Carrier 38BRC Manual

38BRC
38BRG
018–060 60 Hertz
Wiring Diagrams
Fig. 1—38BRC and 38BRG 018–048 208/230v, 1 Phase, 60 Hertz A04021
FACTORY POWER WIRING
FACTORY CONTROL WIRING
FIELD CONTROL WIRING
FIELD POWER WIRING
COMPONENT CONNECTION
FIELD SPLICE
JUNCTION
CONT CONTACTOR
CAP CAPACITOR (DUAL RUN)
*CH CRANKCASE HEATER
*CHS CRANKCASE HEATER SWITCH
COMP COMPRESSOR
*CTD COMPRESSOR TIME DELAY
*DTS DISCHARGE TEMP. SWITCH
*HPS HIGH PRESSURE SWITCH
IFR INDOOR FAN RELAY
*LLS LIQ. LINE SOLENOID VALVE
*LPS LOW PRESSURE SWITCH
OFM OUTDOOR FAN MOTOR
*SC START CAPACITOR
*SR START RELAY
*ST START THERMISTOR
* MAY BE FACTORY OR FIELD INSTALLED.
324476-101 REV. B
CONT
L1
11 21
*CH
EQUIP
GND
*SR
*SC
H
COMP
*ST
C
F
CAP
OFM CONT
23 23
L2
52
1
*LPS
* CTD
*DTS
*HPS
*LLS
IFR
THERMOSTAT
INDOOR
Y
G
RC
R
EXTERNAL POWER SUPPLY 24 V
(NOTE #14)
+t
LOGIC
T1 T3
T2
1. Symbols are electrical representation only.
2. Compressor and fan motor furnished with inherent thermal protection.
3. To be wired in accordance with National Electric N.E.C. and local codes.
4. N.E.C. class 2, 24 V circuit, min. 40 VA required, 60 VA on units installed with LLS.
5. Use copper conductors only. Use conductors suitable for at least 75˚C (167˚F).
6. Connection for typical cooling only thermostat. For other arrangements see installation
instructions.
7. If indoor section has a transformer with a grounded secondary, connect the grounded side
to the BRN lead.
8. When start relay and start capacitor are installed, start thermistor is not used.
9. CH not used on all units.
10. If any of the original wire, as supplied, must be replaced, use the same or equivalent
wire.
11. Check all electrical connections inside control box for tightness.
12. Do not attempt to operate unit until service valves have been opened.
13. Do not rapid cycle compressor. Compressor must be off 3 minutes to allow pressures to
equalize between high and low side before starting.
14. Wire not present if HPS, LPS, DTS or CTD are used.
CONT
-LEGEND-
(SUPERHEAT ˚F AT LOW-SIDE SERVICE PORT)
EVAPORATOR ENTERING AIR ˚F WB.
TEMP ˚F
OUTDOOR
50
TABLE I-SUPERHEAT CHARGING TABLE
52 54 56 58 60 62 64 66 68 70 72 74 76
55 9 12141720232629323537404245
60 7 10121518212427303335384043
65 -- 6 101316192124273033363841
70 -- -- 7 1013161921242730333639
75 -- -- -- 6 9 12 15 18 21 24 28 31 34 37
80 -- -- -- -- 5 8 12 15 18 21 25 28 31 35
85 -- -- -- -- -- -- 8 11 15 19 22 30 3326
90 -- -- -- -- -- --
--------------
-- -- -- -- -- -- --
--
--
--
--
--
----
--
----
--
----
--
------
--
-- --
--
5 9 13 16 20 24 27 31
95 6 101418222529
100 8 1215202327
5 9 13 17 22 26
6 11152025
8 141823
--
--
-- --
-- -- --
105
110
115
918987858381797775
40
89878583817977757338
878583817977757371
36
85838179777573716934
838179777573716967
32
81797775737169676530
797775737169676563
28
77757371696765636126
757371696765636159
24
73716967656361595722
716967656361595755
20
69676563615957555318
676563615957555351
16
65636159575553514914
636159575553514947
12
61595755535149474510
595755535149474543
