug-in relay
INPUT RELAY TYPE IAC-5A 180 to 280 VAC @ 6mA maximum for each plug-in relay
OUTPUT 5VDC @ 12mA from the 225 main pc board assembly P9
12VDC @ 12mA maximum from external source
CONNECTION Removable plug-in screw terminals for up to 14 AWG wire
NOTE! AC INPUT RELAYS ARE VOLTAGE DEPENDENT.
A DIFFERENT RELAY IS REQUIRED FOR 115 VAC AND 230 VAC!

8200-M564-O1 y225 Check Weigher Page 4
AC Input Relay Board(s), Cont.
Figure No. 2
Relay Box Cable Wire Number to Relay Number Table
The relay box cable wire numbers correspond to the 225 indicator P17 terminal connections.
CABLE WIRE
NUMBER RELAY NUMBER
(Set Proper Jumpers) CABLE WIRE
NUMBER RELAY NUMBER
(Set Proper Jumpers)
1 +SRC (For AC Input Relays) 6 5
2 1 7 6
3 2 8 7
4 3 9 8
5 4 10 GND
Relay Box Assembly RB4-ACIN or RB8-ACIN
Relay Box Assembly RB4-ACINV or RB8-ACINV
225 Indicator – P17
INPUT
Relay Board
P17 INPUTS
2 ZERO
3 TARE
4 Gross/Net
5 PRINT
6 PAUSE
7 STOP
8 START
9 DUMP

8200-M564-O1 y225 Check Weigher Page 5
MAIN PC BOARD
CAUTION! This board contains static sensitive components. Improper
handling can result in damage to or destruction of the components or board.
Such actual and/or consequential damage IS NOT covered under warranty.
J1
COM2/3 P18
(SERIAL I/O)
POWER
P5
REMOTE
INPUTS P17
P10
MEGA3
ISP
LOAD
CELL P13
J4
P11
Option
Board
Figure No. 3
REMOTE
OUTPUTS P16 REMOTE
OUTPUTS P15 PRINTER P14
COM1 SERIAL
J5
J6
J7J8
J9 J10
TWO SCALE
INPUT BOARD
P8
2560 ISP
P7
IIC BUS J2
J3
P6 CAL
SEAL

8200-M564-O1 y225 Check Weigher Page 6
MAIN PC BOARD JUMPERS
J4 (PWC1-8) and J5 (PWC9-16) – ACTIVE REMOTE OUT JUMPERS
When installed, these jumpers allow the 225 indicator to supply (source) 5 VDC to a solid-state
relay or other load of 200 ohms or greater. To operate from the 5 VDC source, the positive
connection from the relays must be connected to P15 (P16) pins 2 through 9 and the negative
wire from the relays to P15 (P16) pin 10 (GND). See Figure No. 9 for connector P15 location
and Figure No. 10 for connector P16 location.
For completely isolated outputs, J4 (J5) must be open (on one pin only or removed) and the
user must provide 5 to 12 VDC to P15 (P16) pin 1 (+SRC) and a ground return to the load.
The load must still be 200 ohms or greater and P15 (P16) pin 10 (GND) is not connected.
J6 (REMOTE IN) – REMOTE IN JUMPER
When installed, this jumper allows the 225 indicator to supply (source) 5 VDC to a remote input
circuit. Connecting P17 pins 1 through 9 to P17 pin 10 (GND) through a switch will cause the
selected action. See Figure No. 8 for connector P17 location.
For completely isolated inputs, J6 must be open (on one pin only or removed) and the user
must provide 5 to 12 VDC to P17 pin 1 (+SRC) and a ground return to the switch connected
to P17 pin 2 through 9. Note that P17 pin 10 (GND) is not connected.
J1 (AUTO ON) – AUTO-ON JUMPER
When installed, this jumper will cause the indicator to power on automatically whenever power
is applied to the power input connector. If power is lost momentarily and then reapplied, the
indicator will turn on without pressing the ON key.
J2 (TEST) – TEST JUMPER
When installed, this jumper will turn the backlight on, ignoring the BACK LITE= setting.
J3 (8V) – 8V EXCITATION JUMPER
When installed, this jumper allows the 225 indicator to supply 8 VDC excitation voltage when a
remote (external) 12 VDC battery is used to power the indicator. To operate from the 12 VDC
battery, the load cell excitation voltage MUST be set to 8 VDC (J3 closed). Operating with the
load cell excitation voltage set to 12 VDC will result in an unstable weight display.
J7 (+SEN) and J9 (-SEN) – SENSE JUMPERS
If the sense leads are NOT used, you must install jumpers at J7 and J9 (near the P13 and P14
terminal blocks). These jumpers connect the sense leads to the excitation leads. If sense
leads ARE used (as in motor truck scales), these jumpers should be open (on one pin only or
removed).
J8 (DLB) – DEAD LOAD BOOST JUMPER
For very low dead loads (less than 10% of the combined load cell capacity), connect J8, the
DLB (dead load boost) jumper on the printed circuit board.
J10 (GTC) – GND TO CHASSIS JUMPER
When installed, this jumper connects the analog circuit ground to the indicator chassis ground.

