Carel ir33+ User manual

ir33+ Electronic controller for stand-alone refrigerating units
+05Z0028EN- rel. 1.0 - 13.03.2014
Dimensions (mm)
Panel mounting
Rear (with 2 quick-fit side brackets)
Technical characteristics
power supply:
Model Voltage Power
IREVxxExxxx 230 V~, 50/60 Hz 3 VA, 25 mA~ max.
IREVxxHxxxx 115...230 V~, 50/60 Hz 6 VA, 50 mA~ max.
IREVxxLxxxx 12...24 V~, 50/60 Hz, 12...30 Vdc 3 VA, 300 mA~ /mAdc max.
Insulation guaranteed by the power supply:
IREVxxExxxx
IREVxxHxxxx
insulation in reference to very low
voltage parts
reinforced, 6 mm clearance, 8 mm
creepage, 3750 V insulation
insulation from relay outputs basic, 3 mm clearance, 4 mm creepage,
1250 V insulation
IREVxxLxxxx insulation in reference to very low
voltage parts
externally guaranteed by safety transfor-
mer (SELV power supply)
insulation from relay outputs reinforced, 6 mm clearance, 8 mm
creepage, 3750 V insulation
Inputs
S1 (probe 1) NTC
S2 (probe 2) NTC
DI1
S3 (probe 3)
free contact, contact resistance < 10 Ω, closing current 6 mA
NTC
DI2
S4 (probe 4)
free contact, contact resistance < 10 Ω, closing current 6 mA
NTC
Maximum distance of probes and digital inputs less than 10 m. Note: During installation
keep the power and loads connection separate from probe cables, digital inputs, repeater
display and supervisory system
Probe type
NTC std.
CAREL
10 kΩ a 25 °C, range –50T90 °C
measurement error 1 °C range –50T50 °C
3 °C range 50T90 °C
Relay outputs (depending on the model)
EN60730-1 UL873
model relay 250 V~ operat.
cycles
250 V~ operat.cycles
IRxxxx(E,A)(P,Q,S,U,V,X,Y,Z)xxx R2 (*) 5(1) A 100000 5 A res. 1 FLA
6 LRA C300
30000
IRxxxx(E,A)(N,R,C,B,A,M,L,T)xxx R3 (*) 5(1) A 100000 5 A res. 1 FLA
6 LRA C300
30000
IRxxxx(E,A)(N,R,C,B,A,M,L,T)xxx
IRxxxx(0,L,H)(N,R,C,B,A,M,L,T)xxx
R1, R2
R2, R3,
R4 (*)
8(4)A N.O.
6(4)A N.C.
2(2)A N.O./N.C.
100000 8 A res. 2 FLA
12 LRA C300
30000
IRxxxx(E,A)(P,Q,S,U,V,X,Y,Z)xxx
IRxxxx(0,L,H)(N,R,C,B,A,M,L,T)xxx
R1 12(2)A
N.O./N.C.
100000 12 A res. 5 FLA
30 LRA C300
30000
insulation in reference to very low
voltage parts
reinforced, 6 mm clearance, 8 mm creepage, 3750 V
insulation
insulation between the relay outputs
indipendent
basic, 3 mm clearance, 4 mm creepage, 1250 V
insulation
Connections wire section 0.5 - 2.5 mq max current 12A
(*): Relay not suitable for fluorescent loads (neon lights, ...) that use starters (ballasts) with
phase-shift capacitors. Fluorescent lamps with electronic control devices or without phase-
shift capacitors can be used, within the operating limits specified for each type of relay.
The installer has to provide the correct dimensioning of the power supply and cable con-
nection between the instruments and the loads. Depending on the model, the maximum
current in the common terminals 1, 3 or 5 is 12 A. When using the controller at maximum
operating temperature and full load, use cables featuring a maximum operating tempera-
ture of 105 °C at least.
Clock error at 25 °C ±10 ppm (±5.3 min/year)
error in the temperature range -10T60 °C
-50 ppm (-27 min/year)
Operating temperature -10T60 °C for all versions
Operating humidity <90% r.H. non-condensing
Storage temperature -20T70 °C
Storage humidity <90% r.H. non-condensing
Front panel degree of protection smooth and stiff panel installation with
gasket IP65
Control pollution status 2 (normal situation)
PTI of the insulating material printed circuit board 250, insulation 175
Period of electric stress across insulating parts long
Heat and fire resistance category category D and category B (UL 94-V0)
Class of protection against voltage surges category II
Type of disconnection or interruption 1.B relay contacts (micro-disconnection)
