manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Carrier
  6. •
  7. Air Conditioner
  8. •
  9. Carrier 52M Performance Series Manual

Carrier 52M Performance Series Manual

24ABB3
BasetSeries Air Conditioner with Puronr
1 --- 1 / 2 t o 5 N o m i n a l To n s
Single and Three Phase
Wiring Diagrams
NOTES:
1. Symbols are electrical representation only.
2. Compressor and fan motor furnished with inherent thermal protection.
3. To be wired in accordance with National Electric N.E.C. and local codes.
4. N.E.C. class 2, 24 V circuit, min. 40 VA required, 60 VA on units installed with LLS.
5. Use copper conductors only. Use conductors suitable for at least 75ºC (167ºF).
6. Connection for typical cooling only thermostat. For other arrangements see installation instructions.
7. If indoor section has a transformer with a grounded secondary, connect the grounded
side to the BRN/YEL lead.
8. When start relay and start capacitor are installed, start thermistor is not used.
9. CH not used on all units.
10. If any of the original wire, as supplied must be replaced, use the same or equivalent wire.
11. Check all electrical connections inside control box for tightness.
12. Do not attempt to operate unit until service valves have been opened.
13. Do not rapid cycle compressor. Compressor must be off 3 minutes to allow pressures to equalize
between high and low side before starting.
14. Wire not present if HPS, LPS or CTD are used.
CONNECTION DIAGRAM
1. Compressor damage may occur if system is over charged.
2. This unit is factory charged with R-410A in accordance with
the amount shown on the rating plate. The charge is
adequate for most systems using matched coils and tubing
not over 15 feet long. Check refrigerant charge for maximum
efficiency. See Product Data Literature for required Indoor
air Flow Rates and for use of line lengths over 15 feet.
3. Relieve pressure and recover all refrigerant before system
repair or final disposal. Use all service ports and open all
flow-control devices, including solenoid valves.
4. Never vent refrigerant to atmosphere. Use approved
recovery equipment.
330440-101 REV. F
* MAY BE FACTORY INSTALLED
LEGEND
FACTORY POWER WIRING
FACTORY CONTROL WIRING
FIELD CONTROL WIRING
FIELD POWER WIRING
COMPONENT CONNECTION
FIELD SPLICE
JUNCTION
CONT
CAP
*CH
*CHS
COMP
*CTD
*DTS
*HPS
IFR
*LLS
*LPS
OFM
*SC
*SR
*ST
CONTACTOR
CAPACITOR (DUAL RUN)
CRANKCASE HEATER
CRANKCASE HEATER SWITCH
COMPRESSOR
COMPRESSOR TIME DELAY
DISCHARGE TEMP SWITCH
HIGH PRESSURE SWITCH
INDOOR FAN RELAY
LIQ LINE SOLENOID VALVE
LOW PRESSURE SWITCH
OUTDOOR FAN MOTOR
START CAPICATOR
START RELAY
START THERMISTOR
CAUTION
BLK
or
RED
*CH
RED or BLK
BLK
YEL
YEL
COMP
BLK
BLU CAP
YEL
BLU
BLU
YEL
*ST
BRN
*SR
OFM BRN
BRN/YEL
BLK
BLK
208/230 1Ø
POWER
SUPPLY
GND
EQUIP
+t
L1
L2
H
C
F
YEL
VIO
YEL/ BLU
(NOTE #14)
(NOTE #9)
(NOTE #8)
INDOOR BLOWER MOTOR
EXTERNAL
POWER
SUPPLY
24 V
(NOTE #3)
INDOOR THERMOSTAT (NOTE #6)
R
G
Y
*LLS
BLK
BLK
12
5
S
C
R
C
R
*SC
*CHS
BLK
*LPS *DTS
BLK BLK
*CTD
LOGIC
T1 T3
T2
YEL/PNK BLU/PNK
BLK
YEL/ BLU
BRN/YEL
