Celec S-50 User manual

______________________________________________________________________________________
1
S-50
Field Installation Manual
INDEX
Important Instructions……………………………………………………………… 2
Product Specifications…………………………………………………..…………. 3
Unpacking & Mounting …………………………………………………………… 4
Connection Type 1 ……………………………………………………………..…… 5
Connection Diagram....................................................................... 6
Connection Type 2 ……………………………....... ……………………………… 7
Connection Type 3 ……………………………………………………….…………. 8
Electrical Data Sheet ………………………………………..…………………….. 9
Recommended Part List………………………………………………..…..…….. 10

______________________________________________________________________________________
2
S-50
IMPORTANT INSTRUCTIONS
ATTENTION:After completing the installation and testing, it is essential that this booklet is
drawn to the attention of the person responsible for its future operation and maintenance and
is available for ready reference all the time.
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLATION &
OPERATION WILL VOID WARRANTY OF S-50 AND COULD CAUSE SERIOUS PERSONAL INJURY, FIRE
HAZARD & ELECTRIC SHOCK MAY LEAD TO DEATH.
CAUTION:
To prevent electric shock, disconnect electric power to system at main fuse or circuit breaker box
until installation or rework is complete.
PRECAUTION:
Do not use on circuits exceeding specified voltage.
Do not short main terminals to test.
Electrical Installation and all components of the installation must be UL listed / UL approved and as
per NEC code.
WARNING
Celec manufactured component parts that can be used in a wide variety of industrial &
commercial applications. The selection and application of Celec products remains the responsibility of
the equipment designer or end user. Celec accepts no responsibility for how its products may be
incorporated into final design. Under no circumstances should any Celec product be incorporated into
any product or design as the exclusive or sole safety control, all controls should be designed to
dynamically fault defect and fail safety under all circumstances. Any warning provided by Celec must
be passed through to the end user. Celec offers a warranty only as to the quality of its product to
confirm to the catalog specifications. No other warranty is offered. Celec assumes no liability for any
personal injury, property damage, losses or claims arising out of the misapplication and Non
performance of its products.

______________________________________________________________________________________
3
PRODUCT SPECIFICATIONS
Model: ……………………………………………………………………………… S-50
Rated Voltage……………………………………………………………………… 208V AC
Phases………………………………………………………………………………… 3
Rated Frequency………………………………………………………………… 60Hz
Maximum Current…………..……………………………………………….… 140 Amp per phase
Maximum kVar...………………………………………………………………… 50
Maximum Ambient Temperature..……..……………………………..… 400C
Enclosure……………………………………………………………………………… Type 1
Terminals Wire Size Connection Type Torque N-m (Lb-in)
T1 3/0 AWG, Str. MCCB 31(275)
T2 18-22 AWG, Str. CT Terminal Block 0.5 (7)
Earthing
Terminals
10 AWG, Str. Bonding 15 (133 )

______________________________________________________________________________________
4
UNPACKING
1. Un Pack the S-50 from box using Plastic Strip Cutter & 17 No. Spanner.
2. Collect the Accessories as per the Packing Slip.
3. Remove any cardboard or thermocol packing inside the S-50 given for support during transportation.
4. Do not use S-50 in case of any Breakage or loose connections or Oil Spill inside.
MOUNTING
CAUTION: - Indoor Use Only, Type-1 Enclosure.
1. Choose the dry and Clean Floor to Install the S-50 taking care conduit connections from Bottom side
Enclosure Size is 800 x 1000 x 300 mm and weight 84kg (186 Pounds).
2. Premark the Mounting holes on floor or structure.
3. Tighten the Foundation bolts.
S-50

______________________________________________________________________________________
5
Field Installation Manual
Connection Type # 1
Use this instruction
If 200 Amp circuit breaker is available in customer Main Breaker Panel.
S-50 is designed for use with Main Breaker Panel Three Phase 208V AC WYE/Delta
Connection, up to 1600 Ampere.
S-50 unit should be mounted with four appropriate sized fasteners before connect to
Main Breaker Panel.
1.1 Power Connections
1.11 Using panel key open the door of S-50 exposing connections.
1.12 Locate Earth Terminal in S-50, connect the earth wire to S-50 Earth Terminal. Connect the other
side of earth wire to main breaker panel ground rod. Ensure all mechanical connections are secure
and making full contact.
1.13 Locate existing 3 Pole 200 Amp Circuit Breaker in the Main Breaker Panel.
Connect the wire L1 to Phase 1 of 200 Amp circuit breaker.
(b) Connect the wire L2 to Phase 2 of 200 Amp circuit breaker.
(C) Connect the wire L3 to Phase 3 of 200 Amp circuit breaker.
1.14 Qualified Representative must inspect size of cable minimum 3/0 AWG.
1.15 Connect power cables to BUS BAR of S-50.
1.2 Current Sensor Connections
1.21 Open one side of Split CT (Current Sensor). Clip the CT on the wire L3 before main Circuit
Breaker Panel.
1.22 Locate Terminal Block T2 (S1-S2) in S-50.
1.23 Qualified Representative line side of Main Panel should connect the wires 18-22 AWG from external
CT to T2 (S1-S2), preferably twisted together.
1.24 Firmly secure current sensor to line side (L3) of main circuit breaker.

