Table 1 – RTU Open Inputs and Outputs
POINT NAME BACnet OBJECT
NAME TYPE OF I/O CONNECTION PIN
NUMBER(S) CHANNEL DESIGNATION
DEDICATED INPUTS
Space Temp / Zone Temp zone_temp AI (10K Thermistor) J 2 0 --- 1 & 2 Analog Input 10
Supply Air Temperature sa_temp AI (10K Thermistor) J 2 --- 1 & 2 Analog Input 6
Outside Air Temperature oa_temp AI (10K Thermistor) J 2 --- 3 & 4 Analog Input 7
Space Temperature Offset Pot stpt_adj_offset AI (100K Potentiometer) J 2 0 --- 3 & 4 Analog Input 11
Safety Chain Feedback safety_status BI (24 VAC) J 1 --- 9 Binary Input 4
Compressor Safety Status (1) comp_status BI (24 VAC) J 1 --- 2 Binary Input 3
Fire Shutdown Status firedown_status BI (24 VAC) J 1 --- 1 0 Binary Input 5
Enthalpy Status enthalpy_status BI (24 VAC) J 2 --- 6 & 7 Binary Input 8
Humidistat Input Status humstat_status BI (24 VAC) J 5 --- 7 & 8 Binary Input 9
Zone Temperature n/a n/a J 1 3 --- 1 --- 4 Rnet
CONFIGURABLE INPUTS (4)
Indoor Air CO2 iaq A I ( 4 --- 2 0 m A )
J 4 --- 2 & 3 o r J 4 --- 5 & 6
Analog Input 2
Outdoor Air CO2 oaq A I ( 4 --- 2 0 m A ) Analog Input 1
Space Relative Humidity space_rh A I ( 4 --- 2 0 m A ) Analog Input 10
Supply Fan Status (2) sfan_status BI (24 VAC)
J 5 --- 1 & 2 o r J 5 --- 3 & 4,
J 5 --- 5 & 6 o r J 5 --- 7 & 8 (3)
BinaryInput3,5,8,or9,exceptwhereintrinsicinputisused
Filter Status (2) filter_status BI (24 VAC) BinaryInput3,5,8,or9,exceptwhereintrinsicinputisused
Door Contact (2) door_contact_status BI (24 VAC) BinaryInput3,5,8,or9,exceptwhereintrinsicinputisused
Remote Occupancy input (2) occ_contact_status BI (24 VAC) BinaryInput3,5,8,or9,exceptwhereintrinsicinputisused
IGC input (2) igcovr_status BI (24 VAC) Binary Input 9. Mandatory input on gas heat units.
OUTPUTS
Economizer Output econ_output AO (4 --- 20mA) J 2 --- 5 Analog Output 1
Supply Fan VFD vfd_output A O ( 2 --- 1 0 V d c) J 2 2 --- 1 & 2 Analog Output 2
Supply Fan Relay sfan BO Relay (24VAC, 1A) J 1 --- 4 Binary Output 1 (G)
Cool 1 Relay State comp_1 BO Relay (24VAC, 1A) J 1 --- 8 Binary Output 5 (Y1)
Cool 2 Relay State comp_2 BO Relay (24VAC, 1A) J 1 --- 7 Binary Output 4 (Y2)
Cool 3 Relay State comp_3 BO Relay (24VAC, 1A) J 1 1 --- 5 & 6 Binary Output 7 (Y3)
Heat 1 Relay State heat_1 BO Relay (24VAC, 1A) J 1 --- 6 Binary Output 3 (W1)
Heat 2 Relay State heat_2 BO Relay (24VAC, 1A) J 1 --- 5 Binary Output 2 (W2)
Power Exhaust Relay State pexh BO Relay (24VAC, 1A) J11---2&3(N.O.) Binary Output 8 (PE)
Dehumidification Relay dehum BO Relay (24VAC, 1A) J11---7&8(N.O.) Binary Output 6
(1) Safety Chain Feedback: 24Vac required at this terminal to provide “Run Enable” status. See Input/Output section for additional instructions.