Construction of control incorporated control, electronically
Classification according to protection against
electric shock
Class II, by appropriate incorporation
Max. distance between interface and display 10 m
Programming key available on all models
Safety standards: compliant with the European
reference standards.
Signals on the display
Icon Function Normal operation Startup
ON OFF blink
COMPRESSOR compressor ON compressor OFF compressor
required
FAN fan ON fan OFF fan required
DEFROST defrost in progress defrost not
required
defrost required
AUX auxiliary output AUX
active
auxiliary output
AUX not active
anti-sweat heater
function active
ALARM delayed external alarm
(before the expiry of
the time‘A7’)
no alarm present alarms and
malfunctions
CLOCK at least one timed
defrost has been set
no timed defrost
is present
clock alarm ON if RTC
present
LIGHT auxiliary output
LIGHT active
auxiliary output
LIGHT not active
anti-sweat heater
function active
SERVICE no malfunctions malfunction (es.
EEPROM error or
probe fault)
HACCP function not enabled function enabled
(HA and/or HF)
HACCP alarm
enabled
CONTINUOUS
CYCLE
function enabled function not
enabled
function required
Optional connections
1
2IROPZDSP00
Display interface option
IROPZ48500
Serial board interface RS485
IROPZKEY**
Programming key
Option codes
Code Description
IROPZDSP00 remote display interface
IREVXGD000 remote repeater dispaly
IROPZ485S0 RS485 serial board interface with automatic recognition of the polarity +/-
PSOPZPRG00 programming key kit
PSOPZKEY00 parameter programmin key with 12 V batteries
PSOPZKEYA0 parameter programming key external 230 Vac power supply
IROPZKEY00 parameter programming key, extended memory with 12 V batteries
PSTCON0*B0 repeater display connection cables (*: 1= 1,5 m; 3= 3 m; 5= 5m)
NOPOWER
& SIGNAL
CABLES
TOGETHER
READCAREFULLY IN THE TEXT!
Description: ir33+* represent a range of electronic microprocessor controllers with LED
display developed for the management of stand-alone refrigerating units.
Part number list:
IREVM0LN0U, IREVM0EN0U
IREVS0LN0U, IREVS0EA0U,
IREVC0LN0U, IREVC0LC0U
IREVC0HN0U, IREVC0HC0U, IREVF0EN0U
1
2
drilling template
71x29 mm
34.7
79.5
82
76.2
80.6
38.6
60
64
E, AVersion
65
69
Buttons on the keypad
Button Normal function Start-up Autom.address
assignment
Pressing the button alone Pressing together with other buttons
PRG /
MUTE
- if pressed for more than
3 s accesses the menu
for setting the password
to access the type “F”
(frequent) parameters or
“C” (Configuration)
- in the event of alarm:
silences the audible alarm
(buzzer) and disables the
alarm relay
PRG+ON-OFF/UP:
if pressed together
for more than 3
s reset any alarm
with manual reset
if pressed for
more than 5
s at start-up,
starts the
default
parameter
setting
if pressed for 1
s enters the au-
tomatic serial ad-
dress assigning
procedure
ON-OFF/
UP
- if pressed for more than 3s
disables the regulation / if
pressed for more than 1s,
enables the regulation
- during the parameters
modification increase the
value displayed move to-
wards the next paramenter
ON-OFF/UP+AUX/DOWN: if pressed together for
more than 3 s enable/disable the continuous cycle
operation
ON- OFF/UP+ SET/DEF: if pressed together for
more than 3 s display the temperature read by the
defrost probe no 1
ON-OFF/UP+ PRG/MUTE: if pressed together for
more than 3 s reset any alarm with manual reset
AUX/
DOWN
- if pressed for more than
1 s, enables/disables the
auxiliary output
- during the parameters
modification decrease the
value displayed or move
towards the previous param.
AUX/DOWN + ON-OFF/UP: if pressed together for
more than 3 s enable/disable the continuous cycle
operation
AUX/DOWN + SET/DEF: if pressed together for more