8
5755535149474543416
555351494745434139
4
5351494745434139372
514947454341393735
0
85.782.479.276.073.070.067.164.2
SUCTION PRESSURE AT SERVICE PORT PSIG.
TEMP. ˚F
61.5
SUPERHEAT
(MEASURED AT LOW-SIDE SERVICE PORT)
TABLE II-REQUIRED SUCTION TUBE TEMPERATURE ˚F
1. Operate unit a minimum of 10 minutes before checking charge.
2. Measure suction pressure by attaching a gage to suction valve service port.
3. Measure suction temperature by attaching an accurate thermistor type or
electronic thermometer to the suction line at service valve.
4. Measure outdoor air dry-bulb temperature with a thermometer.
5. Measure indoor air (entering indoor coil) wet-bulb temperature with a sling
psychrometer.
6. Refer to table I. Find outdoor temperature and evaporator entering air wet-bulb
temperature. At this intersection note the superheat.
7. Refer to table II. Find superheat temperature located in step 6 and suction
pressure. At this intersection note suction line temperature.
8. If unit has a higher suction line temperature than charted temperature, add
refrigerant until charted temperature is reached.
9. If unit has a lower suction line temperature than charted temperature, remove and
recover refrigerant until charted temperature is reached.
10. If outdoor air temperature or pressure at suction valve changes, charge to new
suction line temperature indicated on chart.
11. This procedure is valid when indoor air flow is within ±21% of its rated cfm.
-NOTES-
1. Compressor damage may occur if system is overcharged.
2. This unit is factory charged with R-22 in accordance with the amount shown on the rating plate. The charge is adequate for
most systems using matched coils and tubing not over 15 feet long. The best performance will be achieved when the unit
operates with a suction gas superheat at the compressor inlet of 5 ˚F at normal rating conditions of the air conditioning and
refrigeration institute (ARI). This chart may be used to approximate the charge if ARI rating conditions cannot be obtained.
ARI rating conditions are equivalent to DOE test "A" conditions. See product data literature for required indoor air flow
rates and for use of line lengths over 15 Ft.
3. Relieve pressure and recover all refrigerant before system repair or final unit disposal. Use all service ports and open all
flow-control devices, including solenoid valves.
CAU
TIO
N
CONNECTION DIAGRAM SCHEMATIC DIAGRAM (LADDER FORM)
S
CR
BLK
or
RED
*CH
RED or BLK CONT BLK
YEL
YEL
COMP
BLK
BLU CAP
YEL
BLU
BLU
YEL
*ST
BRN
*SR
OFM BRN
BRN BLK
BLK
208/230 1Ø
POWER
SUPPLY
GND
EQUIP
+t
L1
L2 11 21
23 23
H
C
F
YEL
VIO
BLU
(NOTE #14)
(NOTE #9)
(NOTE #8)
YEL
*LPS
YEL
* CTD
*DTS
*HPS
INDOOR BLOWER MOTOR
EXTERNAL
POWER
SUPPLY
24 V
(NOTE #3)
INDOOR THERMOSTAT
(NOTE #6)
R
G
Y
BRN
BLK
BLU BLK
BLU
*LLS
BLU
BLU
BLK
BLK
LOGIC
T1 T3
T2
12
5
S
C
R
C
R
*SC
*CHS
BLK
*CHS
Visit www.carrier.com
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4
Tab 2a 3a PC 101 Catalog No. 533-80109 Printed in U.S.A. Form 38BRC-5W Pg 1 2-04 Replaces: 38BRC-4W