*HPS
YEL/PNK BLU/PNK
CONT
11 21
23
23
SCHEMATIC DIAGRAM (LADDER FORM)
L1
*SR
*SC
H
COMP
*ST
C
FCAP
OFM
L2
52
1
*LPS
* CTD
*DTS
*LLS
IFR
THERMOSTAT
INDOOR
Y
G
RC
R
EXTERNAL POWER SUPPLY 24 V
(NOTE #14)
+t
LOGIC
T1 T3
T2
CONT
S
CR
*HPS
EQUIP
GND
*CH
*CHS
11 21
CONT
CONT
23 23
COOLING ONLY
CHARGING PROCEDURE
1. Only use sub cooling charging method
when OD ambient is greater than 70ºF
and less than 100ºF, indoor temp is
greater than 70ºF and less than 80ºF, and
line set is less than 80 ft.
2. Operate unit a minimum of 15 minutes before
checking the charge.
3. Measure liquid service valve pressure by
attaching an accurate gauge to the
service port.
4. Measure the liquid line temperature by
attaching an accurate thermistor type or
electronic thermometer to the liquid line
near the outdoor coil.
5. Refer to unit rating plate for required
subcooling temperature.
6. Find the point where the required subcooling
temperature intersects the measured liquid
service valve pressure.
7. To obtain the required subcooling temperature
at specific liquid line pressure, add refrigerant
if liquid line temperature is higher than indicated.
When adding refrigerant, charge in liquid form
using a flow restricting device into suction
service port. Recover refrigerant if temperature
is lower. Allow a tolerance of +/- 3ºF.
CONDENSING UNIT CHARGING INSTRUCTIONS
For use with units using R-410A refrigerant
REQUIRED LIQUID LINE TEMPERATURE
Required Subcooling
Temperature (ºF)
Liquid Pressure
at Service
Valve (psig)
6810 12 14
16
251
259
266
274
283
291
299
308
317
326
335
345
354
364
374
76 74 72 70 68
78 76 74 72 70
80 78 76 74 72
82 80 78 76 74
84 82 80 78 76
86 84 82 80 78
88 86 84 82 80
90 88 86 84 82
92 90 88 86 84
94 92 90 88 86
96 94 92 90 88
98 96 94 92 90
100 98 96 94 92
102 100 98 96 94
104 102 100 98 96
384
395
406
416
427
439
450
462
474
106 104 102 100 98
108 106 104 102 100
110 108 106 104 102
112 110 108 106 104
114 112 110 108 106
116 114 112 110 108
118 116 114 112 110
120 118 116 114 112
122 120 118 116 114
78
80
82
84
86
88
90
92
94
96
98
100
102
104
106
108
110
112
114
116
118
120
122
124
Fig. 1 – Wiring Diagram — Model sizes 1--1/2 -- 5 tons, 208/230--1
2
NOTES:
1. Symbols are electrical
representation only.
2. Compressor and fan motor
furnished with inherent
thermal protection.
3. To be wired in accordance
with National Electric
N.E.C. and local codes.
4. N.E.C. class 2, 24 V circuit,
min. 40 VA required,
60 VA on units installed
with LLS.
5. Use copper conductors
only. Use conductors
suitable for at least
75ºC (167ºF).
6. Connection for typical
cooling only thermostat.
For other arrangements
see installation instructions.
7. If indoor section has a
transformer with a
grounded secondary,
connect the grounded
side to the BRN/YEL lead.
8. If any of the original wire,
as supplied must be
replaced, use the same or
equivalent wire.
9. Check all electrical
connections inside control
box for tightness.
10. Do not attempt to operate
unit service valves have
been opened.
11. Do not rapid cycle
compressor.