than 1 s display a submenu with the HACCP alarm
parameters (HA, HAn, HF, HFn)
SET/DEF - if pressed for more than 1s,
enables/displays and/or
set the set point
- if pressed for more than 5 s,
enables a manual defrost
SET/DEF+ AUX/DOWN: if pressed together for more
than 1 s display a submenu with the HACCP alarm
parameters (HA, HAn, HF, HFn)
SET/DEF+ ON-OFF/UP: if pressed together for
more than 3 s display the temperature read by the
defrost probe no 1
Table of alarms and signals: display, buzzer and relay
Code Display icon Alarm
relay
Buzzer Reset Description
‘rE’ + flashing ON ON automatic virtual control probe fault
‘E0’ + flashing OFF OFF automatic room probe S1 fault
‘E1’ + flashing OFF OFF automatic defrost probe S2 fault
‘E2’-3-4 + flashing OFF OFF automatic probe S3-4-5 fault
‘___’ no OFF OFF automatic probe not enabled
‘LO’ flashing ON ON automatic low temperature alarm
‘HI’ flashing ON ON automatic high temperature alarm
‘AFr ’ flashing ON ON manual antifreeze alarm
‘IA’ flashing ON ON automatic immediate alarm from external
contact
‘dA’ flashing ON ON automatic delayed alarm from external contact
‘dEF’ ON OFF OFF automatic defrost running
‘Ed1’-2 no OFF OFF automatic/
manual
defrost on evaporator 1-2 ended by
timeout
‘Pd’ + flashing ON ON automatic/
manual
maximum time pump-down alarm
‘LP’ + flashing ON ON automatic/
manual
low pressure alarm
‘AtS’ + flashing ON ON automatic/
manual
autostart in pump-down
‘cht’ no OFF OFF automatic/
manual
high condenser temperature pre-
alarm
‘CHT’ + flashing ON ON manual high condenser temperature alarm
‘dor’ flashing ON ON automatic door open for too long alarm
‘Etc’ flashing OFF OFF real time claock fault
‘EE’ + flashing OFF OFF automatic EEPROM error, unit parameters
‘EF’ + flashing OFF OFF automatic EEPROM error, operating parameters
‘HA’ flashing OFF OFF manual HACCP alarm, type ‘HA’
‘HF’ flashing OFF OFF manual HACCP alarm, type ‘HF’
‘rCt’ signal Instrument enabled for program-
ming from the remote control (not
available on ir33+)
‘Add’ signal Automatic address assignment
procedure in progress
‘ccb’ signal Request to start continuous cycle
‘ccE’ signal Request to end continuous cycle
‘dFb’ signal Request to start defrost
‘dFE’ signal Request to end defrost
‘On’ signal Switch ON
‘OFF’ signal Switch OFF
‘rES’ signal Reset alarms with manual reset;
Reset HACCP alarms; Reset tempera-
ture monitoring
‘n1’...‘n6’ flashing ON ON automatic Indicates an alarm on unit 1 to 6
present in the network
‘dnL’ signal Download in progress
‘d1’...‘d6’ flashing OFF OFF Download with errors on unit 1 to 6
Note: the buzzer is disabled if parameter‘H4 =1
Fig. 1
Fig. 2
How to set the set point (desired temperature value)
Step Action Effect Meaning
1Press for 1 second
After 1 second the display will
show the current set point
This the currently active
control set point
2Press or
The value on the display will
increase or decrease Set the desired value
3Press
The controller will show the tem-
perat. read by the probes again
The set point is modi-
fied and saved
Another way of changing the set point is to set parameter“St” (see the tables below)
How to access and set parameters
type “F” (FREQUENT, not protected by password)
type “C” (CONFIGURATION, password protected)
Step Action Effect Meaning
1Press for 3 seconds
After 3s the display will
show the 1st parameter, “0”
(password)
Access to type “F” param. is
direct without password
2Press or
The value on the display will
increase or decrease.
Enter the password“22” to
access the type “C” param.
or whatever different value
for the type “F” parameters.
3Press
The display will show “St”
(Setpoint)
This is the current value of
the Setpoint
4Press or
If the password set is 22 the