Fig. 2—38BRC and 38BRG 060 208/230v, 1 Phase, 60 Hertz A04022
*CH (NOTE #9)
RED or BLK
BLK
208/230 1Ø
POWER
SUPPLY
L1
L2
EQUIP
GND
CONT
11 21
13 23 YEL
OFM
YEL
COMP BLU
BRN
BRN
YEL
S
C
RYEL
YEL
BLU BLU
BRN
*SC
BLK
BLK
*ST
*SR
12
5
CAP
*LPS*DTS
*HPS
BLK BLK YEL
BLU
VIO
H
C
F
CONNECTION DIAGRAM
+t˚
BLU
BLK
BLU YEL
*CTD
BRN
(NOTE #14)
BLU
BLU BLK
*LLS
BLK
Y RG
INDOOR THERMOSTAT (NOTE #5) INDOOR BLOWER MOTOR
EXTERNAL POWER
SUPPLY 24V
(NOTES #3 & #6)
(NOTE #8)
SCHEMATIC DIAGRAM
(LADDER FORM)
11 21
CONT
L1
EQUIP
GND
*SR
*SC
52
1H
C
F
*ST
OFM
+t˚
CONT
23 13
CAP
S
CRCOMP
L2
*LPS
*DTS
*HPS
CONT
IFR
EXTERNAL POWER SUPPLY 24 V
*CTD
(NOTE #14)
Y
G
R
INDOOR THERMOSTAT
RC
*CH
1. Symbols are electrical representation only.
2. Compressor and fan motor furnished with inherent thermal protection.
3. To be wired in accordance with National Electric N.E.C. and local codes.
4. N.E.C. class 2, 24 V circuit, min. 40 VA required, 60 VA on units
installed with LLS.
5. Use copper conductors only.
6. Connection for typical cooling only thermostat, for other arrangements,
see installation instructions.
7. If indoor section has a transformer with a grounded secondary, connect
the grounded side to the BRN lead.
8. When start relay and start capacitor are installed, start thermistor is not
used.
9. CH not used on all units.
10.If any of the original wire, as supplied, must be replaced, use the same
or equivalent wire.
11.Check all electrical connections inside control box for tightness.
12.Do not attempt to operate unit until service valves have been opened.
13.Do not rapid cycle compressor. Compressor must be off 3 minutes to
allow pressures to equalize between high and low side before starting.
14.Wire not present if HPS, LPS, DTS or CTD are used.
15.Use conductors suitable for at least 75˚C (167˚F).
EVAPORATOR ENTERING AIR ˚F WB.
TEMP ˚F
OUTDOOR
50
TABLE I-SUPERHEAT CHARGING TABLE
(SUPERHEAT ˚F AT LOW-SIDE SERVICE PORT)
52 54 56 58 60 62 64 66 68 70 72 74 76
55 9 12141720232629323537404245
60 7 10121518212427303335384043
65 -- 6 101316192124273033363841
70 -- -- 7 1013161921242730333639
75 -- -- -- 6 9 12 15 18 21 24 28 31 34 37
80 -- -- -- -- 5 8 12 15 18 21 25 28 31 35
85 -- -- -- -- -- -- 8 11 15 19 22 30 3326
90 -- -- -- -- -- --
--------------
-- -- -- -- -- -- --
--
--
--
--
--
----
--
----
--
----
--
------
--
-- --
--
5 9 13 16 20 24 27 31
95 6 101418222529
100 8 1215202327
5 9 13 17 22 26
6 11152025
8 141823
--
--
-- --
-- -- --
105
110
115
324474-101 REV. C
1. Operate unit a minimum of 10 minutes before checking charge.
2. Measure suction pressure by attaching a gage to suction valve service port.
3. Measure suction temperature by attaching an accurate thermistor type or electronic
thermometer to the suction line at service valve.
4. Measure outdoor air dry-bulb temperature with a thermometer.
5. Measure indoor air (entering indoor coil) wet-bulb temperature with a sling
psychrometer.
6. Refer to table I. Find outdoor temperature and evaporator entering air wet-bulb