Compressor must be off
3 minutes to allow
pressures to equalize
between high and low
side before starting.
12. It is imperative to connect
3Ø field power to unit with
correct phasing. The
Phase Rotation Monitor
will not allow the contactor
to be energized if the
phasing is not correct. If
phasing is reversed,
simply inter change any
two of the three power
connections on field side.
CONNECTION DIAGRAM
SCHEMATIC DIAGRAM (LADDER FORM)
1. Compressor damage may occur if system is
over charged.
2. This unit is factory charged with R-410A in
accordance with the amount shown on the
rating plate. The charge is adequate for most
systems using matched coils and tubing not
over 15 feet long. Check refrigerant charge
for maximum efficiency. See Product Data
Literature for required Indoor air Flow Rates
and for use of line lengths over 15 feet.
3. Relieve pressure and recover all refrigerant
before system repair or final disposal. Use all
service ports and open all flow-control
devices, including solenoid valves.
4. Never vent refrigerant to atmosphere. Use
approved recovery equipment.
335874-101 REV.A
* MAY BE FACTORY INSTALLED
LEGEND
FACTORY POWER WIRING
FACTORY CONTROL WIRING
FIELD CONTROL WIRING
FIELD POWER WIRING
COMPONENT CONNECTION
FIELD SPLICE
JUNCTION
CONT
CAP
*CH
*CHS
COMP
*CTD
*HPS
IFR
*LLS
*LPS
OFM
PRM
CONTACTOR
CAPACITOR (DUAL RUN)
CRANKCASE HEATER
CRANKCASE HEATER SWITCH
COMPRESSOR
COMPRESSOR TIME DELAY
HIGH PRESSURE SWITCH
INDOOR FAN RELAY
LIQ LINE SOLENOID VALVE
LOW PRESSURE SWITCH
OUTDOOR FAN MOTOR
PHASE ROTATION MONITOR
CAUTION
OFM
208/230 3Ø
OR
460 3Ø
POWER
SUPPLY
GNDEQUIP
L1
L3
*LPS
BLU/PNK
* CTD
*HPS
INDOOR BLOWER MOTOR
EXTERNAL
POWER
SUPPLY
24 V
(NOTE #3)
R
G
Y
BRN/YEL
YEL/PNK BLU/PNK
YEL/PNK
*LLS
BLK
BLK
LOGIC
T1 T3
T2
C
R
T2
T1
T3
BLK
YEL
YEL
BLK
YEL
CAP
COMP
* CH
IFR
L2 RED or BLK
RED or BLK
BRN
L1
EQUIP
GND
*LPS
* CTD
*LLS
IFR
INDOOR
THERMOSTAT
Y
G
R
C
R
EXTERNAL POWER SUPPLY 24 V
LOGIC
T1 T3
T2
L2
CONT
*CHS
BLK
CAP
COMP
T3
T1 T2
L3
OFM
BLU
INDOOR THERMOSTAT (NOTE #6)
VIO
BLK
BRN/YEL
BLU
L3
L1 L2
CONT 24 COM
PRM
L3 L1
L2
PRM
YEL/BLU
BRN/YEL
BLU
BLK
YEL
OFF: NO 24VAC
ON: OK
FLASH: PHASE PROBLEM
NOTE
*HPS
PRM LED INDICATOR
PRM
CONT 24V COM
*CH
*CHS
CONT
11 21
23
13
11 21
CONT
23 13
CONT
CONDENSING UNIT CHARGING INSTRUCTIONS
For use with units using R-410A refrigerant
COOLING ONLY
CHARGING PROCEDURE
1. Only use sub cooling charging method
when OD ambient is greater than 70ºF
and less than 100ºF, indoor temp is
greater than 70ºF and less than 80ºF,
and line set is less than 80 ft.
2. Operate unit a minimum of 15 minutes
before checking the charge.
3. Measure liquid service valve pressure by
attaching an accurate gauge to the
service port.
4. Measure the liquid line temperature by
attaching an accurate thermistor type or
electronic thermometer to the liquid line
near the outdoor coil.
5. Refer to unit rating plate for required
subcooling temperature.
6. Find the point where the required sub-
cooling temperature intersects the
measured liquid service valve pressure.
7. To obtain the required subcooling