display will scroll the list of type
“C” parameters (CONFIGURA-
TION) otherwise the list of type
“F” parameters (FREQUENT )
Set the desired value
5Press
The display will show the
parameter name
This is the current value of
the parameter
6Press or
The value on the display will
increase or decrease Set the desired value
7Press
The display will show the
parameter name again
Important: parameters not
yet saved
8
Repeat steps 2, 3, 4 &
5 for all parameters
required
9Press for 5
seconds
The controller will display
the temperature read by the
probes again
Important: only now have
all the parameters been
updated
For both types of access (type “F” and type “C”) there is a timeout (no button on the keypad
pressed for 1 min), the procedure is ended without saving the parameter.
Accessing the parameters divided by functional blocks (allows the user to scroll
the list of parameters in blocks)
Once having accessed the type “F” or “C” parameters (see tables above)
Step Action Effect Meaning
1Press
The display will show the name
of the functional block that the
parameter belongs to
Example ‘CMP’ for the com-
pressor parameters,‘dEF’ for
the defrost parameters
2Press or
The display will show the name
of the other functional blocks
Example ‘Fan’ for the fan
parameters
3Press
The display will show the name
of the first parameter in the
functional block selected
Example “F0” for ‘Fan’
Alarms with manual reset:
the alarms with manual reset can be reset by pressing the and for more than 3 s.
Manual defrost:
as well as the automatic defrost function, a manual defrost can be enabled, if the tempera-
ture conditions allow, by pressing the button for more than 5 s.
HACCP function:
ir33+ is compliant with the HACCP standards in force since it allows the monitoring of the
temperature of the stored food.
“HA” alarm = exceeded maximum threshold: up to three HA events are saved (HA, HA1,
HA2) respectively from the more recent (HA) to the oldest (HA2) and a HAn signal that di-
splays the number of occurred HA events.
“HF” alarm = power failure lasting over a minute and exceeded AH maximum threshold:
up to three HF events are saved (HF, HF1, HF2) respectively from the more recent (HF) to the
oldest (HF2) and a HFn signal that displays the number of occurred HF events.
HA/HF alarm setting: AH parameter (high temp. threshold); Ad and Htd (Ad+Htd = HACCP
alarm activation delay).
Display of the details:
access to HA or HF parameters pressing the button and use or buttons to
glance over.
HACCP alarm erasing:
press the and buttons for more than 5 seconds, the message‘res’indicates that the
alarm have been deleted. To cancel the saved alarms press the + + buttons for
more than 5 seconds.
Continuous cycle:
Pressing the buttons and simultaneously for more than 3 s enables the continuous
cycle function. During operation in continuous cycle, the compressor continues to operate
for the time ‘cc’ and it stops when reaches the ‘cc’ time out or the minimum temperature
envisaged (AL = minimum temperature alarm threshold).
Continuous cycle setting: “cc” parameter (continuous cycle duration): “cc” = 0 never acti-
ve; “c6” parameter (bypassing the alarm after the continuous cycle): “cc” = 0 never active; it
avoids or delays the low temperature alarm after the continuous cycle.
Procedure for setting the default parameter values
To set the default parameter values on the controller, proceed as follows:
1: switch the instrument off;
2: switch the instrument back on, holding the button until the message “Std” is shown
on the display.
Note: the default values are only set for the visible parameters (C and F). For further details
see table “Summary of operating parameters”.
Fig. 3

