manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Carrier
  6. •
  7. Thermostat
  8. •
  9. Carrier 33CS User manual

Carrier 33CS User manual

A Guide To Operating
Your TEMP System
NOTE TO INSTALLER
This manual should be left with the equipment owner.
GENERAL
This manual will assist you in using your Carrier Comfort
System thermostat. There is one basic type of thermostat that
you may encounter. It is called a TEMP system thermostat
and may be equipped with or without a timeclock.
The TEMPsystem thermostat can be identified by the sys-
tem switches (FAN, HEAT, COOL) which are located along
the bottom edge of the front cover. The TEMP system ther-
mostat can be equipped with or without a timeclock. The
timeclock display is located in the upper right corner. The
set point and room temperature display is located in the up-
per left corner. The set point and programming buttons are
located around the display.
There are three typical operations you may perform on
your TEMP system thermostat:
• change set points for heating and cooling
• override the unoccupied schedule
• change occupancy schedules
NOTE: Your ability to perform these functions may be lim-
ited by the security access level function which is config-
ured by the installer. If ‘‘access denied’’is shown on the dis-
play screen, you are not allowed to access that function.
OPERATION
Electronic Timeclock — To set the clock, remove the
cover of the thermostat. Two buttons, located under the time-
clock, are provided to set the clock. They are labeled select
and adjust. Press the select button. The minutes setting on
the clock will flash. Press the adjust button until the correct
minutes are shown. Press the select button. The hour setting
will flash. Press the adjust button until the correct hour is
shown (includingAM and PM). Press the select button again
and the day of the week will flash. Press the adjust button
until the correct day is shown. Press the select button to re-
turn to normal timeclock operation.
System Switches — The TEMPsystem thermostat op-
eration mode is controlled by 3 system switches: FAN, HEAT,
COOL. See Fig. 1.
The FAN switch can be set to ON or AUTO. When the
FAN switch set to ON, the fan will run continuously. When
the FAN switch is set toAUTO, the fan will only run during
heating and cooling.
The COOL switch can be set to OFF orAUTO. When the
COOL switch set to OFF, the TEMP system will not enter
cooling mode. When the COOL switch is set to AUTO, the
TEMP system will enter cooling mode when the zone tem-
perature rises above the cooling set point.
The HEAT switch can be set to OFF or AUTO. When the
HEAT switch set to OFF, the TEMP system will not enter
heating mode. When the HEAT switch is set to AUTO, the
TEMP system will enter heating mode when the zone tem-
perature drops below the heating set point.
TEMP System Thermostat with Timeclock TEMP System Thermostat without Timeclock
33CS
Carrier Comfort System
TEMP System
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4
Tab 11a 13a PC 111 Catalog No. 809-121 Printed in U.S.A. Form VTS-2SO Pg 1 9-95 Replaces: New
System Displays — The TEMP system thermostat has
a display window which is used to show system information
and for programming mode. See Fig. 1.
SET POINTDISPLAY —The heating and cooling set points
are shown in the display window during the normal display
mode. The heating and cooling set points are used to deter-
mine the range of temperatures that are maintained in the
zone.
The cooling set point buttons are located on the left side
of the display screen. The heating set point buttons are lo-
cated on the right side of the display screen.
MODE DISPLAY — When the system fan is energized, the
word FAN appears on the display screen.
When the cooling mode is energized, the word COOL ap-
pears on the display screen. The system fan will also be en-
ergized.
When the heating mode is energized, the word HEAT ap-
pears on the display screen. The system fan will also be en-
ergized, unless it is configured not to run during heating mode.
If the system enters IAQ (Indoor Air Quality) mode, the
word IA9 appears on the display screen.
ALTERNATE DISPLAY— By pressing both cooling or heat-
ing set point buttons simultaneously, the alternate informa-
tion display is activated. The TEMP system thermostat will
display the current zone temperature and then the time of
day. If theAlternate Display function has been configured to
ON, the TEMP system thermostat will show more detailed
zone information. The display will then return to normal.
Adjustment of Set Points — The cooling and heat-
ing set points are configured through the set point buttons.
The heating set point buttons are located on the right side
of the display screen. Press the upper button to raise the heat-
ing set point temperature. Press the lower button to lower
the heating set point temperature. The heating set point is
limited to a range of 66 to 80 F by the TEMP system.
The cooling set point buttons are located on the left side
of the display screen. Press the upper button to raise the cool-
ing set point temperature. Press the lower button to lower
the cooling set point temperature. The cooling set point is
limited to a range of 66 to 80 F by the TEMP system.
NOTE: The heating and cooling set point ranges can be con-
figured to smaller ranges.
The heating and cooling set points may be set for the same
temperature, but the thermostat will not allow the cooling
set point to be adjusted lower than the heating set point, or
the heating set point to be adjusted higher than the cooling
set point.
Operating Modes — The TEMPsystem thermostat has