______________________________________________________________________________________
6

______________________________________________________________________________________
7
S-50
Field Installation Manual
Connection Type#2
Use these instructions
If 200 Amp circuit breaker is unavailable, existing blanks are available.
S-50 unit is designed for use with Customer Main Breaker Panel Three Phase
208V AC WYE/Delta Connection, up to 1600 Ampere.
S-50 units should be mounted with appropriate sized fasteners before connect to Main Breaker
Panel.
1. Using panel key open the door of S-50 exposing connections.
2. Remove existing 3 Pole breaker blanks and install new 3 Pole 200 Amp circuit Breakers.
3. For rest of connection follow the Connection type#1 on page 5.

______________________________________________________________________________________
8
S-50
Field Installation Manual
Connection Type#3
Use this instruction
If 200 Amp circuit breaker is unavailable and require a new disconnect switch or
other approved device.
S-50 unit is designed for use with Customer Main Breaker Panel Three Phase
208V AC WYE/Delta Connection, up to 1600 Ampere.
Representative must purchase 200 Amp Blade-Fused Disconnect Switch or
200 Amp Circuit Breaker for connection of S-50 to Customer Main Breaker Panel.
1. Install new 200 Amp Blade-Fused disconnect or External Circuit Breaker switch to wall or existing
backboard. Qualified Representative should note if codes allow for direct connection to bus bars in
main breaker panel or requires installation of an additional sub panel.
2. Wire in rigid conduit between customer main breaker panel & external disconnect switch.
3. Locate earth ground connection in S-50 and connect to grounding bar or to earth ground rod in
main breaker panel.
4. For rest of connection follow the Connection type#1 on page 5.

______________________________________________________________________________________
9
S-50
Field Installation Manual
Electrical Data Sheet
Model S-50
Phase Configuration Three Phase 208V AC WYE/Delta
Maximum Line Voltage 208V AC
Maximum Power 50 kVar
Steps 8
Monitoring
PF, kVA, kVar, Volt, Current, KW, %THD-V
Internal Temperature & Capacitor Status
Accuracy 1 kVar
Frequency
60Hz
Protection
Capacitor Inbuilt Protection P2, capacitor short circuit 10,000A
Capacitor over current protection.
Equipment Protection
Internal design has adequate clearance and creepage distance
against line transients. MOVs not required.
Circuit breaker Required
200 Amp 3 pole
Low Losses 1.5 Watt each step
Human Protection
All High voltage shielded from contact.
Operating temperature range
40oC Ambient
Dimensions(L X H X D)
( 800 x 1000 x 3000 mm) Metal Enclosure Type 1
Operating Life Switching tested up to 25,000 times,
Dielectric Strength Tested up to 3.5 kV, 1.42 kV for 1 min.
Wire Gauge & Rating
3/0 AWG Str for Power, 18-22 AWG Str for CT, 8 AWG Str for Bonding
Unit Weight 84 kg (186 Pounds)

______________________________________________________________________________________
10
S-50
Field Installation Manual
Recommended Parts List
Item Make Part No. Qnty.
Main Wire 3/0 AWG Str. 600v Any * UL1015 As required
CT Wire 18-22 AWG Str. 600v
Any *
UL1015
As required
Bonding Wire 8 AWG Str. 600v Any * UL 1015 As required
CT (Current Sensor) Megnelab SCT-1250-1000 1
Floor Plug (pin type) Size 10 x 75 mm Any --- 4
Conduit Connector Any * --- 4
Tube/Conduit Any * --- As required
*All the Parts used in installation must be UL recognized or UL listed.
NOTE
Installation of material and workmanship at the customer’s Main Breaker Panel shall be
the responsibility of the qualified Electrician in accordance with NEC. Any and all
connections exterior to the S-50 unit shall be the responsibility of the qualified Electrician.
Table of contents
Other Celec Controllers manuals
Popular Controllers manuals by other brands

Sauter Components
Sauter Components ASF 123S Wiring diagram

Bosch
Bosch Access Modular Controller 2 installation manual

icititech
icititech iPC Mounting instructions

Nevco
Nevco 134 Operator instructions

Automationdirect.com
Automationdirect.com DL06 user manual

Linear Technology
Linear Technology LTC3626EUDC Demo Manual

mensor
mensor CPC8000 operating instructions

NuWhirl
NuWhirl TOUCHSTONE CSLC-317-02-01-01 Installation & operating manual

Siemens
Siemens 5WG1 523-1AB04 quick start guide

Fujitsu
Fujitsu WATERSTAGE UTW-SCB A Series Operation manual

Status Instruments
Status Instruments SEM1700 user guide

TPS
TPS ProChem R manual