+05Z0028EN- rel. 1.0 - 13.03.2014
CAREL INDUSTRIES HQs
Via dell’Industria, 11 - 35020 Brugine - Padova (Italy)
CAREL reserves the right to modify the features of its products without prior notice.
Parameters
Default settings table
Part number Def. settings Part number Def. settings Part number Def. settings
IREVM0LN0U - IREVC0LN0U Def. 2 IREVF0EN0U Def. 2
IREVM0EN0U - IREVC0LC0U Def. 2
IREVS0LN0U Def. 1 IREVC0HN0U Def. 2
IREVS0EA0U Def. 1 IREVC0HC0U Def. 2
Summary of operating parameters (UOM = Unit of measure; Def. = Default value)
Symbol Code Parameter Mod. UOM Type Min. Max. Def.
Pw Password MSYF - C 0 200 22
/2 Measurement stability MSYF - C 1 15 4
/3 Probe display response MSYF - C 0 15 0
/4 Virtual probe MSYF - C 0 100 0
/5 Selection °C o °F (0: °C ,1: °F) MSYF flag C 0 1 0
/6 Display decimal point 0= YES, 1=NO MSYF flag C 0 1 0
/tI Display on internal terminal
1: virtual probe; 5: probe 4
2: probe 1 6: probe 5
3: probe 2 7: set point
4: probe 3
MSYF - C 1 7 1
/tE Display on external terminal remote terminal not present
1: virtual probe 4: probe 3
2: probe 1 5: probe 4
3: probe 2 6: probe 5
MSYF - C 0 6 0
/P Select type of probe
0: NTC standard with range -50T90°C
1: NTC enhanced with range -40T150°C
MSYF - C 0 2 0
/A2 Configuration of probe 2 (S2)
0: probe absent 3: condenser probe
1: product probe (display only) 4: antifreeze probe
2: defrost probe
MS
YF
-
-
C
C
0
0
4
4
0
2
/A3 Configuration of probe 3 (S3/DI1) As for /A2 MSYF - C 0 4 0
/A4 Configuration of probe 4 (S4/DI2) As for /A2 MSYF - C 0 4 0
/c1 Calibration of probe 1 MSYF °C/°F C -20 20 0.0
/c2 Calibration of probe 2 MSYF °C/°F C -20 20 0.0
/c3 Calibration of probe 3 MSYF °C/°F C -20 20 0.0
/c4 Calibration of probe 4 MSYF °C/°F C -20 20 0.0
St Temperature Set Point MSYF °C/°F F r1 r2 Def 1 Def 2
2 -18
rd Control delta (differential) SYF °C/°F F 0,1 20 2,0
r Dead band SYF °C/°F C 0,0 60 4,0
rr Reverse differential for control with dead band SYF °C/°F C 0,1 20 2,0
r1 Minimum set point allowed MSYF °C/°F C -50 r2 -50
r2 Maximum set point allowed MSYF °C/°F C r1 200 60
r3 Operating mode
0: Direct (cooling) with defrost control
1: Direct (cooling)
2: Reverse-cycle (heating)
SYF flag C 0 2 0
r4 Automatic night-time set point variation MSYF °C/°F C -20 20 3,0
r5 Enable temperature monitoring: 0: disabled, 1: enabled MSYF flag C 0 1 0
rt Temperature monitoring interval MSYF hr F 0 999 -
rH Maximum temperature read MSYF °C/°F F - - -
rL Minimum temperature read MSYF °C/°F F - - -
c0 Compressor, fan and AUX delay on start-up SYF min C 0 15 0
c1 Minimum time between successive starts SYF min C 0 15 0
c2 Min. compressor OFF time SYF min C 0 15 2
c3 Minimum compressor ON time SYF min C 0 15 0
c4 Duty setting SYF min C 0 100 0
cc Continuous cycle duration SYF hr C 0 15 0
c6 Alarm bypass after continuous cycle SYF hr C 0 250 2
c7 Maximum pump down time SYF s C 0 900 0
c9 Enable autostart function in PD SYF flag C 0 1 0
c10 Select Pump down by time or pressure
0: Pump down by pressure; 1: Pump down by time
SYF flag C 0 1 0
c11 Second compressor delay SYF s C 0 250 4
d0 Type of defrost
