Celec 98MDC User manual

1. Voltage :
2. Auxiliary Voltage :
3. Current Path :
4. Frequency :
5. Display Size :
6. Setting
7. Programming Lock :
8. Display Parameters :
9. Output , ,
10. Dimensions :
11. Bezel/Panel Cut Out
12. Environment
0 to 500VAC (Line to Line)
0 to 280VAC (Line to Neutral)
230VAC (+/-10%)
Secondary CT 5 Amp.
45Hz to 65Hz
0.56”
a) Maximum Demand : Programmable 10 to 9000KW/KVA
b) Integration Time : Programmable 5 or 30 Minute
c) Primary CT : Programmable Upto 9000Amp.
Time
e) Parameters : Available
RD+MD, KW+KVA and Time+Date
: 3 Relays output 7 Amp. 230VAC
96mm (W) x 96mm (H) x 100mm (D)
: 90mm x 90mm
: Operation Temperature - 10 C to 60 C
Humidity Max 95% (Non Condensing)
d) Weekly Power Cut : Programmable weekly power cut
o o
SPECIFICATION:
General
MDI-CONTROLLER
98MDC
DATE
Y
MD
RD
KVA
KW
DEMAND CONTROLLER
98MDC Program before use
MONTH DATE
HOURS MINUTES
RD
KW
DATE
MD
KVA
TIME
R
B
AL-1
AL-2
TRIP
PROG.
MENU
TIME
ENTER SCROL
ALARM
TRIP
-RESET-
INSTALLATIONGUIDELINES
Caution:
1.Preparethepanelcutoutwithproperdimensionsasshowninspecifications.
2.Removetheclampfromthecontroller.
3.Pushthecontrollerintothepanelcutout.Securethecontrollerinitsplacebypushingtheclampontherearside.Thescrews,ofthe
paneloftheclamp,mustbeinthefurthestforwardslot.
4.For proper sealing, tighten the screws evenly with required torque.
1.
1.Theequipmentshallnotbeinstalledinenvironmentalconditionsotherthanthosespecifiedinthismanual.
2.Fuse protection-The equipment does not contain built-in-fuse. Installation of external fuse for electrical circuitry is highly
recommended.Recommendedratingofsuchfuseshallbe275VAC/1A.
3.Since this is a built-in-type equipment (finds place in main control panel), its output terminals get connected to host equipment.
Such equipment shall also comply with basic EMI/EMC and safety requirements like BS EN 61326-1 and BS EN 61010
respectively.
4.Theoutputterminalsshallbestrictlyloadedtothemanufacturerspecifiedvalues/range.
SAFETY SUMMARY
Thismanualismeantforthepersonnelinvolvedinwiring,installation,operationandroutinemaintenanceoftheequipment.Allsafetyrelated
codifications;symbolsandinstructionsthatappearinthisoperatingmanualorontheequipmentmustbestrictlyfollowedtoensurethe
safetyoftheoperatingpersonnelaswellastheinstrument.
Iftheequipmentisnothandledinamannerspecifiedbythemanufactureritmightimpairtheprotectionprovidedbytheequipment.
Readcompleteinstructionspriortoinstallationandoperationoftheunit.
1
METHODOFMDCALCULATION
AttheendofeachfixedintegrationsPeriodaveragepowerforthatperiodiscalculated.
Assumealoadpatternofthefollowingtype-
10:00 10:15 10:30 10:45 11:00
Integrationperiodis30minutesthen
Demand(RD)-10:00to10:30 block=(20*15+30*15)/30=25kW
Demand(RD)-10:30to11:00 block=(30*15+20*15)/30=25kW
Demand - attheendof11:00 =25kW
30KW
20KW 30KW 20KW
15 Mins