temperature, at this intersection note the superheat.
7. Refer to table II. Find superheat temperature located in step 6 and suction
pressure, at this intersection note suction line temperature.
8. If unit has a higher suction line temperature than charted temperature, add
refrigerant until charted temperature is reached.
9. If unit has a lower suction line temperature than charted temperature, remove and
recover refrigerant until charted temperature is reached.
10. If outdoor air temperature or pressure at suction valve changes, charge to new
suction line temperature indicated on chart.
11. This procedure is valid when indoor air flow is within ±21% of its rated CFM.
1. Compressor damage may occur if system is over charged.
2. This unit is factory charged with R-22 in accordance with the amount shown on the rating plate. The
charge is adequate for most systems using matched coils and tubing not over 15 feet long. The
best performance will be achieved when the unit operates with a suction gas superheat at the
compressor inlet of 5 ˚F at normal rating conditions of the air conditioning and refrigeration institute
(ARI). This chart may be used to approximate the charge if ARI rating conditions cannot be obtained.
ARI rating conditions are equivalent to DOE test "A" conditions. See product data literature for required
indoor air flow rates and for use of line lengths over 15 Ft.
3. Relieve pressure and recover all refrigerant before system repair or final unit disposal. Use all service
ports and open all flow-control devices, including solenoid valves.
91898785838179777540
89878583817977757338
87858381797775737136
85838179777573716934
83817977757371696732
81797775737169676530
79777573716967656328
77757371696765636126
75737169676563615924
73716967656361595722
71696765636159575520
69676563615957555318
67656361595755535116
65636159575553514914
63615957555351494712
61595755535149474510
5957555351494745438
5755535149474543416
5553514947454341394
5351494745434139372
5149474543413937350
85.782.479.276.073.070.067.164.2
SUCTION PRESSURE AT SERVICE PORT PSIG.
TEMP. ˚F
61.5
SUPERHEAT
(MEASURED AT LOW-SIDE SERVICE PORT)
TABLE II-REQUIRED SUCTION TUBE TEMPERATURE ˚F
LOGIC
T1 T3
T2
IFR
C
R
*LLS
LOGIC
T1 T3
T2
*CHS
RED or BLK
*CHS
FACTORY POWER WIRING
FACTORY CONTROL WIRING
FIELD CONTROL WIRING
FIELD POWER WIRING
COMPONENT CONNECTION
FIELD SPLICE
JUNCTION
CONT CONTACTOR
CAP CAPACITOR (DUAL RUN)
*CH CRANKCASE HEATER
*CHS CRANKCASE HEATER SWITCH
COMP COMPRESSOR
*CTD COMPRESSOR TIME DELAY
*DTS DISCHARGE TEMP. SWITCH
*HPS HIGH PRESSURE SWITCH
IFR INDOOR FAN RELAY
*LLS LIQ. LINE SOLENOID VALVE
*LPS LOW PRESSURE SWITCH
OFM OUTDOOR FAN MOTOR
*SC START CAPACITOR
*SR START RELAY
*ST START THERMISTOR
* MAY BE FACTORY OR FIELD
INSTALLED.
NOTES:
-LEGEND-
CAU
TIO
N
BLK
Copyright 2004 CARRIER Corp. • 7310 W. Morris St. • Indianapolis, IN 46231 38brc5w
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4
Tab 2a 3a PC 101 Catalog No. 533-80109 Printed in U.S.A. Form 38BRC-5W Pg 2 2-04 Replaces: 38BRC-4W