0: Electric heater defrost by temperature
1: Hot gas defrost by temperature
2: Electric heater defrost by time
3: Hot gas defrost by time
4: Electric heater defrost thermostat by time
SYF flag C 0 4 0
dI Interval between defrosts SYF hr F 0 250 8
dt1 End defrost temperature, evaporator SYF °C/°F F -50 200 4,0
dt2 End defrost temperature, aux evaporator SYF °C/°F F -50 200 4,0
dP1 Maximum defrost duration, evaporator SYF min F 1 250 30
dP2 Maximum defrost duration, aux evaporator SYF min F 1 250 30
d3 Defrost start delay SYF min C 0 250 0
d4 Enable defrost on start-up
0: No defrost when the instrument is switched on
1: A defrost is performed when the instrument is
switched on
SYF flag C 0 1 0
d5 Defrost delay on start-up SYF min C 0 250 0
d6 Display on hold during defrost
0: Alternating display of dEF and probe value
1: Display of the last temp. shown
2: Display of dEF steady
SYF - C 0 2 1
dd Dripping time after defrost SYF min F 0 15 2
d8 Alarm bypass after defrost SYF hr F 0 250 1
d8d Alarm bypass after door open SYF min C 0 250 0
d9 Defrost priority over compressor protectors
0: The protection times c1, c2 and c3 are observed
1: The protection times c1, c2 and c3 are not observed
SYF flag C 0 1 0
d/1 Display of defrost probe 1 MSYF °C/°F F - - -
d/2 Display of defrost probe 2 MSYF °C/°F F - - -
dC Time base for defrost
0: dI in hours, dP1 and dP2 in minutes
1: dI in minutes, dP1 and dP2 in seconds
SYF flag C 0 1 0
d10 Compressor running time SYF hr C 0 250 0
d11 Running time temperature threshold SYF °C/°F C -20 20 1,0
d12 Advanced defrost SYF - C 0 3 0
dn Nominal defrost duration SYF - C 1 100 65
dH Proportional factor, variation in dI SYF - C 0 100 50
A0 Alarm and fan differential MSYF °C/°F C 0,1 20 2,0
A1 Type of threshold ‘AL’ and ‘AH’
0: AL and AH are relative thresholds to the set point
1: AL and AH are absolute thresholds
MSYF flag C 0 1 0
AL Low temperature alarm threshold MSYF °C/°F F A1=1-50
(alarm ‘LO’
disabled)
A1=00
(alarm ‘LO’
disabled)
200 0,0
AH High temperature alarm threshold MSYF °C/°F F A1=1-50
A1=00
(alarm ‘HI’
disabled)
A1=1200
(alarm ‘HI’
disabled)
A1=0200
0,0
Ad Low and high temperature alarm delay MSYF min F 0 250 120
A4 Digital input 1 configuration (DI1)
0: Input not active
1: Immediate external alarm
2: Delayed external alarm
3: If model M, probe selection
3: Other models enable defrost
4: Start defrost
5: Door switch with compressor and fan stop - light managed
6: Remote ON/OFF
7: Curtain switch
8: Low pressure switch
9: Door switch with fan stop only- light managed
10: Direct/reverse
11: Light sensor
12: Activation of the AUX output
13: Door switch with compressor and fans off and light not
managed
14: Door switch with fans only off and light not managed
SYF
M
-
-
C
C
0
0
14
14
0
3
A5 Digital input 2 configuration (DI2) / As for A4 MSYF - C 0 14 0
A6 Stop compressor from external alarm SYF min C 0 100 0
Disposal of the product
The appliance (or the product) must be disposed of separately in compliance with the local standards in force on waste disposal.
Important warnings:
The CAREL product is a state-of-the-art device, whose operation is specified in the technical documentation supplied with the product or
can be downloaded, even prior to purchase, from the website www.carel.com. The customer (manufacturer, developer or installer of the final
equipment) accepts all liability and risk relating to the configuration of the product in order to reach the expected results in relation to the
specific final installation and/or equipment. The failure to complete such phase, which is required/indicated in the user manual, may cause the
final product to malfunction; CAREL accepts no liability in such cases. The customer must use the product only in the manner described in the
documentation relating to the product. The liability of CAREL in relation to its products is specified in the CAREL general contract conditions,
available on the website www.carel.com and/or by specific agreements with customers.
WARNING: separate as much as possible the probe and digital input signal cables from the cables carrying inductive loads and power
cables to avoid possible electromagnetic disturbance. Never run power cables (including the electrical panel wiring) and signal cables
in the same conduits.
NOPOWER
& SIGNAL
CABLES
TOGETHER
READCAREFULLY IN THE TEXT!
Symbol Code Parameter Mod. UOM Type Min. Max. Def.
A7 External alarm detection delay SYF min C 0 250 0
A8 Enable alarms ‘Ed1’ and ‘Ed2’
A8=0 --> Alarm signals Ed1 and Ed2 disabled
A8=1 --> Alarm signals Ed1 and Ed2 enabled
SYF flag C 0 1 0
Ado Light management mode with door switch MSYF flag C 0 1 0
Ac High condenser temperature alarm SYF °C/°F C 0,0 200 70
AE High condenser temperature alarm differential SYF °C/°F C 0,1 20 10
Acd High condenser temperature alarm delay SYF min C 0 250 0
AF Light sensor OFF time SYF s C 0 250 0
ALF Antifreeze alarm threshold MSYF °C/°F C -50 200 -5
AdF Antifreeze alarm delay MSYF min C 0 15 1
F0 Fan management
0: Fans always on
1: Fans controlled according to the temperature differen-
ce between the virtual control probe and the evaporator
temperature
2: Fans controlled according to the evaporator temperature
FflagC 0 2 0
F1 Fan start temperature F °C/°F F -50 200 5
F2 Fan OFF with compressor OFF
0: Fans always on; 1: Fans off with compressor off
FflagC 0 1 0
F3 Fans in defrost
0: Fans operate during defrosts; 1: Fans do not operate
during defrosts
FflagC 0 1 1
Fd Fan Delay after dripping F min F 0 15 1
F4 Condenser fan stop temperature MSYF °C/°F C -50 200 40
F5 Condenser fan start differential MSYF °C/°F C 0,1 20 5
H0 Serial address MSYF - C 0 207 195
H1 Function of AUX output
0: Alarm output normally energised
1: Alarm output normally de-energised
2: Auxiliary output
3: Light output
4: Auxiliary evaporator defrost output
5: Pump down valve output
6: Condenser fan output
7: Delayed compressor output
8: Auxiliary output with deactivation when OFF
9: Light output with deactivation when OFF
10: No function associated with the output
11: Reverse output in control with dead band
12: Second compressor step output
13: Second compressor step output with rotation
MSYF flag C 0 13 1
