
Step 9—ACCESSORY INSTALLATION
ACCESSORY ELECTRIC HEATERS
Electric heaters may be installed with the 40FKA Fan Coil per
instructions supplied with the electric heater package.
NOTE: It is not necessary to cover the opening for accessory
heaters. The unit will perform properly without this opening
covered.
ELECTRONIC AIR CLEANER CONNECTIONS
Because the ICM2 blower motor used in the 40FKA Fan Coil is
controlled by low-voltage signals, a switched 230-vac electronic
air cleaner power signal is not available. This signal is replaced by
a 24-vac signal which is provided at PCB terminals AUX1 and
AUX 2 (See Fig. 17 and 19.) This signal is present whenever the
G thermostat signal is present (heat pump heating, cooling and
continuous blower modes). When the 40FKA Fan Coil is installed
with an electronic air cleaner, use EAC relay kit Part No.
KFAIR0201ACR or a field supplied 24-vac relay.
NOTE: The 40FKA blower operates in some modes without a G
signal.
If the 40FKA Fan Coil is installed with an air conditioner and
electic heat is the primary source of heat, install a thermostat which
turns on the G output with a call for heat or a corporate thermostat
with its "fan on with W operation" enabled to energize an air
cleaner or humidifier through the AUX and HUM outputs of the
Easy Select PC board. Alternately an airflow sensor may be
installed with the air cleaner.
HUMIDIFIER CONNECTIONS
Terminals HUM1 and HUM2 are provided for direct connection to
the low-voltage control of a humidifier through a standard humi-
distat. (See Fig. 17.) These terminals are energized with 24vac
when G thermostat signal is present. (See Fig. 18.) Alternately, the
24-vac signal may be sourced from the W and C terminal block
connections when electric heaters are used as the primary heating
source. When using a Thermidistat™ Control the 24-vac signal
may be sourced directly from the HUM terminal. (See Figs. 9, 10,
11, and 12.)
Step 10—40FKA Fan Coil Sequence Of Operation
The 40FKA will supply airflow in a range which is more than
twice the range of a standard fan coil. It is designed to provide
nominal cooling capacities at a 50°F evaporator temperature and
the required airflow which enables it to match with 4 air condi-
tioner or heat pump system sizes. Table 1 outlines the CFM range
for the different 40FKA Fan Coil sizes.
Table 1–CFM Range for 40FKA Units
FAN COIL SIZE SYSTEM SIZES CFM RANGE
40FKA002 018, 024, 030, 036 450-1275
40FKA003 024, 030, 036, 042 525-1475
40FKA005 030, 036, 042, 048 550-1700
40FKA006 036, 042, 048, 060 550-2150
CONTINUOUS FAN
1. Thermostat closes circuit R to G
The blower runs at continuous fan airflow.
COOLING MODE — SINGLE SPEED OR 2-SPEED HIGH
1. Thermostat closes circuits R to G, R to Y/Y2 and R to O
The fan coil delivers single speed cooling airflow.
2. Thermostat closes circuits R to G, R to Y1, R to Y2 and R to
O
The fan coil delivers 2-speed high cooling airflow.
COOLING MODE — 2-SPEED LOW
1. Thermostat closes circuits R to G, R to Y1 and R to O
The fan coil delivers 2-speed low cooling airflow.
COOLING MODE — DEHUMIDIFICATION
1. Thermostat or Thermidistat closes circuits R to G, R to O, and
R to Y/Y2 (or R to Y1 for 2-speed low), and humidistat or
Thermidistat opens R to DH
The fan coil delivers airflow which is approximately 80
percent of the nominal cooling airflow to increase the latent
capacity of the system.
COOLING MODE — SUPER DEHUMIDIFY OPERATION
NOTE: The indoor control used, such as a Thermidistat, must be
capable of providing Super Dehumidify operation mode and
control must be configured as outlined in its installation instruc-
tions. Consult indoor control literature to determine if control is
capable and for configuration instructions.
1. If the indoor temperature is below the temperature set point
and the humidity is greater than the humidity set point, the
Thermidistat closes circuit R to O, opens circuits R to DH and
R to G, and cycles circuit R to Y/Y2 (for single speed system
R to Y1, or R to Y1 and Y/Y2 for 2-speed system).
The ICM2 motor reads the G signal to the fan coil while the
heat pump is operating, circuit R to Y/Y2 for single speed
system, R to Y1 or R to Y1 and Y/Y2 for 2-speed system,
closed (24 vac). If circuit R to G is closed (24 vac), the
motor will deliver airflow at the full cooling or cooling plus
dehumidify mode requested value. If circuit R to G is open
(0 vac) for super dehumidify mode, the motor delivers
reduced airflow to maximize the humidity removal of the
system while minimizing overcooling.
ELECTRIC HEAT HEATING MODE
1. Thermostat closes circuit R to W/W1, or W2
The fan coil delivers the selected electric heat airflow.
HEAT PUMP HEATING MODE — SINGLE SPEED OR
2-SPEED HIGH
1. Thermostat closes circuits R to G and R to Y/Y2
The fan coil delivers single speed heat pump heating airflow.
2. Thermostat closes circuits R to G, R to Y1 and R to Y/Y2
The fan coil delivers 2-speed high heat pump heating airflow.
HEAT PUMP HEATING MODE — 2-SPEED LOW
1. Thermostat closes circuits R to G and R to Y1
The fan coil delivers 2-speed heat pump heating low airflow.
HEAT PUMP HEATING WITH AUXILIARY ELECTRIC
HEAT
1. Thermostat closes circuits R to G, R to Y/Y2 and/or R to Y1
with R to W/W1 or W2 (and R to O in the case of defrost)
In the event that electric heating is called for by the
thermostat while the heat pump is also operating in either
heating or defrost modes, the motor will modify its airflow
output, if necessary, to provide an airflow which is defined
as safe for the operation of the electric heater during heat
pump operation. That airflow is the greater of the heat pump
heating airflow and the electric heater only airflow.
Fig. 18 — Humidifier Wiring A95317
HUMIDISTAT
TO HUMIDIFIER
HUMIDIFIER WIRING
HUM 1
(C)
HUM 2
(G)
24-VAC
13