
humidity removal or if warmer heating air is desired. While
providing this improved comfort, the heat pump system will
operate efficiently, but not at the published ARI SEER or HSPF
efficiencies.
If the installed heat pump system uses Puron refrigerant, the fan
coil configuration below will provide excellent comfort, but DO
NOT activate the indoor control Super Comfort Heat configuration
option. Excessive use of the PressureGuard device could result in
its premature failure.
1. AUX HEAT KW/CFM — Select narrrowest heater range to
match size of electric heater installed (skip this step if no
heater is installed).
2. AC/HP SIZE — Select system size installed.
3. SYSTEM TYPE — Select system type HP-COMFORT (for
heat pump system) or AC (for air conditioner system).
4. AC/HP CFM ADJUST — Select LO.
5. ON/OFF DELAY — Select ENH profile.
6. CONTINUOUS FAN — Select desired fan speed when
thermostat is set to continuous fan.
7. If the fan coil is installed with Intelligent Heat Staging capable
electric heaters, remove jumper J2.
NOTE: If configuring to run Super Comfort Heat, do not remove
jumper J2 when using 5-, 8-, or 10-kw heaters.
8. Remove jumper J1 to activate dehumidify modes.
9. Wire low voltage connections for Comfort Options as shown
in Figs. 8, 9, 10, and 11.
10. Configure Thermidistat (or other Super Dehumidify/Super
Comfort Heat capable indoor control) following its installation
instructions for Super Dehumidify and Super Comfort Heat
operation.
This configuration provides the following comfort enhancements:
a. A 30 second blower on delay with 150 seconds at 70
percent airflow to allow the indoor coil to warm up or cool
down before the blower is asked to deliver 100 percent
airflow reducing the cold blow sensation at start up in
heating and allowing the indoor coil to more quickly reach
wet coil operating conditions in cooling.
b. No blower off delay eliminates cold blow which may be
associated with running the blower after shut down of the
compressor and avoids re-evaporation of condensed mois-
ture after cooling/dehumidifying operation.
c. Lower airflow while the compressor is running to reduce
draft effects and increase heating air temperature and
improved humidity control during cooling operation.
d. Intelligent Staging of the electric heater elements to more
closely match heating load requirements and provide more
consistent heating air temperatures.
Step 9—ACCESSORY INSTALLATION
ACCESSORY ELECTRIC HEATERS
Electric heaters may be installed with the 40FKA Fan Coil per
instructions supplied with the electric heater package.
NOTE: Units installed without elecric heat should have a field-
supplied sheet metal block off plate covering the heater opening.
This will reduce air leakage and formation of exterior condensa-
tion.
AUXILIARY TERMINALS
The AUX and HUM terminals on the Easy Select Board are tied
directly to the G terminal, and provide a 24-vac signal whenever
the G terminal is energized. (See Figs 16 and 19.) During Super
Comfort Heat and Superdehumidify modes, the G signal is not
present and the auxiliary terminals are not energized. If the
installation includes the use of these operation modes, it is
recommended you do not use these terminals to control accesso-
ries. See Electronic Air Cleaner and Humidifier sections for further
information.
ELECTRONIC AIR CLEANER (EAC) CONNECTIONS
The AUX1 and AUX2 terminals are not always energized during
blower operation, as described above. When using an electronic air
cleaner with the 40FKA Fan Coil and Super Comfort Heat or
Super Dehumidity modes, use Airflow Sensor Part No.
KEAAC0101AAA. The airflow sensor turns on electronic air
cleaner when the fan coil blower is operating.
HUMIDIFIER CONNECTIONS
The HUM1 and HUM2 terminals are not always energized during
blower operation, as described under Auxiliary Terminals Section.
To ensure humidifier will operate properly during Super Comfort
Heat mode, use HUM output of Thermidistat Control or Comfort
Zone II to control humidifier operation. Alternatively, the 24-vac
signal can be sourced from the W and C terminal block connec-
tions when electric heaters are used as the primary heating source,
or if another humidistat is desired to control the humidifier. (See
Figs. 8, 9, 10, and 11.)
Step 10—40FKA Fan Coil Sequence Of Operation
The 40FKA will supply airflow in a range which is more than
twice the range of a standard fan coil. It is designed to provide
nominal cooling capacities at a 50°F evaporator temperature and
the required airflow which enables it to match with 4 air condi-
tioner or heat pump system sizes. Table 6 outlines the CFM range
for the different 40FKA Fan Coil sizes.
Table 6—CFM Range for 40FKA Units
FAN COIL SIZE SYSTEM SIZES CFM RANGE
40FKA002 018, 024, 030, 036 450-1275
40FKA003 024, 030, 036, 042 525-1475
40FKA005 030, 036, 042, 048 550-1700
40FKA006 036, 042, 048, 060 550-2150
CONTINUOUS FAN
1. Thermostat closes circuit R to G
The blower runs at continuous fan airflow.
COOLING MODE — SINGLE SPEED OR 2-SPEED HIGH
1. Thermostat closes circuits R to G, R to Y/Y2 and R to O
The fan coil delivers single speed cooling airflow.
2. Thermostat closes circuits R to G, R to Y1, R to Y2 and R to
O
The fan coil delivers 2-speed high cooling airflow.
COOLING MODE — 2-SPEED LOW
1. Thermostat closes circuits R to G, R to Y1 and R to O
The fan coil delivers 2-speed low cooling airflow.
COOLING MODE — DEHUMIDIFICATION
1. Thermostat or Thermidistat closes circuits R to G, R to O, and
R to Y/Y2 (or R to Y1 for 2-speed low), and humidistat or
Thermidistat opens R to DH
The fan coil delivers airflow which is approximately 80
percent of the nominal cooling airflow to increase the latent
capacity of the system.
COOLING MODE — SUPER DEHUMIDIFY OPERATION
NOTE: The indoor control used, such as a Thermidistat, must be
capable of providing Super Dehumidify operation mode and
control must be configured as outlined in its installation instruc-
tions. Consult indoor control literature to determine if control is
capable and for configuration instructions.
13
→
→
→