MDI-CONTROLLER
3
1
2
4
5
6
7
8
910 11 12
13
14
15
16
17
18
19 20 21 22 23
DISPLAY & INDICATIONS
Display & Wiring Diagram
WIRING DIAGRAM
R
Y
B
N
TO
LOAD
TRIP AL2 AL1
From
Source
Inputs Outputs
TRIP AL2 AL1
N
Contactor
Shunt Release
N
N
Contactor
N
Hooter
N
Contactor
N
Hooter
Line
CONTROL
ThevoltageofcontactorcoilorShuntreleaseorHooter/Sirennotmorethan240Volt.
Protectionfuseratingmax.2Amp.
Alarm1energizeswhenkWMorethanSetMD.
Alarm2energizeswhentargetdemandreachedat95%*
Tripenergizeswhentargetdemandreachedat100%.
*(Percentageoftargetdemandisselectableatanyvalue75%to99%.)
MDI-CONTROLLER
98MDC
1. Bright Red, 0.56", 7 Segment, 4 digit Display.
2. Bright Red, 0.56", 7 Segment, 4 digit Display.
3. RD LED Indicate Display, Show Rising Demand
4. KW LED Indicate Display, Show Instantaneous
Killowatt (Active Power)
5. Date LED Indicate Display show Present DATE
(MM:DAY)
6. MD LED Indicate Display 2 show Target demand of
present Time Tarif (Maximum Demand) Indication
7. KVA LED Indicate display 2 shows Instantaneous KVA (Apparent
power)
8. Time LED indicate Display 2 shows Present time (24 Hour
Format).
9. Peak Time LED indicate Display show present Peak Load Start
Timer).
10. PROG. LED indicate the system is in programming mode.
11. PKL ON LED Indicate system in peak load time mode
12. Weekly Off LED indicate system in weekly off mode
13, 14 & 15 -LED’s indicate phase wise parameters
16. Peak Time trip Indication
17. Pre-Alarm Indication
18. Trip Indication
19. Key to display RD & MD (during program mode this key
increase parameters)
20. Key for display KW & KVA (during program mode this key
decrease parameters.
21. Key to display Time & Date ( To select CT Ratio keep press
this key) (during program mode this key shift digit left to right
or right to left to set parameters)
22. Key to display present Peak Time, Start & finish. (during
program mode this key Enter ( ) parameter)
23. Scroll key & Auto manual selection key
2

GENERAL WORKING
1. Display Rising Demand & Maximum Demand / KVA / Clock
Press Key Display shows
Press Key Display show
Again press Key Display shows
. press key Display shows average of 3 phase KW & kVA.
Press key R phase LED glows and Display shows R phase kW & kVA.
Again Press
On Load Check the KW on each phase R, Y, B by using scroll.
Maximum (Target) Demand (MD) and Rising Demand (RD).
s Rising Demand (RD) and running load (in kVA)
Rising Demand (RD) and Internal Clock Time.
Any combination with running demand can be set as per set customer requirement.
key Y phase LED glows and Display shows Y phase kW & kVA.
Again Press key B phase LED glows and Display shows B phase kW & kVA
.
Press key display show Real Time Clock (RTC) and Date.
If Alarm1 or Alarm2 is energize, Press key to reset both the Alarm.
Alarm1 and Alarm2 reset and Alarm1 and Alarm2 LED’s are blinking in reset mode.
.
After to reset the alarm1 or Alarm2 press key to reset Trip.
2. Display kW and kVA
3. Display Date and Time
4. To Reset Alarm
5. To Reset Trip
Caution:-
.If Display shows in any phase then interchange S1 & S2 of the phase which show
If Display shows Current is below than minimum kW sensitivityg
User Manual
MDI-CONTROLLER
98MDC
3

CONTROLLER PROGRAMMING
1 Start Programming mode
2 / - Lock and Unlock the program
3. To set the power cut start time
4. To set the power cut start day
To set the power cut
6 - To set the power cut off day
7. To set CT Ratio
8. To set Maximum Demand in normal period
9. - To set Maximum Demand in peak load period
10. To set Maximum Demand in power cut period
.Press key, Press key, Peak time LED glows and Display shows Peak load On/Off period for present
month.
.Again press key, if Display shows ,device is locked but
-Again Press key, Display shows - power cut start time.
change the power cut start time.
Use key to enter change HH : MM.
-Again Press key, Display shows - power cut start day.
change the power cut start
Again Press key, Display shows - power cut off time.
change the power cut time.
Use key to enter change HH : MM
.Again Press key, Display shows - power cut off day.
change the power cut
-Again Press key, Display shows change CT Ratio.
-Again press key, Display shows
Again press key, Display shows denote peak time sanction load.
-Again press key, Display shows denote power cut sanction load.
display show internal clock time and Date.
operator can view the program.
If Display shows , device is unlocked operator can modify the program.
Use and keys to change the value, when Display is equal to unlock PROG. LED
glows and Display shows , program can be changed.
Use and keys to
Use and keys to day.
Use and keys to off
Use and keys to off day.
Use and keys to
Use and keys to set maximum demand at normal time.
Use and keys to set maximum demand at peak time.
Use and keys to set maximum demand at power cut.
*Unlock Number is program value of program ( ) +7
*1-Monday, 2-Tuesday, 3-Wednesday, 4-Thursday, 5-Friday, 6-Saturday, 7-Sunday
* 1-Monday, 2-Tuesday, 3-Wednesday, 4-Thursday, 5-Friday, 6-Saturday, 7-Sunday
5. - off time
User Manual
MDI-CONTROLLER
98MDC
4

