Vtronix TF85L-200 User manual

Vtronix
TF85L-200 (T200) Manual Changeover
TF85L-201 (T201) Auto Changeover
Digital Room Thermostat
INSTALLATION MANUAL
APPLICATION
The TF85L Thermostat provides 24VAC single stage temperature control of 2 pipe and 4 pipe fan-coil
applications with automatic control of a 3 speed fan along with manual heat/cool changeover.
The TF85L Thermostat is mercury free and requires no batteries. All set points are retained permanently in
non-volatile memory in case of a power interruption.
Heat/Cool*
Fig.1. LCD Digital Room Thermostat.
* Heat or Cool mode selection. For Auto changeover model, Heat/Cool mode can not be changed.
WARNING
•
Improper installation, adjustment, alteration, service, maintenance or use can cause explosion, fire,
electrical shock or other conditions which may cause personal injury, death or property damage.
•Observe all warning and caution notices in this document and those posted on the equipment.
•Wear safety glasses, gloves and protective clothing.
•Do not operate equipment or apply electrical power without panels in place.
•Normal system operation will cause some components and surfaces to become hot and can cause burns.
•
Before installing, modifying or servicing system, main electrical disconnect switch must be in the OFF
position. There may be more than one disconnect switch. Lock out and tag switches with a suitable
warning label. Electrical shock can cause personal injury or death.
•
All electrical power should be turned off when servicing or repairing electrical components. Extreme
caution should be observed when trouble shooting electrical components when power is applied.
Observe all warning notices posted on equipment.
1
VTRONIX, LLC Po Box 267096, Weston, FL 33326
Copyright © 2017 Vtronix Document no. 170064-110E (Rev.00)

Vtronix
SPECIFICATIONS
POWER SUPPLY
24 VAC system 18 –30 VAC, 50/60 Hz
TEMPERATURE :
Temperature accuracy ±1.8 °F
Storage temperature 32 – 158 °F
Ambient temperature 50 – 122 °F
Setting temperature range 64 – 85 °F
Deadband (Auto changeover model) ±1 °F of Setpoint
FAN RELAY, HEAT and COOL RELAY : (P4-P8)
Rating (resistive load)
Maximum switching capacity 2 A 277 VAC
3 A 125 VAC
Delay time (HEAT and COOL RELAY) 1 minute or 3 minute (default)
EXTERNAL SENSOR (OPTIONAL) NTC TYPE 6.8 Kohm @ 77 °F
INSTALLATION
Read these instructions thoroughly before installing product. Failure to follow these instructions could
damage the product or cause a hazardous condition. Check the voltage and current ratings on the product to
ensure that it is suitable for your application. Installer must be a trained, experienced service technician.
Check product for proper operation after installation.
CAUTION
Damage to heating and cooling system may occur. Disconnect power from the equipment at the main
breaker/fuse block while installing the thermostat.
Mounting Location
Mount the thermostat approximately 5 ft. (1.5m) above the floor in a location that is free from direct
sunlight, heat from appliances, hot or cold air from ducts, concealed pipes and chimneys, and drafts or dead
spots behind doors or in corners. Do not mount on exterior wall, if possible. Failure to locate thermostat
mounting as indicated will result in poor temperature control.
Note : Level thermostat mounting is for appearance only and is not required for proper thermostat operation.
Mount and Wire the Thermostat
Fig. 1. Separate front of the thermostat from the rear case by using screwdriver to twist and open the locking
tab as shown. Do not push on the LCD as it will damage it. Do not twist or bend the the thermostat.
2
VTRONIX, LLC Po Box 267096, Weston, FL 33326
Copyright © 2017 Vtronix Document no. 170064-110E (Rev.00)

Vtronix
Using the mounting bracket base as a guide,
mark two mounting holes on the wall. Drill
two mounting holes. Place anchors (provided)
into the holes until flush with the hole.
Position bracket on the wall and insert the
wires from the heating and cooling equipment
through the wiring hole. Holding the bracket
and rear case in place on the wall, secure it to
the wall using mounting screws (provided).
Fig.2. Mounting bracket(optional) and rear case on wall.
For mounting thermostat directly on the wall
(optional), drill two mounting holes (4-5/16 inch
apart). Place anchors into the holes until flush
with the hole. Holding the rear case in place on
the wall, secure it to the wall using mounting
screws (provided) as Fig.3
Fig.3. Mounting thermostat directly on the wall
Color-coded 18-22 gauge wire is recommended for
wiring. All wiring must follow local electrical code.
Loosen the terminal screw on the thermostat, strip
the wire and connect the wire as shown in Fig. 4.
Firmly tighten terminal screw when finished.
Follow wiring diagram shown in Fig. 8.
Fig.4. Connect system wires to thermostat terminals
(strip 5/6 inch).
Install the front case, carefully inspect wiring as
per diagram before mounting thermostat.
Fig.6. Mount the thermostat on the rear case by
first placing the thermostat on the top tabs
and then pressing down on the bottom of
the thermostat to snap in place.
Fig. 7. Tighten the screw.
3
VTRONIX, LLC Po Box 267096, Weston, FL 33326
Copyright © 2017 Vtronix Document no. 170064-110E (Rev.00)

Vtronix
WIRING DIAGRAM
Fig.8. For 24 VAC system.
4
VTRONIX, LLC Po Box 267096, Weston, FL 33326
Copyright © 2017 Vtronix Document no. 170064-110E (Rev.00)