3 operating modes: occupied mode, unoccupied mode, and
unoccupied override. Occupied mode is the mode used when
the area is normally occupied. Unoccupied mode is used to
conserve energy and is used when the area is normally un-
occupied. Unoccupied Override is used to temporarily over-
ride unoccupied mode when an area is in use during the un-
occupied schedule time. The user can manually activate
unoccupied override. Set points can be adjusted during both
occupied and unoccupied override modes.
The occupied schedule controls when the zone is in oc-
cupied or unoccupied mode. The schedule can be sent from
a device over the network, or it can be programmed at the
TEMP system thermostat.
UNOCCUPIED OVERRIDE — Unoccupied override is used
to temporarily change the system set points to the occupied
mode set points. An example of unoccupied override would
be a worker staying past 6:00 PM to finish a job when the
scheduled unoccupied time is 6:00 PM.
To override unoccupied mode, press a set point button.
The unoccupied display will be replaced with the occupied
mode display. The TEMP system thermostat will automati-
cally return to unoccupied mode when the override timer
expires.
Fig. 1 — TEMP System Thermostat Functions
2
Occupancy Schedule — The occupancy schedule es-
tablishes the time periods when the TEMP system thermo-
stat operates in the occupied or unoccupied mode.
The unoccupied/occupied schedule has individual 7-day
programming with 8 time periods. Unoccupied/occupied ON/
OFF times are entered on the minute. The start of an ON
time is the beginning of the occupied mode. The start of an
OFF time is the beginning of the unoccupied mode.
NOTE: If an ON time and an OFF time are set for the same
time, the TEMP system thermostat operates in unoccupied
mode for that entire period.
NOTE: Access to the occupancy schedule by certain users
may be limited through the security level access function.
CONFIGURATION OF SCHEDULES — The unoccupied/
occupied program can be directly configured at the TEMP
system thermostat. To configure the schedule, perform the
following:
1. Press both upper or lower set point buttons at the same
time to enter into the program mode. The word ‘‘cat-
egory’’and the number 1 will be displayed. See Fig. 2 for
the functions of the programming buttons.
2. Press the left upper set point button. The word ‘‘cat-
egory’’ and the number 2 will be displayed. Category 2
contains the occupied/unoccupied schedules for the TEMP
system thermostat.
3. The lower right set point button is the select button. Press
the select button. The word ‘‘category’’ will change to
‘‘option’’and the number 1 will be displayed. Category 2,
options 1 through 8 are the 8 different occupancy time
periods. Option 1 is occupied period 1. Option 2 is oc-
cupied period 2. The options continue to option 8 which
is occupancy period 8.
4. The start time for option 1 will be shown. Each occupied
period (options 2.1 through 2.8) will have three different
screens associated with it: start time, stop time, and ac-
tive days. Use the left set point buttons to scroll through
the start time, stop time, and active days for each option.
Press the select button (right lower set point button) to
modify the screen.
5. Configure the start time for category 2, option 1. When
the select button is pressed from the start time screen, the
hours number will flash. The hours are modified through
the left set point buttons. The AM/PM modifier will au-
tomatically switch when scrolling through the times. To
change the minutes, press the select button again. The min-
utes numbers will flash. Use the left set point buttons to
modify the minutes. Press select again to save the current
time and return to the options screen, or press escape (up-
per right set point button) to exit without saving changes.
6. Configure the stop time. Press the upper left set point but-
ton to advance to the stop time screen of category 2, op-
tion 1. Press the select button. The hours number will flash.
The hours are modified through the left set point buttons.
TheAM/PM modifier will automatically switch when scroll-
ing through the times. To change the minutes, press the
select button again. The minutes numbers will flash. Use
the left set point buttons to modify the minutes. Press se-
lect again to save the current time and return to the op-
tions screen, or press escape to exit without saving changes.
7. Configure the active days. Press the upper left set point
button to advance to the active days screen of category 2,
option 1. Press the select button. The active days will be
shown and the first day, M (Monday) will be blinking.
Use the left set point buttons to turn the day ON or OFF.
Use the select button to scroll through the possible active
days. The programmable days are: M (Monday),T (Tues-
day), W(Wednesday), TH (Thursday), F (Friday), SA(Sat-
urday), SU (Sunday), and H (Holiday). Press select again
to save the current active days and return to the options
screen, or press escape to exit without saving changes.
8. Repeat this procedure for each time period until the cor-
rect schedule has been programmed.
9. When the schedule is complete, press escape to exit the
programming mode. If no buttons are pressed for 3 min-
utes while in programming mode, the display will auto-
matically revert back to its standard operating mode.
INCREASE
VALUE
DECREASE
VALUE
PRESS BOTH TO ENTER
PROGRAMMING MODE ESCAPE SELECT
Fig. 2 — Programming Mode Buttons
3
Copyright 1995 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4
Tabe 11a 13a PC 111 Catalog No. 809-121 Printed in U.S.A. Form VTS-2SO Pg 4 9-95 Replaces: New