temperature at specific liquid line
pressure, add refrigerant if liquid line
temperature is higher than indicated.
When adding refrigerant, charge in liquid
form using a flow restricting device into
suction service port. Recover refrigerant
if temperature is lower. Allow a tolerance
of +/- 3ºF.
REQUIRED LIQUID LINE TEMPERATURE
Required Subcooling
Temperature (ºF)
Liquid Pressure
at Service
Valve (psig)
6810 12 14
16
251
259
266
274
283
291
299
308
317
326
335
345
354
364
374
76 74 72 70 68
78 76 74 72 70
80 78 76 74 72
82 80 78 76 74
84 82 80 78 76
86 84 82 80 78
88 86 84 82 80
90 88 86 84 82
92 90 88 86 84
94 92 90 88 86
96 94 92 90 88
98 96 94 92 90
100 98 96 94 92
102 100 98 96 94
104 102 100 98 96
384
395
406
416
427
439
450
462
474
106 104 102 100 98
108 106 104 102 100
110 108 106 104 102
112 110 108 106 104
114 112 110 108 106
116 114 112 110 108
118 116 114 112 110
120 118 116 114 112
122 120 118 116 114
78
80
82
84
86
88
90
92
94
96
98
100
102
104
106
108
110
112
114
116
118
120
122
124
Fig. 2 – Wiring Diagram — Model size 2--1/2 -- 5 tons, 208/230--3 and Model size 3 -- 5 tons, 460/3
3
NOTES:
1. Symbols are electrical
representation only.
2. Compressor and fan motor
furnished with inherent
thermal protection.
3. To be wired in accordance
with National Electric
N.E.C. and local codes.
4. N.E.C. class 2, 24 V circuit,
min. 40 VA required,
60 VA on units installed
with LLS.
5. Use copper conductors
only. Use conductors
suitable for at least
75ºC (167ºF).
6. Connection for typical
cooling only thermostat.
For other arrangements
see installation instructions.
7. If indoor section has a
transformer with a
grounded secondary,
connect the grounded
side to the BRN/YEL lead.
8. If any of the original wire,
as supplied must be
replaced, use the same or
equivalent wire.
9. Check all electrical
connections inside control
box for tightness.
10. Do not attempt to operate
unit service valves have
been opened.
11. Do not rapid cycle
compressor.
Compressor must be off
3 minutes to allow
pressures to equalize
between high and low
side before starting.
12. It is imperative to connect
3Ø field power to unit with
correct phasing. The
Phase Rotation Monitor
will not allow the contactor
to be energized if the
phasing is not correct. If
phasing is reversed,
simply inter change any
two of the three power
connections on field side.
CONNECTION DIAGRAM
SCHEMATIC DIAGRAM (LADDER FORM)
1. Compressor damage may occur if system is
over charged.
2. This unit is factory charged with R-410A in
accordance with the amount shown on the
rating plate. The charge is adequate for most
systems using matched coils and tubing not
over 15 feet long. Check refrigerant charge
for maximum efficiency. See Product Data
Literature for required Indoor air Flow Rates
and for use of line lengths over 15 feet.
3. Relieve pressure and recover all refrigerant
before system repair or final disposal. Use all
service ports and open all flow-control
devices, including solenoid valves.
4. Never vent refrigerant to atmosphere. Use
approved recovery equipment.