Vtronix
SET UP
WARNING
Failure to set up according to the application may damage the heating and cooling system.
Set up mode
Press and hold , and buttons at the same time for 3 seconds, the display will show the
existing set up as per Table 1. Note that all 3 buttons have to be pressed simultaneously.
Display Steady Flashing
P1 Auto Fan Timer – 1 hour (default) Auto Fan Timer – 3 hour
P2 Continuous Fan (default) Cycled Fan
P3 °F (default) °C
P4 Cycled Fan Standard Cycled Fan Override (default)
P5 Low Temp Limit 64 º F (default) Low Temp Limit 70 º F
(1)
P6 Hi Temp Limit 85 º F (default) Hi Temp Limit 78 º F
(2)
P7 3 minute delay time (default) 1 minute delay time
Table 1. Set up table.
Note (1) For T200 manual changeover, applies in cool mode only
(2) For T200 manual changeover, applies in heat mode only
Example 1 : The Display shows P2 steady means the thermostat is set up for Continuous Fan operation.
Change the Set Up Parameters
a)
While in set up mode, press or button to go to the required set up parameter.
b) To change the set up as listed in Table 1, press button.
c) Repeat (a) & (b) for the next set up parameter.
d) Press button to exit from the set up mode.
Note : If button is pressed before exiting from the set up mode (Section d above), the thermostat
will exit without changing the setup parameters.
P4 setting applies only when P2 is set to Cycled Fan.
OPERATION
Power
Press button to turn on/off the equipment. The thermostat will operate to the set point stored in non
volatile memory.
Heat/Cool (For Manual changeover only)
Press the button to change the current mode.
Cool Mode - LCD display shows icon .
Heat Mode - LCD display shows icon .
Note: -
This button is deactivated for Auto changeover model. Heat/Cool mode can not be changed.
Fan
Press button to select the fan speed in the following sequence.
LCD at will show the status of the fan
.
5
VTRONIX, LLC Po Box 267096, Weston, FL 33326
Copyright © 2017 Vtronix Document no. 170064-110E (Rev.00)

Vtronix
Auto mode icon
The speed will be adjusted according to the difference between the room and the setpoint temperature.
If the difference is 4°F or more, the fan will run at high speed.
If the difference is 3°F, the fan will run at medium speed.
If the difference is 2°F, or lower, the fan will run at low speed.
Note : Fan speed defaults to Automatic after 1 hour if it is changed by the user to a particular speed.
Continuous Fan
FAN is always on in High, Medium or Low speeds as long as the thermostat is powered.
Cycled Fan Standard
Fan is on when the heat or cool outputs are on (on cycle). Automatic fan operation is active in the on cycle.
When the heat or cool outputs are off (off cycle), the Fan output is off. The Fan icons (Auto, High, Med and
Low) are all turned off. The button is deactivated in the off cycle. During the on cycle the fan speed can
be manually changed. The fan will turn off in the off cycle and revert back to the selected fan speed during
the on cycle.
Cycled Fan Override
Fan is on when the heat or cool outputs are on (on cycle). Automatic fan operation is active in the on cycle.
When the heat or cool outputs are off (off cycle), the Fan output is off. The Fan icons (Auto, High, Med and
Low) are all turned off. The button can be activated in the off cycle. The appropriate Fan icon (High,
Med and Low) is turned on and the appropriate output is energized. It stays on this speed during the on cycle
as well as the off cycle. This is subject to the automatic fan speed default timer.
Warning: This mode should not be selected for hydronic applications with no control valves.
Excessive heating can result if the Fan is turned on manually.
Auto Fan Speed Timer
Fan speed defaults back to Automatic after 1 hour (or 3 hours based on P1 flashing setting) if it is changed to
a particular speed.
Temperature setting
Press or button for setting the temperature in a range of 64 – 85 °F . But High and Low setting will
depend on P5 and P6
Display will show the new temperature setting for 5 seconds.
T200 Manual changeover
In Cool mode, setting range will be 64-85°F or 70-85°F (set in P5).
In Heat mode, setting range will be 64-85°F or 64-78°F (set in P6).
T201 Auto changeover
Low setting temperature will be 64°F or 70°F (set in P5).
High setting temperature will be 85°F or 78°F (set in P6).
Note: -
icon on LCD display indicates the auto changeover model.
System status
Display at shows when there is a demand for heating or cooling. The LCD icon will flash when
the delay time is activated. Default system delay time is 3 minutes.
Sensor Error Alarm
If the thermostat temperature sensor is defective, the thermostat will turn off the equipment and start flashing
“SE” on the display.
Auto Restart
All the setup parameters are stored in non volatile memory. When there is a power failure and return to
normal, the thermostat will resume operation with the previous setup parameters.
External Sensor
icon on LCD display indicates that the external sensor has been connected to terminal 2 and 3. In this
case the thermostat is controlling to the temperature sensed on the external sensor.
6
VTRONIX, LLC Po Box 267096, Weston, FL 33326
Copyright © 2017 Vtronix Document no. 170064-110E (Rev.00)
This manual suits for next models
3
Table of contents
Other Vtronix Thermostat manuals
Popular Thermostat manuals by other brands

Remotec
Remotec ZTS-110 Z-Thermostat user guide

Danfoss
Danfoss 102E7 Installation & user's instructions

Salus
Salus Optima S user guide

Aprilaire
Aprilaire S86W MUPR owner's manual

Lennox
Lennox ComfortSense L3532H Operation manual

Jackson Systems
Jackson Systems Web Comfort Z-2000 Quick installation and start-up guide