
RSA-104 Technical Manual 4
© 2010 CBS ArcSafe™ 2012-06-20
2.0 Operation
1. Ensure that the unit is properly installed on the circuit breaker as described in Section 1.0 and
that the charge/close arm is in the up position.
2. Install the 3 pin twist style connector from the RSO-III onto the motor control box and install
the 4 pin threaded connector onto the trip solenoid assembly.
Please ensure that all cables are clear of moving parts. Failure to do so could damage cables
and/or actuator.
3. This RSA was tested on a fully maintained and functioning breaker within the CBS ArcSafe
facility. During this testing the optimum settings for closing the breaker were found and
recorded on a placard located on the RSA. Please refer to these settings when setting the “#
Strokes”, “T1”, and “T2”.Once the timing is correctly set, the unit is now fully operational and
ready to use.
These settings may or may not apply to your breaker exactly as listed. These settings are only a
starting point for remote operations. If during the operation the desired effects are not
achieved, these may be adjusted.
4. Power on the RSO-III.
Please ensure that either the batteries on the unit are fully charged or the unit is plugged into
AC power.
5. Press the “CHARGE/CLOSE” button to actuate the breaker arm downward to close the breaker.
Built onto the RSA-104 there are 2 microswitch stops that prevent the RSA handle adapter from
over rotating. However, these are not meant to make the applicable settings obsolete, they
are simply in place to stop the motion of the actuator for small amounts of over-travel and may
be adjusted to achieve optimum results on the gear being operated.
6. The breaker is now able to be tripped. Press the “TRIP”button located on the RSO-III faceplate
to open the breaker.