H2 Disable keypad
Parameter
“H2”
LIGHT
ON/OFF
AUX
HACCP
PRG/MUTE
(mute)
UP/CC
DOWN/DEF
SET
parameter F
modication
Set point
modication
0••
1
2••
3
4••••
5•••••
6•• • •
Keypad function “•”= Disabled
MSYF flag C 0 6 1
H4 Disable buzzer: 0: Buzzer enabled: 1: Buzzer disabled MSYF flag C 0 1 0
H6 Lock keypad MSYF - C 0 255 0
H8 Select activation of output with time band
0: Time band linked to output configured for light
1: Time band linked to output configured for aux
MSYF flag C 0 1 0
H9 Enable set point variation with time band
0: Set point variation with time band disabled
1: Set point variation with time band enabled
MSYF flag C 0 1 0
Hdh Anti-sweat heater offset MSYF °C/°F C -50 200 0
HAn Number of HA events recorded MSYF - C 0 15 0
HA
y__
M__
d__
h__
n__
t__
Date/time of last HA event
Year
Month
Day
Hour
Minute
Duration
MSYF -
years
months
days
hours
min
hours
C
0
1
1
0
0
0
-
99
12
7
23
59
99
-
0
0
0
0
0
0
HA1 Date/time of penultimate HA event MSYF - C - - -
HA2 Date/time of third-to-last HA event MSYF - C - - -
HFn Number of HF events recorded MSYF - C 0 15 0
HF
y__
M__
d__
h__
n__
t__
Date/time of last HF event
Year
Month
Day
Hour
Minute
Duration
MSYF -
years
months
days
hours
min
hours
C
0
1
1
0
0
0
-
99
12
7
23
59
99
-
0
0
0
0
0
0
HF1 Date/time of penultimate HF event MSYF - C - - -
HF2 Date/time of third-to-last HF event MSYF - C - - -
Htd HACCP alarm delay MSYF min C 0 250 0
td1
d__
h__
n__
Defrost time band 1
Day
Hour
Minute
SFY -
days
hours
min
C-
0
0
0
-
11
23
59
-
0
0
0
td2 Defrost time band 2 SFY - C - - -
td3 Defrost time band 3 SFY - C - - -
td4 Defrost time band 4 SFY - C - - -
td5 Defrost time band 5 SFY - C - - -
td6 Defrost time band 6 SFY - C - - -
td7 Defrost time band 7 SFY - C - - -
td8 Defrost time band 8 SFY - C - - -
ton
d__
h__
n__
Light/aux on time band, set point variance
Day
Hour
Minute
SFY -
days
hours
min
C-
0
0
0
-
11
23
59
-
0
0
0
toF
d__
h__
n__
Light/aux off time band, set point variance
Day
Hour
Minute
SFY -
days
hours
min
C-
0
0
0
-
11
23
59
-
0
0
0
tc
y__
M__
d__
u__
h__
n__
RTC date/time setting
Year
Month
Day of the month
Day of the week
Hour
Minute
MSYF -
years
months
days
days
hours
min
-
0
1
1
1
0
0
-
99
12
31
7
23
59
-
0
1
1
6
0
0
Important: for the set times to become immediately operational, the instrument must be turned off and on again.
Other manuals for ir33+
3
Other Carel Controllers manuals

Carel
Carel PZD0SNP0E1 User manual

Carel
Carel uAM User manual

Carel
Carel FCM series User manual

Carel
Carel pCO2 Series User manual

Carel
Carel PCOC000AM0 User manual

Carel
Carel MCHRTF Series User manual

Carel
Carel UltraCella Instruction Manual

Carel
Carel thTx User manual

Carel
Carel ir33+ VCC Series User manual

Carel
Carel ADCD000110 User manual

Carel
Carel ADP 30 pAD Series User manual

Carel
Carel supernode Manual

Carel
Carel PCOXS User manual

Carel
Carel mboss Manual

Carel
Carel boss Series User manual

Carel
Carel mchiller compact User manual

Carel
Carel ir33+ Installation manual

Carel
Carel pCO1 series User manual

Carel
Carel pCO5 Manual

Carel
Carel FCPM0420A0 User manual