335875-101 REV. A
* MAY BE FACTORY INSTALLED
LEGEND
FACTORY POWER WIRING
FACTORY CONTROL WIRING
FIELD CONTROL WIRING
FIELD POWER WIRING
COMPONENT CONNECTION
FIELD SPLICE
JUNCTION
CONT
CAP
*CH
*CHS
COMP
*CTD
*HPS
IFR
*LLS
*LPS
OFM
CONTACTOR
CAPACITOR
CRANKCASE HEATER
CRANKCASE HEATER SWITCH
COMPRESSOR
COMPRESSOR TIME DELAY
HIGH PRESSURE SWITCH
INDOOR FAN RELAY
LIQ LINE SOLENOID VALVE
LOW PRESSURE SWITCH
OUTDOOR FAN MOTOR
CAUTION
*LPS
BLU/PNK
* CTD
*HPS
INDOOR BLOWER MOTOR
EXTERNAL
POWER
SUPPLY
24 V
(NOTE #3)
R
G
Y
BRN/YEL
YEL/PNK BLU/PNK
YEL/PNK
*LLS
BLK
BLK
LOGIC
T1 T3
T2
C
R
IFR
*LPS
* CTD
*LLS
IFR
INDOOR
THERMOSTAT
Y
G
R
C
R
EXTERNAL POWER SUPPLY 24 V
LOGIC
T1 T3
T2
CONT
INDOOR THERMOSTAT (NOTE #6)
VIO
BLK
BRN/YEL
*HPS
L1
EQUIP
GND
L2 L3
*CH
OFM
COMP
CAP
T2
T1
T3
L1
L3
L2
OFM
575 3Ø
POWER
SUPPLY
GND
EQUIP
T2
T1
T3
BLK
YEL
YEL
BLU
BLK
YEL
CAP
COMP
RED or BLK
RED or BLK
*CH
BRN
CONT
12 22
11 21
13 23
11 21
CONT
23 13
CONT
22 12
CONT
CONDENSING UNIT CHARGING INSTRUCTIONS
For use with units using R-410A refrigerant
COOLING ONLY
CHARGING PROCEDURE
1. Only use sub cooling charging method
when OD ambient is greater than 70ºF
and less than 100ºF, indoor temp is
greater than 70ºF and less than 80ºF,
and line set is less than 80 ft.
2. Operate unit a minimum of 15 minutes
before checking the charge.
3. Measure liquid service valve pressure by
attaching an accurate gauge to the
service port.
4. Measure the liquid line temperature by
attaching an accurate thermistor type or
electronic thermometer to the liquid line
near the outdoor coil.
5. Refer to unit rating plate for required
subcooling temperature.
6. Find the point where the required sub-
cooling temperature intersects the
measured liquid service valve pressure.
7. To obtain the required subcooling
temperature at specific liquid line
pressure, add refrigerant if liquid line
temperature is higher than indicated.
When adding refrigerant, charge in liquid
form using a flow restricting device into
suction service port. Recover refrigerant
if temperature is lower. Allow a tolerance
of +/- 3ºF.
REQUIRED LIQUID LINE TEMPERATURE
Required Subcooling
Temperature (ºF)
Liquid Pressure
at Service
Valve (psig)
6810 12 14
16
251
259
266
274
283
291
299
308
317
326
335
345
354
364
374
76 74 72 70 68
78 76 74 72 70
80 78 76 74 72
82 80 78 76 74
84 82 80 78 76
86 84 82 80 78
88 86 84 82 80
90 88 86 84 82
92 90 88 86 84
94 92 90 88 86
96 94 92 90 88
98 96 94 92 90
100 98 96 94 92
102 100 98 96 94
104 102 100 98 96
384
395
406
416
427
439
450
462
474
106 104 102 100 98
108 106 104 102 100
110 108 106 104 102
112 110 108 106 104
114 112 110 108 106
116 114 112 110 108
118 116 114 112 110
120 118 116 114 112
122 120 118 116 114
78
80
82
84
86
88
90
92
94
96
98
100
102
104
106
108
110
112
114
116
118
120
122
124
Fig. 3 – Wiring Diagram — Model size 3 -- 5 tons, 575/3
4
Copyright 2009 Carrier Corp. S7310 W. Morris St. SIndianapolis, IN 46231
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Catalog No: 24ABB3---1W
Replaces:New
Printed in U.S.A. Edition Date: 09/09