(2) These inputs are configurable. If installed, they take the place of the default input on the specific channel. See appropriate Input Configuration Section for wiring and setup instructions.
(3) Pa r a l l e l p i n s J 5 --- 1 = J 2 --- 6 , J 5 --- 3 = J 1 --- 1 0 , J 5 --- 5 = J 1 --- 2 a r e u s e d f o r f i l e d i n s t a l l a t i o n .
(4) Refer to the input configuration and accessory sections for more detail.
Sensors and Accessories
The RTU Open controller is configurable with the
following field-supplied sensors:
NOTE: Supply air temperature sensor (33ZCSENSAT) is
factory-installed.
SSpace temperature sensor (ZS--CAR, ZS--C--CAR,
ZS--H--CAR, ZS--HC--CAR, ZSPL--C--CAR,
ZSPL--H--CAR, ZSPL--HC--CAR, ZSP--CAR,
ZSP--C--CAR, ZSP--H--CAR, ZSP--HC--CAR ,
33ZCT55SPT, 33ZCT56SPT, or 33ZCT59SPT)
SIndoor air quality sensor (ZS--C--CAR, ZS--HC--CAR,
Z S P L -- C -- C A R , Z S P L -- H C -- C A R , Z S P -- C -- C A R ,
ZSP--HC--CAR, 33ZCSPTCO2--01,
33ZCSPTCO2LCD--01, 33ZCT55CO2--02, or
33ZCT56CO2--02) required for demand control
ventilation.
SOutdoor air quality sensor (33ZCSPTCO2--01,
33ZCSPTCO2LCD--01)
SCO2aspirator box (C33ZCCASPCO2) required for CO2
return duct/outside air applications
SOutdoor air enthalpy switch (33CSENTHSW)
SReturn air enthalpy sensor (33CSENTSEN) required for
differential enthalpy control
SSpace relative humidity sensor (33ZCSENSRH-02)
SDuct relative humidity (33ZCSENDRH-02)
SHumidistat (--HL--38MG-029) (not permitted for use on
48LC 07--26 units due to same input as IGC input)
SSmoke Detectors (CRSMKSEN002A00,
CRSMKKIT002A00)
SFan and/or Filter Status (CRSTATUS001A00,
CRSTATUS005A00)
User Interfaces
SField Assistant (USB-TKIT required)
SWall mounted Equipment Touch
SWall mounted System Touch
Install Analog Sensors
Supply Air Sensor (SAT)
The factory supplies the discharge (supply) air sensor with
the unit and is pre--wired.
Unit/Size SAT Shipping Location/Installation Location
LC 04 --- 12
HC/TC 04--- 16
HCQ 04--- 12
T C Q 0 4 --- 1 4
The SAT is secured to the unit’s supply duct opening.
This sensor must be relocated into the supply duct
during unit installation.
LC 14 --- 26
HC 17 --- 24
TC/TCQ 17--- 30
The SAT is mounted through the side of the heat
chamber below the fan deck, and does NOT require
relocation.
OutdoorAirSensor(OAT)
The OAT is supplied with the economizer option or
accessory. It is wired through the 12-pin plug (PL6) in the
return air section of the unit and is mounted on the
economizer assembly.
Space Temperature Sensor (SPT)
There are 2 types of space temperature sensors available
from Carrier, resistive input non-communicating (T55, T56,
and T59) and Rnet communicating (ZS--CAR, ZS--C--CAR,
ZS--H--CAR, ZS--HC--CAR, ZSPL--C--CAR, ZSPL--H--CAR,
Z S P L -- H C -- C A R , Z S P -- C A R , Z S P -- C -- C A R , Z S P -- H -- C A R ,
ZSP--HC--CAR) sensors. Each type has a variety of options
consisting of: timed override button, set point adjustment, a
LCD screen, combination of humidity or CO2sensing and
communication tie in. Space temperature can be also be
written to from a building network or zoning system.
However, it is still recommended that return air duct sensor
be installed to allow stand-alone operation for back-up.
Refer to the configuration section for details on controller
configurations associated with space sensors.
48---50LHTCQ---01T