8200-M564-O1 y225 Check Weigher Page 7
RE-INSTALLING THE REAR PANEL
After all terminations have been made;
1. Remove the excess cable from the instrument enclosure and securely tighten each of
the cable gland connectors.
yDo not over-tighten these connectors but make certain they are snug.
yDO NOT USE TOOLS! Finger-tighten only!
2. Ensure any unused gland connectors are plugged and replace the rear panel.
3. Secure the rear panel with the 14 acorn nuts removed earlier.
4. Follow a diagonal pattern when tightening the acorn nuts.

8200-M564-O1 y225 Check Weigher Page 8
SETUP
Check Weigher (Mode of Operation = 4)
When selected, the Check Weigher will compare the displayed weight with preset values and
display the results as under, accept, or over. The checkweighing operation features are
selected in the Check Weigher Menu. To access the setup menus:
1. Press the SHIFT key and then the RED SQUARE navigation key.
2. The display will change to show the SETUP/REVIEW MENU.
3. Press the 1key and then the ENTER key.
4. The display will change to show SETUP MENU #1.
With SETUP MENU #1 displayed the current setting for the 10. MODE OF OP=X
parameter will be shown. Press the 1 and 0 keys and then the ENTER key. The display will
change to show the Mode Of Operation Menu. Press the 4 key and then the ENTER
key to select 4. Check Weigher. The display will change to show the
Check Weigher Menu.
The Check Weigher Menu shows the selections for the Check Weigher setup parameters.
Check Weigher Menu
1. OUTPUTS=X
2. AUTO PRINT=XXX
Enter Selection: X EXIT
1. OUTPUTS=X – NUMBER OF CHECK WEIGHER OUTPUTS
The display will show OUTPUTS=X, where X is the current value. If the setting displayed
is acceptable, continue to 2. AUTO PRINT=XXX.
To change the current setting, press the 1 key and then the ENTER key. OUTPUTS=X will
be displayed at the bottom of the display. Using the numeric keys, enter the new setting
and then press the ENTER key to save it. Allowable values are 3 or 5.
When OUTPUTS=3 is selected, the check weigher will compare the displayed weight with
either high and low preset values. When OUTPUTS=5 is selected, the check weigher will
compare the displayed weight with high, high-accept, low-accept and low preset values.

8200-M564-O1 y225 Check Weigher Page 9
SETUP, CONT.
OUTPUTS=3
If the check weigher feature is configured for a three-zone weight comparison,
(OUTPUTS=3), the indicator will make a comparison of the displayed weight with a
high and low preset value. The results of that comparison will be indicated as Over,
Under or Accept.
OUTPUTS=3
Low State before cutoff (Relay¾Open)
PWC1 UNDER
PWC2 ACCEPT
PWC3 OVER
OUTPUTS=5
If the check weigher feature is configured for the five-zone weight comparison,
OUTPUTS=5, the indicator will make a comparison of the displayed weight with the
high, high-accept, low-accept and low preset values. The results of this comparison will
be indicated as Over, High-Accept, Accept, Low-Accept or Under.
OUTPUTS=5
Low State before cutoff (Relay¾Open)
PWC1 UNDER
PWC2 UNDER ACCEPT
PWC3 ACCEPT
PWC4 ACCEPT OVER
PWC5 OVER
¾The relay state is based on using Cardinal Scale relays (p/n 6850-1013). If using relays
other than those supplied by Cardinal Scale, refer to the relay manufacturers specifications.
NOTE! When power to the indicator is lost, the output returns to a Low State condition.
2.AUTO PRINT=XXX – AUTOMATIC PRINT
The automatic print feature will cause an optional printer to print when the weight is in the
ACCEPT range and STABLE. STABLE is defined by the STABLE= and STBL CNT=
parameters settings in the SCALE 1 SETUP MENU #1.
The display will show AUTO PRINT=XXX where XXX is the current value. If the setting
displayed is acceptable, continue to the next section.
To change the current setting, press the 2 key and then the ENTER key.
AUTO PRNT=XXX will be displayed at the bottom of the display. Using the YES or NO
key, select the new setting and then press the ENTER key to save it.
AUTO PRNT=YES
Automatic Print Enabled
AUTO PRNT=NO
Automatic Print Disabled