Other manuals for 52M Performance Series

4

This manual suits for next models

1

Other Carrier Air Conditioner manuals

Carrier 48LCB07 User guide

Carrier

Carrier 48LCB07 User guide

Carrier 42TGF BP Series User manual

Carrier

Carrier 42TGF BP Series User manual

Carrier 51KPD09N7S User manual

Carrier

Carrier 51KPD09N7S User manual

Carrier 48TC 17 Series Installation and user guide

Carrier

Carrier 48TC 17 Series Installation and user guide

Carrier CPFILTRK007A00 User manual

Carrier

Carrier CPFILTRK007A00 User manual

Carrier 38GJ Series Original instructions

Carrier

Carrier 38GJ Series Original instructions

Carrier GR-45 Operation manual

Carrier

Carrier GR-45 Operation manual

Carrier bryant 619PHB User manual

Carrier

Carrier bryant 619PHB User manual

Carrier 40KQM012 User manual

Carrier

Carrier 40KQM012 User manual

Carrier 42BJ ULTRA User manual

Carrier

Carrier 42BJ ULTRA User manual

Carrier KC_141P User manual

Carrier

Carrier KC_141P User manual

Carrier Infinity 24VNA0 User manual

Carrier

Carrier Infinity 24VNA0 User manual

Carrier CA16NA 018-061 Operation manual

Carrier

Carrier CA16NA 018-061 Operation manual

Carrier 51CM Operating instructions

Carrier

Carrier 51CM Operating instructions

Carrier 38BK-009 User manual

Carrier

Carrier 38BK-009 User manual

Carrier Air V User manual

Carrier

Carrier Air V User manual

Carrier 50HJ015-025 Dimensions and installation guide

Carrier

Carrier 50HJ015-025 Dimensions and installation guide

Carrier XCT Series Installation instructions

Carrier

Carrier XCT Series Installation instructions

Carrier 42TSV052P1 User manual

Carrier

Carrier 42TSV052P1 User manual

Carrier 38MGQ Series User manual

Carrier

Carrier 38MGQ Series User manual

Carrier WeatherMaker 48FC04-07 User manual

Carrier

Carrier WeatherMaker 48FC04-07 User manual

Carrier Aura User manual

Carrier

Carrier Aura User manual

Carrier 38AD User manual

Carrier

Carrier 38AD User manual

Carrier 42TVU016 User manual

Carrier

Carrier 42TVU016 User manual

Popular Air Conditioner manuals by other brands

Daikin EWAQ004BAVP Installer's reference guide

Daikin

Daikin EWAQ004BAVP Installer's reference guide

Retro Aire R30C Installation, operation & maintenance manual

Retro Aire

Retro Aire R30C Installation, operation & maintenance manual

Daikin R32 Split Series installation manual

Daikin

Daikin R32 Split Series installation manual

Sealey sac9000.V3 instruction manual

Sealey

Sealey sac9000.V3 instruction manual

Daikin FTKS50EV1B Operation manual

Daikin

Daikin FTKS50EV1B Operation manual

S2P KS2P-18C210 owner's manual

S2P

S2P KS2P-18C210 owner's manual

Soleus Air GB-PAC-08E4 operating instructions

Soleus Air

Soleus Air GB-PAC-08E4 operating instructions

Panasonic PZ2 Series operating instructions

Panasonic

Panasonic PZ2 Series operating instructions

York DJ 300 Technical guide

York

York DJ 300 Technical guide

OMAS Air-Fi AFT7 Installer and User Instruction Manual

OMAS

OMAS Air-Fi AFT7 Installer and User Instruction Manual

Trane TTK060K4 Product bulletin

Trane

Trane TTK060K4 Product bulletin

Gree GWHD(14)NK6OO(LC)(LH) Service manual

Gree

Gree GWHD(14)NK6OO(LC)(LH) Service manual

Frigidaire FAS155K1A1 Factory parts catalog

Frigidaire

Frigidaire FAS155K1A1 Factory parts catalog

Samsung AC024JXADCH installation manual

Samsung

Samsung AC024JXADCH installation manual

Nordyne WARRCOIL01 quick start guide

Nordyne

Nordyne WARRCOIL01 quick start guide

QuietCool QC18DVS owner's manual

QuietCool

QuietCool QC18DVS owner's manual

Fortress Technologies FWAC08M16 user manual

Fortress Technologies

Fortress Technologies FWAC08M16 user manual

Hisense APC09 Use and Installation Instructions

Hisense

Hisense APC09 Use and Installation Instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.