Other manuals for 38BRC

2

This manual suits for next models

1

Other Carrier Air Conditioner manuals

Carrier 38QUS009DS User manual

Carrier

Carrier 38QUS009DS User manual

Carrier 40TGF UP Series User manual

Carrier

Carrier 40TGF UP Series User manual

Carrier 50CD/CH Dimensions and installation guide

Carrier

Carrier 50CD/CH Dimensions and installation guide

Carrier 42GCVPH010-303P User manual

Carrier

Carrier 42GCVPH010-303P User manual

Carrier 50NF Manual

Carrier

Carrier 50NF Manual

Carrier 00EFN900003000A User manual

Carrier

Carrier 00EFN900003000A User manual

Carrier 38GJ Series Original instructions

Carrier

Carrier 38GJ Series Original instructions

Carrier 40KQV050-7 User manual

Carrier

Carrier 40KQV050-7 User manual

Carrier WeatherMaster 50HC04 Installation and user guide

Carrier

Carrier WeatherMaster 50HC04 Installation and user guide

Carrier 50PG03-07 User manual

Carrier

Carrier 50PG03-07 User manual

Carrier 48TJD008-014 Dimensions and installation guide

Carrier

Carrier 48TJD008-014 Dimensions and installation guide

Carrier GZ024 User manual

Carrier

Carrier GZ024 User manual

Carrier WEATHERMASTER 36TE User manual

Carrier

Carrier WEATHERMASTER 36TE User manual

Carrier 40SMC N Series Technical Document

Carrier

Carrier 40SMC N Series Technical Document

Carrier AIRSTREAM 42BHE Operation manual

Carrier

Carrier AIRSTREAM 42BHE Operation manual

Carrier 42PQV050S User manual

Carrier

Carrier 42PQV050S User manual

Carrier 42TVAB010 User manual

Carrier

Carrier 42TVAB010 User manual

Carrier 40GXC User manual

Carrier

Carrier 40GXC User manual

Carrier 38MGQ Series User manual

Carrier

Carrier 38MGQ Series User manual

Carrier CA16NA 018-061 Operation manual

Carrier

Carrier CA16NA 018-061 Operation manual

Carrier Air-L Series User manual

Carrier

Carrier Air-L Series User manual

Carrier 42N S Series User manual

Carrier

Carrier 42N S Series User manual

Carrier 38AKS013-024 Dimensions and installation guide

Carrier

Carrier 38AKS013-024 Dimensions and installation guide

Carrier 38ASB Series Dimensions and installation guide

Carrier

Carrier 38ASB Series Dimensions and installation guide

Popular Air Conditioner manuals by other brands

Fujitsu ASYG 09 LLCA installation manual

Fujitsu

Fujitsu ASYG 09 LLCA installation manual

Frigidaire FFRE0533S1E0 Use & care guide

Frigidaire

Frigidaire FFRE0533S1E0 Use & care guide

Haier HDU-42HT03/H Operating & installation manual

Haier

Haier HDU-42HT03/H Operating & installation manual

Panasonic CU-QE12MKE Service manual

Panasonic

Panasonic CU-QE12MKE Service manual

LG LS-J0761CL Service manual

LG

LG LS-J0761CL Service manual

Haier AB052MAERA Operation & installation manual

Haier

Haier AB052MAERA Operation & installation manual

Mitsubishi Electric MS-GK36VAT operating instructions

Mitsubishi Electric

Mitsubishi Electric MS-GK36VAT operating instructions

Panasonic CS-KE12NB41 installation instructions

Panasonic

Panasonic CS-KE12NB41 installation instructions

Tecumseh TC300 SERIES Operator's manual

Tecumseh

Tecumseh TC300 SERIES Operator's manual

Admiral AW-05CM1FLU use and care manual

Admiral

Admiral AW-05CM1FLU use and care manual

Daikin FTKS40JVLT Service manual

Daikin

Daikin FTKS40JVLT Service manual

Tycoon TS2MVI32-09 Service manual

Tycoon

Tycoon TS2MVI32-09 Service manual

LG LMU365HV Specifications

LG

LG LMU365HV Specifications

Diplomat DX-80CHRC instruction manual

Diplomat

Diplomat DX-80CHRC instruction manual

Daikin RXYQ72PAYD installation manual

Daikin

Daikin RXYQ72PAYD installation manual

Kaden KSI R32 owner's manual

Kaden

Kaden KSI R32 owner's manual

Kenmore 405.84086 Use & care manual

Kenmore

Kenmore 405.84086 Use & care manual

Sanyo KS1822 Service manual

Sanyo

Sanyo KS1822 Service manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.