Other manuals for 33CS

18

Other Carrier Thermostat manuals

Carrier 33CS User manual

Carrier

Carrier 33CS User manual

Carrier Infinity SYSTXCCITC01-C User manual

Carrier

Carrier Infinity SYSTXCCITC01-C User manual

Carrier 53DFS250-SL User manual

Carrier

Carrier 53DFS250-SL User manual

Carrier 33CS420-01 User manual

Carrier

Carrier 33CS420-01 User manual

Carrier Programmable Dual Fuel Thermostats Instructions and recipes

Carrier

Carrier Programmable Dual Fuel Thermostats Instructions and recipes

Carrier TST-EEPC06111SCS00 User manual

Carrier

Carrier TST-EEPC06111SCS00 User manual

Carrier A94134 Instructions and recipes

Carrier

Carrier A94134 Instructions and recipes

Carrier SYSTXCCITN01-A Infinity User manual

Carrier

Carrier SYSTXCCITN01-A Infinity User manual

Carrier 33CSSP3-FC User manual

Carrier

Carrier 33CSSP3-FC User manual

Carrier PROGRAMMABLE THERMOSTAT Assembly instructions

Carrier

Carrier PROGRAMMABLE THERMOSTAT Assembly instructions

Carrier Comfort Non-Programmable User manual

Carrier

Carrier Comfort Non-Programmable User manual

Carrier Debonair 2 User manual

Carrier

Carrier Debonair 2 User manual

Carrier 33CS420-01 User manual

Carrier

Carrier 33CS420-01 User manual

Carrier Totaline Star P474-1010 User manual

Carrier

Carrier Totaline Star P474-1010 User manual

Carrier TSTTCCPB101 User manual

Carrier

Carrier TSTTCCPB101 User manual

Carrier Infinity SYSTXCCITW01 User manual

Carrier

Carrier Infinity SYSTXCCITW01 User manual

Carrier TSTAT Instructions and recipes

Carrier

Carrier TSTAT Instructions and recipes

Carrier 33CS2PPRH-02 User manual

Carrier

Carrier 33CS2PPRH-02 User manual

Carrier 53DFS250-HW User manual

Carrier

Carrier 53DFS250-HW User manual

Carrier Thermostat Assembly instructions

Carrier

Carrier Thermostat Assembly instructions

Carrier P/N 33CSSN2-MH User manual

Carrier

Carrier P/N 33CSSN2-MH User manual

Carrier TSTAT Operation manual

Carrier

Carrier TSTAT Operation manual

Carrier EDGE PRO 33CS2PPRH-01 User manual

Carrier

Carrier EDGE PRO 33CS2PPRH-01 User manual

Carrier TC-PHP User manual

Carrier

Carrier TC-PHP User manual

Popular Thermostat manuals by other brands

York ARTTP001S user guide

York

York ARTTP001S user guide

Vtronix TF85L-200 installation manual

Vtronix

Vtronix TF85L-200 installation manual

Siemens RDY2000 installation instructions

Siemens

Siemens RDY2000 installation instructions

HAI RC-100BZ installation instructions

HAI

HAI RC-100BZ installation instructions

Salus QUANTUM SQ610RF manual

Salus

Salus QUANTUM SQ610RF manual

ATC OCC2 user manual

ATC

ATC OCC2 user manual

baridi DH31 manual

baridi

baridi DH31 manual

Lux Products P0511 Installation and operating instructions

Lux Products

Lux Products P0511 Installation and operating instructions

Johnson Controls S1-TTSCC01 User's information manual

Johnson Controls

Johnson Controls S1-TTSCC01 User's information manual

2HEAT MRF Series user manual

2HEAT

2HEAT MRF Series user manual

Heatmiser neo Stat WIFI manual

Heatmiser

Heatmiser neo Stat WIFI manual

HLS TH 21 operating manual

HLS

HLS TH 21 operating manual

Radiant TS8100W-25A instructions

Radiant

Radiant TS8100W-25A instructions

Danfoss DEVIreg 330 installation guide

Danfoss

Danfoss DEVIreg 330 installation guide

Mysa AC V1-0 user manual

Mysa

Mysa AC V1-0 user manual

Honeywell WebStat T7350 user guide

Honeywell

Honeywell WebStat T7350 user guide

Tekmar tekmarNet 552 Quick setup guide

Tekmar

Tekmar tekmarNet 552 Quick setup guide

Danfoss ECtemp 550 installation guide

Danfoss

Danfoss ECtemp 550 installation guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.