8200-M564-O1 y225 Check Weigher Page 10
OPERATION
If the check weigher feature is configured for a 3-zone weight comparison, the indicator will
make a comparison of the displayed weight with a high (OVER) and low (UNDER) preset
value. The results of that comparison will be indicated as UNDER, ACCEPT, or OVER.
If the check weigher feature is configured for the 5-zone weight comparison, the indicator will
make a comparison of the displayed weight with the UNDER, LOW OK, HIGH OK, and OVER
preset values. The results of this comparison will be indicated as UNDER, UNDER ACCEPT,
ACCEPT, ACCEPT OVER, or OVER.
RELAY CONTROL OUTPUTS
OUTPUTS=3
Low State before cutoff (Relay* Open)
PWC1 UNDER
PWC2 ACCEPT
PWC3 OVER
OUTPUTS=5
Low State before cutoff (Relay* Open)
PWC1 UNDER
PWC2 UNDER ACCEPT
PWC3 ACCEPT
PWC4 ACCEPT OVER
PWC5 OVER
Enter the Preset values for a 3 zone Check Weigher using the following procedure:
1. With the indicator in the Gross or Net Weight mode, press the PRESET key.
2. The display will show UNDER=XXXXXX, where XXXXXX is the current value of the
under preset.
3. If the displayed value is acceptable, press the ENTER key to save it. Otherwise use the
numeric keys to enter a new value and then press the ENTER key to save it.
4. The display will show OVER=XXXXXX where XXXXXX is the current value of the over
preset
5. If the displayed value is acceptable, press the ENTER key to save it. Otherwise use the
numeric keys to enter a new value and then press the ENTER key to save it. Note that
the over value must be greater than the under value.
6. After the over preset value is entered, the 225 will return to normal operation.

8200-M564-O1 y225 Check Weigher Page 11
OPERATION, CONT.
Enter the Preset values for a 5 zone Checkweigher using the following procedure:
1. With the indicator in the Gross Weight mode (Gross annunciator, Gon the display), press
the PRESET key.
2. The display will show UNDER=XXXXXX, where XXXXXX is the current value of the
under preset.
3. If the displayed value is acceptable, press the ENTER key to save it. Otherwise use the
numeric keys to enter a new value and then press the ENTER key to save it.
4. The display will show LOW OK=XXXXXX, where XXXXXX is the current value of the
low accept preset.
5. If the displayed value is acceptable, press the ENTER key to save it. Otherwise use the
numeric keys to enter a new value and then press the ENTER key to save it. Note that
this value must be greater than the under value.
6. The display will show HIGH OK=XXXXXX, where XXXXXX is the current value of the
high accept preset.
7. If the displayed value is acceptable, press the ENTER key to save it. Otherwise use the
numeric keys to enter a new value and then press the ENTER key to save it. Note that
this value must be greater than the under value, but less than the over value.
8. The display will show OVER=XXXXXX, where XXXXXX is the current value of the over
preset
9. If the displayed value is acceptable, press the ENTER key to save it. Otherwise use the
numeric keys to enter a new value and then press the ENTER key to save it. Note that
the over value must be greater than the high accept value.
7. After the over preset value is entered, the 225 will return to normal operation.
NOTE! Remember that the check weigher function operates on the absolute value of
the weight ignoring the polarity.

8200-M564-O1 y225 Check Weigher Page 12
NOTES

8200-M564-O1 y225 Check Weigher Page 13

8200-M564-O1 y225 Check Weigher Page 14
Other manuals for 225
2
Table of contents
Other Cardinal Measuring Instrument manuals
Popular Measuring Instrument manuals by other brands

elsner elektronik
elsner elektronik KNX I4-ERD Installation and adjustment

DAKOTA ULTRASONICS
DAKOTA ULTRASONICS MAX II manual

Keysight
Keysight PNA-X Series Configuration guide

SIRETTA
SIRETTA SNYPER-LTEM quick start guide

Intellitec
Intellitec BATTERY GUARD 2000 Service manual

OTT HydroMet
OTT HydroMet KIPP & ZONEN SMP12 operating manual