11. - To set Alarm1 percentage
Example:-
12. - To set Alarm2 percentage
Example:-
12. - To set Trip percentage
Example:-
13. - To Test outputs
14. - To set Integration ,
15. - To Manipulating Error ,
Note:-
Again press key, Display shows ,
.
Again press key, Display shows , it is the percentage value of running demand period at which Alarm2 will
be on full normal period.
.
Again press key, Display shows , it is the percentage value of running demand period at which Trip will
be on full normal period.
.
Again press key, Display shows
Use key, Display show and AL1 LED glows, and Alarm1 on in 10 seconds.
Again press key, Display show and AL2 LED glows, Alarm2 on in 10 seconds.
Again press key, Display show and Trip LED glows, Trip on in 5 seconds.
Again press key, Display shows it should be equal to energy meter.
Again press key, Display shows This feature is for matching controller kW with energy meter kW and
hence RD running demand will match automatically.
= 100 - actual controller calibration
= 110 - 10% addition to the actual controller calibration
= 90 - 10% below actual controller calibration
Measurement should be stimulation from controller and energy meter for matching.
Alarm1 energizes when kW More than Set MD.
If user set target demand at 160 kW and AL1 is at 110
Then over load limit will be 160x110/100 = 176 kW
As the running load exceeds 176 Alarm1 will be ON.
If user set target demand at 160 kW and AL2 is at 95
There limit for Alarm2 will be 160x95/100 = 152 kW
As Rising Demand (RD) reaching 152 Alarm2 will be ON.
If user set target demand at 160 kW and Trip is at 100
There limit for Alarm2 will be 160x100/100 = 160 kW
As Rising Demand (RD) reaching 160 Trip will be working 5 seconds.
Use and keys to set Alarm1 value.
Use and keys to set Alarm2 value.
Use and keys to set Trip value.
Use and keys to set integration time 15 and 30 minutes.
Suit the Integration time equal to energy meter Integration time usual it is 30 minutes
Use and keys to increase and decrease value.
User Manual
MDI-CONTROLLER
98MDC
5

Example:-
16. - ,
17. ,
18. - To set Password ,
Example:-
19. - To set peak load on time January ,
20. - To set peak load off time January ,
19. - To set peak load on time February ,
20. - To set peak load off time February ,
Say energy meter kW =110
Controller kW = 100
Calibration Number = x100
= x 100
Calibration Number = 110
Reason for mismatching can be transformer and C.T.’s, P.T.’s variation.
Again press key, Display shows
-Again press key, Display shows
Again press key, Display shows set the password for controller programming Lock and Unlock
Default setting 7 then unlock number is 7+7=14
Use key and key to change the value.
If you can set value =15
then unlock number is =15+7 = 22
Again press key, Display shows set the January peak load on time.
Use key and key to change the peak load time.
Use key to enter change HH : MM
Again press key, Display shows set the January peak load off time.
Use key and key to change the peak load time.
Use key to enter change HH : MM
Again press key, Display shows set the February peak load on time.
Use key and key to change the peak load time.
Use key to enter change HH : MM
Again press key, Display shows set the February peak load off time.
Use key and key to change the peak load time.
Use key to enter change HH : MM
User Manual
MDI-CONTROLLER
98MDC
6
Energy Meter kW
Controller kW
110
100

