Chore-Time 28999 User manual

Introduction
The 28999 Drop Feeder Control is designed to be used
with a Chore-Time Drop Feeding System and Chore-
Time Flex-Auger®System.
The control will automatically open the Drop Feeders,
close the Drop Feeders, and start the fill system. The
system may also be operated manually.
The components of the control are housed in a dust proof,
water tight box. Liquid tight connectors must be used
when wiring into the control. The cover must be latched
in closed position unless switches or time clockis being
adjusted.
Wire the Drop Feeder Control, according to the
appropriate wiring diagram.
Setting the Control
Unlatch and open front cover.
Time Clock operation
Set the desired feeding time(s) on clock by sliding out sufficient tabs to allow for auger run time. Slide out one
additional tab for drop cycle (time required to open drops and close drops). Each tab represents 15 minutes. See
“Time Clock Features and Operation” on page 5 for clock setting information.
The lower toggle switch should be in the TIME CLOCK OPERATION position.
The upper toggle switch should be in the OFF position.
How it Operates
When the switch on the time clock is activated by the tabs, all drops will open at the same time. The drops will
automatically begin closing 15 seconds to 5 minutes after the clock is activated. This delay is adjustable
inside the control panel.
In multiple lift applications the #1 lift will completely close, then #2, etc. until all drops have closed. At that
time the fill system contactor and AUGER ENABLED Pilot Light will become energized and the fill system
auger(s) will refill the drop boxes. The switch in the Drop Feeder Control Unit will stop the fill system(s).
The fill system contactor and AUGER ENABLED Pilot Light will remain energized until the tabs no longer
activate the Time Clock Switch.
CAUTION: Only use the number of time clock tabs needed to fill the system plus one extra tab.
Manual Operation
Set the lower toggle switch to the MANUAL OPERATION position. The Time Clock is now disabled and the
drops may be opened or closed using the upper toggle switch.
The upper toggle switch should be in the OFF position when not in use.
MA922-7D
Drop Feeder Control
Part Number 28999
CTB Inc.
P.O. Box 2000 • Milford, Indiana 46542-2000 • U.S.A.
Phone (574) 658-4101 • Fax (877) 730-8825

Drop Feeder Control
2MA922F
How it Operates
Set the upper toggle switch to the OPEN DROPS position and the drops will open. Set the upper toggle switch
to the CLOSE DROPS AND FILL position, and the drops will close. When the balls are fully seated the fill
system contactor and AUGER ENABLED Pilot Light will become energized. The switch in the Drop
Feeder Control Unit will stop the fill system.
Close the cover and secure latch to keep moisture and contamination from entering box and voiding warranty.
Drop Feeder Control Internal Wiring Diagram (Feed-Fill)
RED
BLACK
RED
BLACK
GREEN
BLACK
ORANGE
RED
BLUE
YELLOW
YELLOWORANGE
L2
L1
2526-286
230V 1PH
TO FILL
CONTACTOR
ORG
RED
YELLOW
ORANGE
GREEN
BLACK
RED
WH
L1
L2
BLACK
TO
230V 1PH
SUPPLY
BLK
RED
BLUE
YELLOW BLACK
BLACK
YELLOW
YELLOW
RED
BLACK
BLUE
ORANGE
YELLOW
ORANGE
BLUE
RED
RED
230V 1PH
POWER
PACK
RED BLACK
YELLOW
MA922-3 10/95

Drop Feeder Control
3
MA922F
Internal Wiring Changes for converting a standard 28999 Drop Feeder
Control Panel to a Feed-Delay Fill style control
In this mode of operation the drops will be full of feed at feeding. The refilling will be delayed to a preset time of
choice. After the balls have been lifted to allow feeding, the ball will remain in the up position until time to refill
the feed boxes.
The control will need to be wired as shown to run as a delay fill system, See Figure 1.
Figure 1. Standard Control converted
Instructions for setting the time clock, See Figure 2. Push in all the tabs between the selected feed time and fill
time. With the time clock set this way it will delay filling of the boxes.
STEP 2
MA922-6 10/95
CONNECT BLACK WIRE HERE
CONNECT RED WIRE HERE
STEP 4
ORANGE
230V 1 PH
SUPPLY
STEP 3
DISCONNECT RED WIRE HERE
230 V 1 PH
TO FILL
CONTACTOR
STEP 1
DISCONNECT BLACK WIRE HERE
L2
L1
RED
BLK
ORG
WH
L2
L1
BLACK
TO
230 V 1 PH
POWER PACK
DISCONNECT YELLOW WIRE
STEP 5
RED
YELLOW YELLOW
AT BOTH ENDS AND DISCARD