19. - To set peak load on time March ,
20. - To set peak load off time March ,
19. - To set peak load on time April ,
20. - To set peak load off time April ,
19. - To set peak load on time May ,
20. - To set peak load off time May ,
19. - To set peak load on time June ,
20. - To set peak load off time June ,
19. - To set peak load on time July ,
20. - To set peak load off time July ,
Again press key, Display shows set the March peak load on time.
Use key and key to change the peak load time.
Use key to enter change HH : MM
Again press key, Display shows set the March peak load off time.
Use key and key to change the peak load time.
Use key to enter change HH : MM
Again press key, Display shows set the April peak load on time.
Use key and key to change the peak load time.
Use key to enter change HH : MM
Again press key, Display shows set the April peak load off time.
Use key and key to change the peak load time.
Use key to enter change HH : MM
Again press key, Display shows set the May peak load on time.
Use key and key to change the peak load time.
Use key to enter change HH : MM
Again press key, Display shows set the May peak load off time.
Use key and key to change the peak load time.
Use key to enter change HH : MM
Again press key, Display shows set the June peak load on time.
Use key and key to change the peak load time.
Use key to enter change HH : MM
Again press key, Display shows set the June peak load off time.
Use key and key to change the peak load time.
Use key to enter change HH : MM
Again press key, Display shows set the July peak load on time.
Use key and key to change the peak load time.
Use key to enter change HH : MM
Again press key, Display shows set the July peak load off time.
Use key and key to change the peak load time.
Use key to enter change HH : MM
User Manual
MDI-CONTROLLER
98MDC
7

19. - To set peak load on time August ,
20. - To set peak load off time August ,
19. - To set peak load on time September ,
20. - To set peak load off time September ,
19. - To set peak load on time October ,
20. - To set peak load off time October ,
19. - To set peak load on time November ,
20. - To set peak load off time November ,
19. - To set peak load on time December ,
20. - To set peak load off time December ,
Again press key, Display shows set the August peak load on time.
Use key and key to change the peak load time.
Use key to enter change HH : MM
Again press key, Display shows set the August peak load off time.
Use key and key to change the peak load time.
Use key to enter change HH : MM
Again press key, Display shows set the September peak load on time.
Use key and key to change the peak load time.
Use key to enter change HH : MM
Again press key, Display shows set the September peak load off time.
Use key and key to change the peak load time.
Use key to enter change HH : MM
Again press key, Display shows set the October peak load on time.
Use key and key to change the peak load time.
Use key to enter change HH : MM
Again press key, Display shows set the October peak load off time.
Use key and key to change the peak load time.
Use key to enter change HH : MM
Again press key, Display shows set the November peak load on time.
Use key and key to change the peak load time.
Use key to enter change HH : MM
Again press key, Display shows set the November peak load off time.
Use key and key to change the peak load time.
Use key to enter change HH : MM
Again press key, Display shows set the December peak load on time.
Use key and key to change the peak load time.
Use key to enter change HH : MM
Again press key, Display shows set the December peak load off time.
Use key and key to change the peak load time.
Use key to enter change HH : MM
User Manual
MDI-CONTROLLER
98MDC
8

User Manual
MDI-CONTROLLER
98MDC
21. / - Clock and Calender Setting
22. - Reset Seconds
23. - Set Clock ,
24. - Set Date ,
25. - Set Day ,
26. - Set Year ,
Again press key, if Display shows ,device is locked but
Again press key, Display shows
In this mode if you press key seconds will be zero (0)
Again press key, Display shows set the controller’s internal clock match with energy meter
Use key to enter change HH : MM
Again press key, Display shows
Use key to enter change :
Again press key, Display shows
Again press key, Display shows
operator can view the clock and calender.
If Display shows , device is unlocked operator can modify the clock and calender.
Use and keys to change the value, when Display is equal to unlock. Display shows
, clock and calender can be changed.
Use and keys to change the value
Month Date
Use and keys to change the value
Use and keys to change the value
*Unlock Number is program value of program ( ) +7
*1-Monday, 2-Tuesday, 3-Wednesday, 4-Thursday, 5-Friday, 6-Saturday, 7-Sunday
Press key for save all setting
9
Table of contents
Other Celec Controllers manuals