Drop Feeder Control
4MA922F
Drop Feeder Control Internal Wiring Diagram (Feed-Delay Fill)
RED
BLACK
RED
BLACK
GREEN
ORANGE
RED
BLUE
ORANGE
L2
L1
2526-286
230V 1PH
TO FILL
CONTACTOR
ORG
RED
YELLOW
ORANGE
GREEN
BLACK
RED
WH
L1
L2
BLACK
TO
230V 1PH
SUPPLY
BLK
RED
BLUE
YELLOW BLACK
BLACK
YELLOW
YELLOW
RED
BLACK
BLUE
ORANGE
YELLOW
ORANGE
BLUE
RED
RED
230V 1PH
POWER
PACK
RED BLACK
YELLOW
MA922-8 10/95
BLACK

Drop Feeder Control
5
MA922F
Time Clock Features and Operation
• The outside edge of the clock face is a series of tabs.
• Use a finger nail of small screw driver to push tabs out.
• Each white tab on the time clock is equivalent to 15 minutes.
• Turn the white minute hand clockwise until the real time (actual time of day) is lined up with white arrow on
inner clock face.
•Do not turn the hand counter-clockwise! This will strip out the nylon gears and void your warranty.
Also, never adjust the time clock by turning the outer dial.
Drop Feeder Control (with Single Linear Actuator) Wiring Diagram
Time of Day (AM & PM Format)
Pull tabs as required for feeding cycle
(1hr. shown)
When adjusting, turn minute hand
clockwise only.
Figure 2. Setting Time Clock

Drop Feeder Control
6MA922F
Drop Feeder Control (with Multiple Linear Actuators) Wiring Diagram

Drop Feeder Control
MA922F 7
Drop Feeder Control (with One Linear-Lift™) Wiring Diagram

Drop Feeder Control
8MA922F
Drop Feeder Control (with Two Linear-Lifts™) Wiring Diagram

Drop Feeder Control
MA922F 9
Drop Feeder Control (with One MULTI-LIFT®and One Tower Switch) Wiring Diagram

Drop Feeder Control
10 MA922F
Drop Feeder Control Two MULTI-LIFT®/Two Tower Switches Wiring Diagram

Drop Feeder Control
11
MA922F
Drop Feeder Control Parts Listing (Part No. 28999)
Item Description Part No.
1 Pilot Light 7044
2 Control Box 28821
3 Push Nut Retainer 29879
4 10-32 Ground Screw 4968
5 #10 External Lock Washer 305
6 Corner Bracket 29013-1
7 Sheet Edge Insert 29878
8 Time Delay Relay (230 V) 29890
9 Fuse Block 7588
10 5 amp Normal Blow Fuse 7001
11 Mounting Plate 28689
12 Copper Lug 28822
13 Terminal Block 7270
14 ---- ----
15 Strapping 29014-2
16 Mounting Adapter 25480
17 Time Clock 26795
18 Front Panel 28685
19 Toggle Switch 20135
20 Toggle Switch 29727

Note: The original, authoritative version of this manual is the English version produced by
CTB,Inc.oranyofitssubsidiariesordivisions,(hereafter collectivelyreferred to as "CTB").
Subsequent changes to any manual made by any third party have not been reviewed nor
authenticated by CTB. Such changes may include, but are not limited to, translation into
languages other than English, and additions to or deletions from the original content. CTB
disclaims responsibility for any and all damages, injuries, warranty claims and/or any other
claims associated with such changes, inasmuch as such changes result in content that is
different from the authoritative CTB-published English version of the manual. For current
product installation and operation information, please contact the customer service and/or
technical service departments of the appropriate CTB subsidiary or division. Should you
observe any questionable content in any manual, please notify CTB immediately in writing
to: CTB Legal Department, P.O. Box 2000, Milford, IN 46542-2000 USA.
Revisions to this Manual
Page No. Description of Change
7,8 Changed Wiring Diagrams to match Current Linear Lift.
Contact your nearby Chore-Time distributor or representative for additional parts and information.
CTB Inc.
P.O. Box 2000 • Milford, Indiana 46542-2000 • U.S.A.
Phone (574) 658-4101 • Fax (877) 730-8825
E-mail: poultry@choretime.com • Internet: http//www.choretime.com
Table of contents
Other Chore-Time Controllers manuals